 "manufacturer": "Yokogawa",
 "manufacturer_slug": "yokogawa",
 "model": "UTAdvanced UT75A digital indicating controller",
 "model_slug": "ut75a",
 "short_model": "UT75A",
 "aliases": [
  "UT75A"
 ],
 "equipment_type": "Sensor (digital indicating temperature controller)",
 "applies_to": "Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.",
 "summary": "The UT75A is the high-end UTAdvanced PID controller with up to two loops, 20 SP groups and a simple program function. Its data live in D registers that map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers the process data block, the current SP/PID group for both loops and the operation-mode switches.",
 "transport": [
  "RTU",
  "ASCII",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual",
  "doc_number": "IM 05P07A01-01EN 13th Edition",
  "revision_date": "2026-03",
  "url": "https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf",
  "pages": "D register addressing p. 3-4; D register classification p. 14-4; tables and descriptions pp. 14-6 to 14-20"
 },
 "notes": [
  "All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).",
  "D2001-D2100 are read-only. D2101-D2112 / D2151-D2163 act on the SP group in use (1-20); D2114-D2135 / D2164-D2185 on the PID group in use (1-16 or R).",
  "Program-operation registers (D2031, D2327-D2329, pattern area D7701-D7900), ramp-rate registers D2112/D2113 and the GREEN-series compatible area (D0001-D2000) are not included.",
  "Only part of the D-register space is listed; alarm setpoints 5-8, cooling-side PID terms, SP/PID groups 9-20 (D9001 onward) and the setup parameter areas (D2501 onward) are left out.",
  "Modbus/TCP applies only to units with the Ethernet communication option."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "D2001",
   "name": "AD1.E A/D converter error status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "PV input A/D converter error",
    "1": "PV2 input (E1) A/D converter error",
    "2": "AIN2 input (E2) A/D converter error",
    "4": "AIN4 input (E4) A/D converter error",
    "5": "PV input RJC error",
    "6": "PV2 input RJC error",
    "8": "PV input burnout error",
    "9": "PV2 input (E1) burnout error",
    "10": "AIN2 input (E2) burnout error",
    "12": "AIN4 input (E4) burnout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "D2002",
   "name": "PV1.E_L1 loop-1 PV input error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Loop-1 PV input burnout",
    "1": "Loop-1 PV2 input burnout",
    "2": "Burnout of loop-1 PV2 input used for control",
    "4": "Loop-1 PV over-scale",
    "5": "Loop-1 PV under-scale",
    "14": "Loop-1 auto-tuning timeout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "D2003",
   "name": "PV_L1 loop-1 measured value",
   "description": "Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "D2004",
   "name": "CSP_L1 loop-1 control setpoint",
   "description": "Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2004,
   "documented": "D2005",
   "name": "OUT_L1 loop-1 control output",
   "description": "-5.0 to 105.0 %; valve opening in position-proportional control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2005,
   "documented": "D2006",
   "name": "H.OUT_L1 heating-side output",
   "description": "Heating/cooling control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "D2007",
   "name": "C.OUT_L1 cooling-side output",
   "description": "0.0 to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "D2008",
   "name": "MOD_L1 loop-1 operation mode status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "A.M (0 AUTO, 1 MAN)",
    "1": "R.L (0 local, 1 remote)",
    "2": "S.R (0 run, 1 stop)",
    "4": "CAS (cascade modes)",
    "5": "AUTO (cascade modes)",
    "6": "MAN (cascade modes)",
    "8": "Output tracking",
    "14": "Auto-tuning ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "D2009",
   "name": "PID_L1 current PID number (loop 1)",
   "description": "Bits 0-4 hold the PID number; reads 0 for reference PID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2009,
   "documented": "D2010",
   "name": "CSPNO. current control setpoint number",
   "description": "Bits 0-4 hold the SP number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "D2011",
   "name": "ALM_L1 loop-1 alarm 1-8 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 ON (loop 1)",
    "1": "Alarm 2 ON",
    "2": "Alarm 3 ON",
    "4": "Alarm 4 ON",
    "5": "Alarm 5 ON",
    "6": "Alarm 6 ON",
    "8": "Alarm 7 ON",
    "9": "Alarm 8 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2011,
   "documented": "D2012",
   "name": "LA.ER ladder error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Corrupted ladder program",
    "1": "Ladder calculation overflow",
    "2": "Ladder program error",
    "4": "Load factor over 100 %",
    "5": "Load factor over 200 % (forced end)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2012,
   "documented": "D2013",
   "name": "ALM_L2 loop-2 alarm 1-8 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 ON (loop 2)",
    "1": "Alarm 2 ON",
    "2": "Alarm 3 ON",
    "4": "Alarm 4 ON",
    "5": "Alarm 5 ON",
    "6": "Alarm 6 ON",
    "8": "Alarm 7 ON",
    "9": "Alarm 8 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2017,
   "documented": "D2018",
   "name": "PV2.E_L2 loop-2 PV input error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Loop-2 PV input burnout",
    "1": "Loop-2 PV2 input burnout",
    "2": "Burnout of loop-2 PV2 input used for control",
    "4": "Loop-2 PV over-scale",
    "5": "Loop-2 PV under-scale",
    "14": "Loop-2 auto-tuning timeout error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2018,
   "documented": "D2019",
   "name": "PV_L2 loop-2 measured value",
   "description": "Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2019,
   "documented": "D2020",
   "name": "CSP_L2 loop-2 control setpoint",
   "description": "Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2020,
   "documented": "D2021",
   "name": "OUT_L2 loop-2 control output",
   "description": "-5.0 to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2021,
   "documented": "D2022",
   "name": "H.OUT_L2 loop-2 heating-side output",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2022,
   "documented": "D2023",
   "name": "C.OUT_L2 loop-2 cooling-side output",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2023,
   "documented": "D2024",
   "name": "MOD_L2 loop-2 operation mode status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "A.M_L2 (0 AUTO, 1 MAN)",
    "1": "R.L_L2 (0 local, 1 remote)",
    "2": "S.R_L2 (0 run, 1 stop)",
    "14": "Loop-2 auto-tuning ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2024,
   "documented": "D2025",
   "name": "PID_L2 current PID number (loop 2)",
   "description": "Bits 0-4 hold the PID number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2028,
   "documented": "D2029",
   "name": "SEG.N current program segment",
   "description": "0 = not executing, 1-20.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2029,
   "documented": "D2030",
   "name": "SEG_RTIME remaining segment time",
   "description": "0-59999; unit (min or s) set by TMU.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2034,
   "documented": "D2035",
   "name": "DEV_L1 loop-1 deviation",
   "description": "-105.0 to 105.0 % of span, sent as engineering value without decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2035,
   "documented": "D2036",
   "name": "DEV_L2 loop-2 deviation",
   "description": "Same format as DEV_L1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2036,
   "documented": "D2037",
   "name": "ALO_L1 loop-1 alarm output 1-8 status",
   "description": "1 = relay contact closed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm output 1 contact closed (loop 1)",
    "1": "Alarm output 2 contact closed",
    "2": "Alarm output 3 contact closed",
    "4": "Alarm output 4 contact closed",
    "5": "Alarm output 5 contact closed",
    "6": "Alarm output 6 contact closed",
    "8": "Alarm output 7 contact closed",
    "9": "Alarm output 8 contact closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2037,
   "documented": "D2038",
   "name": "ALO_L2 loop-2 alarm output 1-8 status",
   "description": "1 = relay contact closed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm output 1 contact closed (loop 2)",
    "1": "Alarm output 2 contact closed",
    "2": "Alarm output 3 contact closed",
    "4": "Alarm output 4 contact closed",
    "5": "Alarm output 5 contact closed",
    "6": "Alarm output 6 contact closed",
    "8": "Alarm output 7 contact closed",
    "9": "Alarm output 8 contact closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2063,
   "documented": "D2064",
   "name": "VALV valve status",
   "description": "Position-proportional control.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Estimating-type operation (0 = feedback input)",
    "1": "Open output on",
    "2": "Close output on",
    "3": "Automatic valve position adjustment running"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2064,
   "documented": "D2065",
   "name": "AD2.E A/D converter error status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Feedback input resistor/current burnout",
    "1": "Valve position automatic adjustment error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2067,
   "documented": "D2068",
   "name": "PA.ER parameter error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "System data error",
    "1": "Calibration value error",
    "2": "User default value error",
    "4": "Setup parameter error",
    "5": "Operation parameter error",
    "8": "Faulty FRAM",
    "10": "Control parameter error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2069,
   "documented": "D2070",
   "name": "OP.ER option error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "E1 terminal hardware not responding",
    "1": "E2 terminal hardware not responding",
    "2": "E3 terminal hardware not responding",
    "4": "E4 terminal hardware not responding",
    "10": "E3 communication error",
    "12": "E4 communication error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "D2101",
   "name": "SP_L1 loop-1 target setpoint",
   "description": "Current SP group. Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "D2102",
   "name": "SUB sub-target setpoint",
   "description": "Offset from SP in two-position two-level control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2102,
   "documented": "D2103",
   "name": "PIDN_L1 loop-1 PID number selection",
   "description": "PID group number to use.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "D2104",
   "name": "A1_L1 loop-1 alarm-1 setpoint",
   "description": "-19999 to 30000, decimal point per input.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2104,
   "documented": "D2105",
   "name": "A2_L1 loop-1 alarm-2 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2105,
   "documented": "D2106",
   "name": "A3_L1 loop-1 alarm-3 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2106,
   "documented": "D2107",
   "name": "A4_L1 loop-1 alarm-4 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2113,
   "documented": "D2114",
   "name": "P_L1 proportional band",
   "description": "0.0-999.9 % (heating side in heating/cooling).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2114,
   "documented": "D2115",
   "name": "I_L1 integral time",
   "description": "0 = off, 1-6000 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2115,
   "documented": "D2116",
   "name": "D_L1 derivative time",
   "description": "0 = off, 1-6000 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2116,
   "documented": "D2117",
   "name": "OH_L1 control output high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2117,
   "documented": "D2118",
   "name": "OL_L1 control output low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2118,
   "documented": "D2119",
   "name": "MR_L1 manual reset",
   "description": "Used when integral time is off.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2123,
   "documented": "D2124",
   "name": "DR_L1 direct/reverse action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RVS reverse action",
    "1": "DIR direct action"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2132,
   "documented": "D2133",
   "name": "PO_L1 preset output",
   "description": "Output used in STOP mode, -5.0 to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2150,
   "documented": "D2151",
   "name": "SP_L2 loop-2 target setpoint",
   "description": "Same as D2101 for loop 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2163,
   "documented": "D2164",
   "name": "P_L2 loop-2 proportional band",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2164,
   "documented": "D2165",
   "name": "I_L2 loop-2 integral time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2165,
   "documented": "D2166",
   "name": "D_L2 loop-2 derivative time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2300,
   "documented": "D2301",
   "name": "A.M_L1 loop-1 AUTO/MAN switch",
   "description": "Not for cascade modes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "1": "MAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2301,
   "documented": "D2302",
   "name": "A.M_L2 loop-2 AUTO/MAN switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "1": "MAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2302,
   "documented": "D2303",
   "name": "C.A.M CAS/AUTO/MAN switch",
   "description": "Cascade control modes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "1": "MAN",
    "2": "CAS"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2303,
   "documented": "D2304",
   "name": "S.R_L1 loop-1 STOP/RUN switch",
   "description": "Preset output is used in STOP.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "STOP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2304,
   "documented": "D2305",
   "name": "S.R_L2 loop-2 STOP/RUN switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "STOP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2305,
   "documented": "D2306",
   "name": "R.L_L1 loop-1 REMOTE/LOCAL switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "LCL (local)",
    "1": "REM (remote)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2306,
   "documented": "D2307",
   "name": "R.L_L2 loop-2 REMOTE/LOCAL switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "LCL (local)",
    "1": "REM (remote)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2307,
   "documented": "D2308",
   "name": "AT_L1 loop-1 auto-tuning switch",
   "description": "0 = off, 1-16 = tune into that PID, 17 = reference PID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2308,
   "documented": "D2309",
   "name": "AT_L2 loop-2 auto-tuning switch",
   "description": "Same as AT_L1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2311,
   "documented": "D2312",
   "name": "SPNO. SP number selection",
   "description": "1-8.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2313,
   "documented": "D2314",
   "name": "TRK_ON_L1 loop-1 output tracking",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2314,
   "documented": "D2315",
   "name": "TRK_ON_L2 loop-2 output tracking",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2330,
   "documented": "D2331",
   "name": "C.RSP_L1 loop-1 communication remote setpoint",
   "description": "Used when remote mode takes SP from comms. Engineering value without decimal point; position set by the PV input decimal point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2331,
   "documented": "D2332",
   "name": "C.RSP_L2 loop-2 communication remote setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2332,
   "documented": "D2333",
   "name": "MOUT_L1 loop-1 manual output",
   "description": "Heating-side output in MAN mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2334,
   "documented": "D2335",
   "name": "MOUT_L2 loop-2 manual output",
   "description": "Heating-side output in MAN mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read D2001-D2013 in one block for errors, PV, SP, output and alarms; write the target setpoint to D2101 (loop 2: D2151) and switch AUTO/MAN, RUN/STOP and REMOTE/LOCAL with D2301, D2304 and D2306.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2002,
    "why": "Loop-1 PV (D2003)"
   },
   {
    "table": "holding_register",
    "address": 2003,
    "why": "Loop-1 control setpoint (D2004)"
   },
   {
    "table": "holding_register",
    "address": 2004,
    "why": "Loop-1 output (D2005)"
   },
   {
    "table": "holding_register",
    "address": 2007,
    "why": "Operation mode status (D2008)"
   },
   {
    "table": "holding_register",
    "address": 2010,
    "why": "Loop-1 alarm status (D2011)"
   },
   {
    "table": "holding_register",
    "address": 2100,
    "why": "Loop-1 target setpoint (D2101)"
   },
   {
    "table": "holding_register",
    "address": 2300,
    "why": "AUTO/MAN (D2301)"
   },
   {
    "table": "holding_register",
    "address": 2303,
    "why": "RUN/STOP (D2304)"
   }
  ],
  "enable": "Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.",
  "watchdog": null,
  "quirks": [
   "Address D register n at wire address n-1 (D2101 = 0834H).",
   "Write values without the decimal point (50.0 with one decimal place = 500).",
   "To take the setpoint from communication, put the loop in REMOTE (D2306 = 1) with the remote source set to communication, then write D2331."
  ],
  "setup": [
   "Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1."
  ],
  "gotchas": [
   "Available registers depend on the suffix code (single/dual loop, options) and parameter settings; blank addresses must not be read or written."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/yokogawa/ut75a",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}