 "manufacturer": "Yokogawa",
 "manufacturer_slug": "yokogawa",
 "model": "UTAdvanced UT35A / UT32A digital indicating controller",
 "model_slug": "ut35a-ut32a",
 "short_model": "UT35A/UT32A",
 "aliases": [
  "UT35A",
  "UT32A",
  "UT35A/MDL",
  "UT32A/MDL"
 ],
 "equipment_type": "Sensor (digital indicating temperature controller)",
 "applies_to": "Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).",
 "summary": "The UT35A and UT32A are single-loop PID controllers in Yokogawa's UTAdvanced family. Their data live in D registers that map one-to-one onto Modbus holding registers, reachable over RS-485 (Modbus RTU/ASCII) or, on Ethernet models, Modbus/TCP. This map covers the process data block (PV, setpoint, outputs, status words), the current SP/PID group and the operation-mode switches.",
 "transport": [
  "RTU",
  "ASCII",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual",
  "doc_number": "IM 05P07A01-01EN 13th Edition",
  "revision_date": "2026-03",
  "url": "https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf",
  "pages": "D register addressing p. 3-4; serial settings section 2.1 (p. 2-1); D register tables pp. 8-6 to 8-21"
 },
 "notes": [
  "All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).",
  "D2001-D2100 are read-only; registers marked as group items (D2101-D2135) act on the SP/PID group currently in use.",
  "UT32A-D loop-2, UP35A/UP32A program-pattern and GREEN-series compatible (D0001-D2000) registers are not included.",
  "Only part of the D-register space is listed; setup and operation parameter areas (D2501 onward) are left out.",
  "Up to 100 registers per read and 50 per multi-register write; blank (undefined) addresses must not be read or written.",
  "Modbus/TCP applies only to UT35A units with the Ethernet option; the UT32A is serial only."
 ],
 "integration": {
  "summary": "Set protocol MBRTU (factory default) and an address, then read D2001-D2012 in one block for status, PV, SP and output, write the target setpoint to D2101 and switch AUTO/MAN and RUN/STOP with D2301 and D2304.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2002,
    "why": "PV (D2003)"
   },
   {
    "table": "holding_register",
    "address": 2003,
    "why": "Control setpoint (D2004)"
   },
   {
    "table": "holding_register",
    "address": 2004,
    "why": "Control output (D2005)"
   },
   {
    "table": "holding_register",
    "address": 2007,
    "why": "Operation mode status (D2008)"
   },
   {
    "table": "holding_register",
    "address": 2010,
    "why": "Alarm status (D2011)"
   },
   {
    "table": "holding_register",
    "address": 2100,
    "why": "Target setpoint (D2101)"
   },
   {
    "table": "holding_register",
    "address": 2300,
    "why": "AUTO/MAN (D2301)"
   },
   {
    "table": "holding_register",
    "address": 2303,
    "why": "RUN/STOP (D2304)"
   }
  ],
  "enable": "Set the communication setup parameters PSL (protocol, MBRTU or MBASC), BPS, PRI, STP, DLN and ADR on the keypad. Ethernet models use Modbus/TCP on port 502 by default.",
  "watchdog": null,
  "quirks": [
   "Address D register n at wire address n-1 (D2101 = 0834H).",
   "Writing values with a decimal point: send the integer without it (50.0 with one decimal place = 500)."
  ],
  "setup": [
   "Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1. Speeds 600-38400 bps (38400 only on suffix types that allow it)."
  ],
  "gotchas": [
   "Available registers depend on the suffix code and parameter settings; check the model before writing."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "D2001",
   "name": "AD1.E A/D converter error status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "PV input A/D converter error",
    "5": "PV input RJC error",
    "8": "PV input burnout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "D2002",
   "name": "PV1.E_L1 PV input error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "PV input burnout",
    "4": "PV over-scale",
    "5": "PV under-scale",
    "14": "Auto-tuning timeout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "D2003",
   "name": "PV_L1 measured value",
   "description": "Engineering value without decimal point; position set by the PV decimal point parameter.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "D2004",
   "name": "CSP_L1 control setpoint",
   "description": "Engineering value without decimal point; position set by the PV decimal point parameter.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2004,
   "documented": "D2005",
   "name": "OUT_L1 control output",
   "description": "-5.0 to 105.0 %; valve opening in position-proportional control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2005,
   "documented": "D2006",
   "name": "H.OUT_L1 heating-side output",
   "description": "Heating/cooling control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "D2007",
   "name": "C.OUT_L1 cooling-side output",
   "description": "Heating/cooling control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "D2008",
   "name": "MOD_L1 operation mode status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Manual (0 = AUTO)",
    "1": "Remote (0 = Local)",
    "2": "Stop (0 = Run)",
    "8": "Output tracking",
    "14": "Auto-tuning on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "D2009",
   "name": "PID_L1 current PID number",
   "description": "Bits 0-2 give the PID number; 0 when reference PID (R) is used.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2009,
   "documented": "D2010",
   "name": "CSPNO. current SP number",
   "description": "Bits 0-2 give the control setpoint number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "D2011",
   "name": "ALM_L1 alarm status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 ON",
    "1": "Alarm 2 ON",
    "2": "Alarm 3 ON",
    "4": "Alarm 4 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2011,
   "documented": "D2012",
   "name": "LA.ER ladder error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Corrupted ladder program",
    "1": "Ladder calculation overflow",
    "2": "Ladder program error",
    "4": "Load factor over 100 %",
    "5": "Load factor over 200 % (forced end)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2034,
   "documented": "D2035",
   "name": "DEV_L1 deviation",
   "description": "-105.0 to 105.0 % of PV span; no decimal point sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2036,
   "documented": "D2037",
   "name": "ALO_L1 alarm output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm output 1 contact closed",
    "1": "Alarm output 2 contact closed",
    "2": "Alarm output 3 contact closed",
    "4": "Alarm output 4 contact closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2060,
   "documented": "D2061",
   "name": "HC1 heater break current 1",
   "description": "0.0 to 360.0 A rms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2061,
   "documented": "D2062",
   "name": "HC2 heater break current 2",
   "description": "0.0 to 360.0 A rms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2062,
   "documented": "D2063",
   "name": "CT_AL heater break alarm status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Heater break alarm 1 ON",
    "1": "Heater break alarm 2 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2063,
   "documented": "D2064",
   "name": "VALV valve status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Estimating-type operation (0 = feedback)",
    "1": "Open output on",
    "2": "Close output on",
    "3": "Automatic valve position adjustment"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2064,
   "documented": "D2065",
   "name": "AD2.E A/D converter error status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Feedback input burnout",
    "1": "Valve position auto adjustment error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2067,
   "documented": "D2068",
   "name": "PA.ER parameter error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "System data error",
    "1": "Calibration value error",
    "2": "User default value error",
    "4": "Setup parameter error",
    "5": "Operation parameter error",
    "8": "Faulty FRAM",
    "10": "Control parameter error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2069,
   "documented": "D2070",
   "name": "OP.ER option error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "E1 terminal hardware not responding",
    "2": "E3 terminal hardware not responding",
    "4": "E4 terminal hardware not responding",
    "8": "E1 communication error (UT32A)",
    "10": "E3 communication error (UT35A)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2070,
   "documented": "D2071",
   "name": "ALOLA1_L1 alarm latch-1 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-1",
    "1": "Alarm 2 latch-1",
    "2": "Alarm 3 latch-1",
    "4": "Alarm 4 latch-1"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2072,
   "documented": "D2073",
   "name": "ALOLA2_L1 alarm latch-2 output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 latch-2",
    "1": "Alarm 2 latch-2",
    "2": "Alarm 3 latch-2",
    "4": "Alarm 4 latch-2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "D2101",
   "name": "SP_L1 target setpoint",
   "description": "Engineering value without decimal point; position set by the PV decimal point parameter.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "D2102",
   "name": "SUB sub-target setpoint",
   "description": "Offset from SP, two-position two-level control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2102,
   "documented": "D2103",
   "name": "PIDN_L1 PID number selection",
   "description": "PID group 1-4 used by the current SP group.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "D2104",
   "name": "A1_L1 alarm-1 setpoint",
   "description": "-19999 to 30000; decimal point follows the input.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2104,
   "documented": "D2105",
   "name": "A2_L1 alarm-2 setpoint",
   "description": "-19999 to 30000; decimal point follows the input.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2105,
   "documented": "D2106",
   "name": "A3_L1 alarm-3 setpoint",
   "description": "-19999 to 30000; decimal point follows the input.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2106,
   "documented": "D2107",
   "name": "A4_L1 alarm-4 setpoint",
   "description": "-19999 to 30000; decimal point follows the input.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2113,
   "documented": "D2114",
   "name": "P_L1 proportional band",
   "description": "0.0-999.9 %. Current SP/PID group.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2114,
   "documented": "D2115",
   "name": "I_L1 integral time",
   "description": "0 = OFF, 1-6000 s. Current SP/PID group.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2115,
   "documented": "D2116",
   "name": "D_L1 derivative time",
   "description": "0 = OFF, 1-6000 s. Current SP/PID group.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2116,
   "documented": "D2117",
   "name": "OH_L1 output high limit",
   "description": "-4.9 to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2117,
   "documented": "D2118",
   "name": "OL_L1 output low limit",
   "description": "-5.0 to 104.9 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2118,
   "documented": "D2119",
   "name": "MR_L1 manual reset",
   "description": "Used when integral time is OFF.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2123,
   "documented": "D2124",
   "name": "DR_L1 direct/reverse action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RVS (reverse)",
    "1": "DIR (direct)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2125,
   "documented": "D2126",
   "name": "Pc_L1 cooling-side proportional band",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2126,
   "documented": "D2127",
   "name": "Ic_L1 cooling-side integral time",
   "description": "0 = OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2127,
   "documented": "D2128",
   "name": "Dc_L1 cooling-side derivative time",
   "description": "0 = OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2128,
   "documented": "D2129",
   "name": "OHc_L1 cooling-side output high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2129,
   "documented": "D2130",
   "name": "OLc_L1 cooling-side output low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2132,
   "documented": "D2133",
   "name": "PO_L1 preset output",
   "description": "Output used in STOP mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2300,
   "documented": "D2301",
   "name": "A.M AUTO/MAN switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "1": "MAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2303,
   "documented": "D2304",
   "name": "S.R STOP/RUN switch",
   "description": "Preset output is used in STOP.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "STOP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2305,
   "documented": "D2306",
   "name": "R.L_L1 REMOTE/LOCAL switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "LCL (local)",
    "1": "REM (remote)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2307,
   "documented": "D2308",
   "name": "AT_L1 auto-tuning switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "AT to PID 1",
    "2": "AT to PID 2",
    "3": "AT to PID 3",
    "4": "AT to PID 4",
    "9": "AT to reference PID (R)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2311,
   "documented": "D2312",
   "name": "SPNO. SP number selection",
   "description": "1-4, limited by the SPGR. setup parameter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2313,
   "documented": "D2314",
   "name": "TRK_ON_L1 output tracking",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2330,
   "documented": "D2331",
   "name": "C.RSP_L1 communication remote setpoint",
   "description": "Engineering value without decimal point; position set by the PV decimal point parameter.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2332,
   "documented": "D2333",
   "name": "MOUT_L1 manual output",
   "description": "Output in MAN mode (heating side in heat/cool).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2333,
   "documented": "D2334",
   "name": "MOUTc_L1 cooling-side manual output",
   "description": "Heating/cooling control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/yokogawa/ut35a-ut32a",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}