 "manufacturer": "Yokogawa",
 "manufacturer_slug": "yokogawa",
 "model": "UTAdvanced UT35A-L limit controller",
 "model_slug": "ut35a-l",
 "short_model": "UT35A-L",
 "aliases": [
  "UT35A-L"
 ],
 "equipment_type": "Sensor (limit controller)",
 "applies_to": "Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.",
 "summary": "The UT35A-L is a high/low limit controller in Yokogawa's UTAdvanced family that trips an output relay when the PV passes its limit setpoint. Its D registers map one-to-one onto Modbus holding registers. This map covers the process monitoring block: PV, limit setpoint, exceed and relay status, alarms, latches, exceed duration time and PV peak value.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual lists D register numbers; the Modbus reference is the D number with D replaced by 4 (D2003 = 42003) and the wire address is that minus 40001, as printed in the H No. column (07D2H)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual",
  "doc_number": "IM 05P07A01-01EN 13th Edition",
  "revision_date": "2026-03",
  "url": "https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf",
  "pages": "D register addressing p. 3-4; serial settings p. 2-1; UT35A-L process data pp. 12-4 to 12-9"
 },
 "notes": [
  "All registers are 16-bit and read-only in this block (D2001-D2100).",
  "PV is sent without its decimal point; the position follows the input's decimal point setting.",
  "Alarm setpoints and setup parameters (D2501 onward) are not included in this map.",
  "Current SP group registers (D2101-D2200) are not included."
 ],
 "integration": {
  "summary": "Use the factory Modbus RTU setting, then read D2001-D2008 for errors, PV, limit setpoint and the exceed/relay status bits.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2002,
    "why": "PV (D2003)"
   },
   {
    "table": "holding_register",
    "address": 2001,
    "why": "PV input error flags (D2002)"
   },
   {
    "table": "holding_register",
    "address": 2003,
    "why": "Limit setpoint (D2004)"
   },
   {
    "table": "holding_register",
    "address": 2007,
    "why": "Exceeded / output relay (D2008)"
   },
   {
    "table": "holding_register",
    "address": 2010,
    "why": "Alarm status (D2011)"
   },
   {
    "table": "holding_register",
    "address": 2036,
    "why": "Alarm output status (D2037)"
   }
  ],
  "enable": "Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).",
  "watchdog": null,
  "quirks": [
   "Wire address = D number - 1 (D2003 = 07D2H)."
  ],
  "setup": [
   "Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1."
  ],
  "gotchas": [
   "Reading undefined (blank) D registers is not allowed and can upset the unit."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "D2001",
   "name": "AD1.E A/D converter error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "PV input A/D converter error",
    "5": "PV input RJC error",
    "8": "PV input burnout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "D2002",
   "name": "PV1.E_L1 PV input error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "PV input burnout",
    "4": "PV over-scale",
    "5": "PV under-scale"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "D2003",
   "name": "PV_L1 measured value",
   "description": "-5 to 105 % of input range, engineering value without decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "D2004",
   "name": "CSP_L1 control (limit) setpoint",
   "description": "Setpoint in engineering units without decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "D2008",
   "name": "MOD_L1 operation status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "12": "Limit exceeded",
    "13": "Output relay ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "D2011",
   "name": "ALM_L1 alarm 1-3 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 ON",
    "1": "Alarm 2 ON",
    "2": "Alarm 3 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2036,
   "documented": "D2037",
   "name": "ALO_L1 alarm output 1-3 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm output 1 contact closed",
    "1": "Alarm output 2 contact closed",
    "2": "Alarm output 3 contact closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2065,
   "documented": "D2066",
   "name": "DIMG message display status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Message 1 displayed",
    "1": "Message 2 displayed",
    "2": "Message 3 displayed",
    "4": "Message 4 displayed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2067,
   "documented": "D2068",
   "name": "PA.ER parameter error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "System data error",
    "1": "Calibration value error",
    "2": "User default value error",
    "4": "Setup parameter error",
    "5": "Operation parameter error",
    "8": "Faulty FRAM",
    "10": "Control parameter error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2069,
   "documented": "D2070",
   "name": "OP.ER option error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "E3 terminal hardware not responding",
    "10": "E3 communication error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2070,
   "documented": "D2071",
   "name": "ALOLA1_L1 alarm latch-1 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-1",
    "1": "Alarm 2 latch-1",
    "2": "Alarm 3 latch-1"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2072,
   "documented": "D2073",
   "name": "ALOLA2_L1 alarm latch-2 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-2",
    "1": "Alarm 2 latch-2",
    "2": "Alarm 3 latch-2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2074,
   "documented": "D2075",
   "name": "ALOLA3_L1 alarm latch-3 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-3",
    "1": "Alarm 2 latch-3",
    "2": "Alarm 3 latch-3"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2076,
   "documented": "D2077",
   "name": "ALOLA4_L1 alarm latch-4 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-4",
    "1": "Alarm 2 latch-4",
    "2": "Alarm 3 latch-4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2080,
   "documented": "D2081",
   "name": "TIME duration time",
   "description": "Duration time; unit set by parameter TMU (1 h 38 min 57 s reads 5937 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2081,
   "documented": "D2082",
   "name": "MAX/MIN PV peak value",
   "description": "Maximum or minimum PV per the HI.LO limit type; no decimal point sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/yokogawa/ut35a-l",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}