Boiler · Modbus register map

Buderus SSB condensing boilers (built-in Modbus RTU) Modbus register map

Updated 29 October 2026

Short answer

Buderus SSB floor-standing condensing boilers have a Modbus RTU slave on their own controller. Everything is a 16-bit holding register: burner state, status and error code, pump outputs, supply/return/DHW/flue temperatures, firing rate, counters, lockout and blocking history, cascade dependents, and the CH, DHW and outdoor-reset setpoints. Writes need a write-enable bit set just before each write.

This page lists 50 Modbus registers for the Buderus SSB condensing boilers (built-in Modbus RTU) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Buderus’s own free documentation (linked below) and checked against it.

Manufacturer
Buderus
Model
SSB condensing boilers (built-in Modbus RTU)
Equipment type
Boiler
Registers
50 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SSB, Buderus SSB boiler, Bosch SSB, 6720818450
Source document
Modbus for Buderus SSB Boilers - Installation and Service Instructions for Contractors · 6720818450 (2015/10) US Rev.0 · rev. 2015-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Buderus SSB condensing boilers (built-in Modbus RTU)

Integration in brief

Wire Modbus + and - to the MOD BUS terminals of the boiler's terminal strip, set the master to 9600 8-N-2 and read holding registers 100-142 with function 03. To change a setpoint, first write register 99 = 1 (Write Enable), then write the value x10 within 4 seconds.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 101StatusUINT16Boiler statusRead
HR 102Error codeUINT16Error codeRead
HR 120Supply temperatureUINT16Supply temperatureRead
HR 121Return temperatureUINT16Return temperatureRead
HR 140Firing rateUINT16Firing rateRead
HR 502CH set-pointUINT16CH setpointRead/write
HR 503DHW set-pointUINT16DHW setpointRead/write
HR 99Control registerBITMAP16Write enable / lockout resetRead/write

Enable Modbus control & writes

Writes are refused unless register 99 bit 0 (Write Enable) is set. The bit clears itself after each write sequence or after 4 seconds, so set it again before every write.

Communication loss & watchdog

If no Modbus read or write arrives for more than 4 seconds the control register 99 is cleared. No other comm-loss behaviour is documented.

Byte order & addressing

Network setup

Watch out for

Buderus SSB condensing boilers (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Buderus SSB condensing boilers (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR98doc 98 (0x0062)Unit selectionBit 0 picks °C or °F, bit 1 bar or psi; needs Write Enable first.BITMAP16Read/writebit 0 = Temperature unit (°C / °F); bit 1 = Pressure unit (bar / psi)
HR99doc 99 (0x0063)Control registerSet bit 0 before every write; bit 14 resets a lockout.BITMAP16Read/writebit 0 = Write Enable (cleared automatically after a write or after 4 s); bit 14 = Controller reset (only in lockout; clears itself)
HR100doc 100 (0x0064)StateBurner sequence state.UINT16Read0 = RESET_0 (start-up init); 1 = RESET_1 (start-up); 2 = STANDBY_0 (standby / idle); 3 = PRE_PURGE (init); 4 = PRE_PURGE_1 (pre purging); 5 = SAFETY_ON (test safety relay on); 6 = SAFETY_OFF (test safety relay off); 7 = IGNIT_0 (ignition); 8 = IGNIT_1 (ignition); 9 = BURN_0 (burning); 10 = SHUT_DOWN_RELAY_TEST_0 (init); 11 = SHUT_DOWN_RELAY_TEST_1 (testing safety and gas valve relays); 12 = POST_PURGE_0 (init); 13 = POST_PURGE_1 (post purging); 14 = PUMP_CH_0 (init); 15 = PUMP_CH_1 (pumping for CH); 16 = PUMP_HW_0 (init); 17 = PUMP_HW_1 (pumping for DHW); 18 = ALARM_1 (lockout); 19 = ERROR_CHECK (blocking); 20 = BURNER_BOOT (rebooting); 21 = CLEAR_E2PROM_ERROR; 22 = STORE_BLOCK_ERROR; 23 = WAIT_A_SECOND
HR101doc 101 (0x0065)StatusWhat the boiler is doing.UINT16Read0 = STANDBY; 10 = ALARM (lockout); 14 = BLOCK (blocking error); 15 = FROST_PROTECT; 16 = CH_DEMAND; 17 = RESET_STATE; 18 = STORAGE_DEMAND; 19 = DHW_TAP_DEMAND; 20 = DHW_PRE_HEAT; 21 = STORE_HOLD_WARM; 22 = GENERAL_PUMPING
HR102doc 102 (0x0066)Error codeActive lockout or blocking error, see error table.UINT16Read1 = Ignit Error (3 failed ignitions) - lockout; 2 = Gv Relay Error - lockout; 3 = Gv Relay Not Open - lockout; 4 = Gv Relay Not Close - lockout; 5 = Safety Relay Error - lockout; 6 = Safety Relay Open - lockout; 7 = Safety Relay Closed - lockout; 11 = Blocking Too Long Error (blocked > 20 h) - lockout; 12 = Fan Error - lockout; 13 = Ram Error - lockout; 14 = Wrong E2prom Signature - lockout; 15 = X Ram Error - lockout; 16 = E2Prom Error - lockout; 17 = E2Prom Error C - lockout; 18 = E2Prom Error Cal Table - lockout; 19 = State Error - lockout; 20 = Rom Error - lockout; 21 = Rom Error C - lockout; 22 = Air Sw Not Open - lockout; 23 = 15Ms Xrl Error - lockout; 24 = Air Sw Not Closed - lockout; 25 = T Max Lock Error (external overheat) - lockout; 26 = Stack Error - lockout; 27 = Flame Out Too Late Error - lockout; 28 = Flame Error 1 (flame before ignition) - lockout; 29 = 20Ms Xrl Error - lockout; 30 = 41Ms Error - lockout; 31 = Too Many Flame Failures - lockout; 32 = Flow Switch Not Closed Error - lockout; 33 = Flow Switch Not Open Error - lockout; 34 = Flag Byte Integrity Error - lockout; 35 = Ad Hi Cpl Error - lockout; 36 = Ad Lo Cpl Error - lockout; 37 = Register Error - lockout; 45 = WD Error Ram - blocking; 46 = WD Error Rom - blocking; 47 = WD Error Stack - blocking; 48 = WD Error Register - blocking; 49 = WD Error Xrl - blocking; 50 = Refhi Too Lo Error - blocking; 51 = Refhi Too Hi Error - blocking; 52 = Reflo Too Lo Error - blocking; 53 = Reflo Too Hi Error - blocking; 54 = Flame Error 2 - blocking; 55 = Water Level Detect - blocking; 56 = Water Level Meas - blocking; 57 = Low Water Cutoff Error - blocking; 58 = Low Water Pressure Error - blocking; 59 = Low Water Pressure Sensor - blocking; 60 = Flue Gas Error - blocking; 61 = Return Temp Error - blocking; 62 = Blocked Drain Error - blocking; 64 = Wd Freq Error - blocking; 65 = Phase Error (hot/neutral reversed) - blocking; 66 = Net Freq Error - blocking; 67 = Faulty Earth Error - blocking; 68 = WD Communication Error - blocking; 70 = Overheat Error - blocking; 72 = T Supply Open - blocking; 73 = T Return Open - blocking; 76 = T Dhw Out Open - blocking; 80 = T Supply Shorted - blocking; 81 = T Return Shorted - blocking; 84 = T Dhw Out Shorted - blocking; 86 = T Flue Shorted - blocking; 87 = Reset Button Error - blocking; 93 = Appliance Selection - blocking; 107 = Gas Pressure Error - blocking; 108 = Flue Press Error - blocking
HR110CH pump0 or 100 % (or 0-100 % if modulating).UINT16× 0.1%Read
HR111DHW pump0 or 100 % (or 0-100 % if modulating).UINT16× 0.1%Read
HR112General pump0 or 100 % (or 0-100 % if modulating).UINT16× 0.1%Read
HR120Supply temperatureIn °C or °F per register 98.UINT16× 0.1°C/°FRead
HR121Return temperatureIn °C or °F per register 98.UINT16× 0.1°C/°FRead
HR122DHW temperatureIn °C or °F per register 98.UINT16× 0.1°C/°FRead
HR123Flue gas temperatureIn °C or °F per register 98.UINT16× 0.1°C/°FRead
HR124System (heat exchanger) temperatureIf fitted; °C or °F per register 98.UINT16× 0.1°C/°FRead
HR140Firing rateBurner power output.UINT16× 0.1%Read
HR142Flame (ionization) currentUINT16× 0.1µARead
HR201Failed ignition counterUINT16Read
HR202Flame failure counterUINT16Read
HR203Burn hours CHUINT16hRead
HR204Burn hours DHWUINT16hRead
HR220First lockout in historyHistory slot 1 of 16 (220-235); not in time order.UINT16Read1 = Ignit Error (3 failed ignitions) - lockout; 2 = Gv Relay Error - lockout; 3 = Gv Relay Not Open - lockout; 4 = Gv Relay Not Close - lockout; 5 = Safety Relay Error - lockout; 6 = Safety Relay Open - lockout; 7 = Safety Relay Closed - lockout; 11 = Blocking Too Long Error (blocked > 20 h) - lockout; 12 = Fan Error - lockout; 13 = Ram Error - lockout; 14 = Wrong E2prom Signature - lockout; 15 = X Ram Error - lockout; 16 = E2Prom Error - lockout; 17 = E2Prom Error C - lockout; 18 = E2Prom Error Cal Table - lockout; 19 = State Error - lockout; 20 = Rom Error - lockout; 21 = Rom Error C - lockout; 22 = Air Sw Not Open - lockout; 23 = 15Ms Xrl Error - lockout; 24 = Air Sw Not Closed - lockout; 25 = T Max Lock Error (external overheat) - lockout; 26 = Stack Error - lockout; 27 = Flame Out Too Late Error - lockout; 28 = Flame Error 1 (flame before ignition) - lockout; 29 = 20Ms Xrl Error - lockout; 30 = 41Ms Error - lockout; 31 = Too Many Flame Failures - lockout; 32 = Flow Switch Not Closed Error - lockout; 33 = Flow Switch Not Open Error - lockout; 34 = Flag Byte Integrity Error - lockout; 35 = Ad Hi Cpl Error - lockout; 36 = Ad Lo Cpl Error - lockout; 37 = Register Error - lockout; 45 = WD Error Ram - blocking; 46 = WD Error Rom - blocking; 47 = WD Error Stack - blocking; 48 = WD Error Register - blocking; 49 = WD Error Xrl - blocking; 50 = Refhi Too Lo Error - blocking; 51 = Refhi Too Hi Error - blocking; 52 = Reflo Too Lo Error - blocking; 53 = Reflo Too Hi Error - blocking; 54 = Flame Error 2 - blocking; 55 = Water Level Detect - blocking; 56 = Water Level Meas - blocking; 57 = Low Water Cutoff Error - blocking; 58 = Low Water Pressure Error - blocking; 59 = Low Water Pressure Sensor - blocking; 60 = Flue Gas Error - blocking; 61 = Return Temp Error - blocking; 62 = Blocked Drain Error - blocking; 64 = Wd Freq Error - blocking; 65 = Phase Error (hot/neutral reversed) - blocking; 66 = Net Freq Error - blocking; 67 = Faulty Earth Error - blocking; 68 = WD Communication Error - blocking; 70 = Overheat Error - blocking; 72 = T Supply Open - blocking; 73 = T Return Open - blocking; 76 = T Dhw Out Open - blocking; 80 = T Supply Shorted - blocking; 81 = T Return Shorted - blocking; 84 = T Dhw Out Shorted - blocking; 86 = T Flue Shorted - blocking; 87 = Reset Button Error - blocking; 93 = Appliance Selection - blocking; 107 = Gas Pressure Error - blocking; 108 = Flue Press Error - blocking
HR260First blocking in historyHistory slot 1 of 16 (260-275); not in time order.UINT16Read1 = Ignit Error (3 failed ignitions) - lockout; 2 = Gv Relay Error - lockout; 3 = Gv Relay Not Open - lockout; 4 = Gv Relay Not Close - lockout; 5 = Safety Relay Error - lockout; 6 = Safety Relay Open - lockout; 7 = Safety Relay Closed - lockout; 11 = Blocking Too Long Error (blocked > 20 h) - lockout; 12 = Fan Error - lockout; 13 = Ram Error - lockout; 14 = Wrong E2prom Signature - lockout; 15 = X Ram Error - lockout; 16 = E2Prom Error - lockout; 17 = E2Prom Error C - lockout; 18 = E2Prom Error Cal Table - lockout; 19 = State Error - lockout; 20 = Rom Error - lockout; 21 = Rom Error C - lockout; 22 = Air Sw Not Open - lockout; 23 = 15Ms Xrl Error - lockout; 24 = Air Sw Not Closed - lockout; 25 = T Max Lock Error (external overheat) - lockout; 26 = Stack Error - lockout; 27 = Flame Out Too Late Error - lockout; 28 = Flame Error 1 (flame before ignition) - lockout; 29 = 20Ms Xrl Error - lockout; 30 = 41Ms Error - lockout; 31 = Too Many Flame Failures - lockout; 32 = Flow Switch Not Closed Error - lockout; 33 = Flow Switch Not Open Error - lockout; 34 = Flag Byte Integrity Error - lockout; 35 = Ad Hi Cpl Error - lockout; 36 = Ad Lo Cpl Error - lockout; 37 = Register Error - lockout; 45 = WD Error Ram - blocking; 46 = WD Error Rom - blocking; 47 = WD Error Stack - blocking; 48 = WD Error Register - blocking; 49 = WD Error Xrl - blocking; 50 = Refhi Too Lo Error - blocking; 51 = Refhi Too Hi Error - blocking; 52 = Reflo Too Lo Error - blocking; 53 = Reflo Too Hi Error - blocking; 54 = Flame Error 2 - blocking; 55 = Water Level Detect - blocking; 56 = Water Level Meas - blocking; 57 = Low Water Cutoff Error - blocking; 58 = Low Water Pressure Error - blocking; 59 = Low Water Pressure Sensor - blocking; 60 = Flue Gas Error - blocking; 61 = Return Temp Error - blocking; 62 = Blocked Drain Error - blocking; 64 = Wd Freq Error - blocking; 65 = Phase Error (hot/neutral reversed) - blocking; 66 = Net Freq Error - blocking; 67 = Faulty Earth Error - blocking; 68 = WD Communication Error - blocking; 70 = Overheat Error - blocking; 72 = T Supply Open - blocking; 73 = T Return Open - blocking; 76 = T Dhw Out Open - blocking; 80 = T Supply Shorted - blocking; 81 = T Return Shorted - blocking; 84 = T Dhw Out Shorted - blocking; 86 = T Flue Shorted - blocking; 87 = Reset Button Error - blocking; 93 = Appliance Selection - blocking; 107 = Gas Pressure Error - blocking; 108 = Flue Press Error - blocking
HR300Dependent 01 stateCascade dependent boiler, state table codes.UINT16Read0 = RESET_0 (start-up init); 1 = RESET_1 (start-up); 2 = STANDBY_0 (standby / idle); 3 = PRE_PURGE (init); 4 = PRE_PURGE_1 (pre purging); 5 = SAFETY_ON (test safety relay on); 6 = SAFETY_OFF (test safety relay off); 7 = IGNIT_0 (ignition); 8 = IGNIT_1 (ignition); 9 = BURN_0 (burning); 10 = SHUT_DOWN_RELAY_TEST_0 (init); 11 = SHUT_DOWN_RELAY_TEST_1 (testing safety and gas valve relays); 12 = POST_PURGE_0 (init); 13 = POST_PURGE_1 (post purging); 14 = PUMP_CH_0 (init); 15 = PUMP_CH_1 (pumping for CH); 16 = PUMP_HW_0 (init); 17 = PUMP_HW_1 (pumping for DHW); 18 = ALARM_1 (lockout); 19 = ERROR_CHECK (blocking); 20 = BURNER_BOOT (rebooting); 21 = CLEAR_E2PROM_ERROR; 22 = STORE_BLOCK_ERROR; 23 = WAIT_A_SECOND
HR302Dependent 01 error codeCascade dependent boiler, error table codes.UINT16Read1 = Ignit Error (3 failed ignitions) - lockout; 2 = Gv Relay Error - lockout; 3 = Gv Relay Not Open - lockout; 4 = Gv Relay Not Close - lockout; 5 = Safety Relay Error - lockout; 6 = Safety Relay Open - lockout; 7 = Safety Relay Closed - lockout; 11 = Blocking Too Long Error (blocked > 20 h) - lockout; 12 = Fan Error - lockout; 13 = Ram Error - lockout; 14 = Wrong E2prom Signature - lockout; 15 = X Ram Error - lockout; 16 = E2Prom Error - lockout; 17 = E2Prom Error C - lockout; 18 = E2Prom Error Cal Table - lockout; 19 = State Error - lockout; 20 = Rom Error - lockout; 21 = Rom Error C - lockout; 22 = Air Sw Not Open - lockout; 23 = 15Ms Xrl Error - lockout; 24 = Air Sw Not Closed - lockout; 25 = T Max Lock Error (external overheat) - lockout; 26 = Stack Error - lockout; 27 = Flame Out Too Late Error - lockout; 28 = Flame Error 1 (flame before ignition) - lockout; 29 = 20Ms Xrl Error - lockout; 30 = 41Ms Error - lockout; 31 = Too Many Flame Failures - lockout; 32 = Flow Switch Not Closed Error - lockout; 33 = Flow Switch Not Open Error - lockout; 34 = Flag Byte Integrity Error - lockout; 35 = Ad Hi Cpl Error - lockout; 36 = Ad Lo Cpl Error - lockout; 37 = Register Error - lockout; 45 = WD Error Ram - blocking; 46 = WD Error Rom - blocking; 47 = WD Error Stack - blocking; 48 = WD Error Register - blocking; 49 = WD Error Xrl - blocking; 50 = Refhi Too Lo Error - blocking; 51 = Refhi Too Hi Error - blocking; 52 = Reflo Too Lo Error - blocking; 53 = Reflo Too Hi Error - blocking; 54 = Flame Error 2 - blocking; 55 = Water Level Detect - blocking; 56 = Water Level Meas - blocking; 57 = Low Water Cutoff Error - blocking; 58 = Low Water Pressure Error - blocking; 59 = Low Water Pressure Sensor - blocking; 60 = Flue Gas Error - blocking; 61 = Return Temp Error - blocking; 62 = Blocked Drain Error - blocking; 64 = Wd Freq Error - blocking; 65 = Phase Error (hot/neutral reversed) - blocking; 66 = Net Freq Error - blocking; 67 = Faulty Earth Error - blocking; 68 = WD Communication Error - blocking; 70 = Overheat Error - blocking; 72 = T Supply Open - blocking; 73 = T Return Open - blocking; 76 = T Dhw Out Open - blocking; 80 = T Supply Shorted - blocking; 81 = T Return Shorted - blocking; 84 = T Dhw Out Shorted - blocking; 86 = T Flue Shorted - blocking; 87 = Reset Button Error - blocking; 93 = Appliance Selection - blocking; 107 = Gas Pressure Error - blocking; 108 = Flue Press Error - blocking
HR303Dependent 01 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR306Dependent 02 stateCascade dependent boiler, state table codes.UINT16Read
HR308Dependent 02 error codeCascade dependent boiler, error table codes.UINT16Read
HR309Dependent 02 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR312Dependent 03 stateCascade dependent boiler, state table codes.UINT16Read
HR314Dependent 03 error codeCascade dependent boiler, error table codes.UINT16Read
HR315Dependent 03 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR318Dependent 04 stateCascade dependent boiler, state table codes.UINT16Read
HR320Dependent 04 error codeCascade dependent boiler, error table codes.UINT16Read
HR321Dependent 04 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR324Dependent 05 stateCascade dependent boiler, state table codes.UINT16Read
HR326Dependent 05 error codeCascade dependent boiler, error table codes.UINT16Read
HR327Dependent 05 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR330Dependent 06 stateCascade dependent boiler, state table codes.UINT16Read
HR332Dependent 06 error codeCascade dependent boiler, error table codes.UINT16Read
HR333Dependent 06 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR336Dependent 07 stateCascade dependent boiler, state table codes.UINT16Read
HR338Dependent 07 error codeCascade dependent boiler, error table codes.UINT16Read
HR339Dependent 07 firing rateCascade dependent boiler power output.UINT16× 0.1%Read
HR502CH set-pointCentral heating setpoint; °C or °F per register 98.UINT16× 0.1°C/°FRead/write
HR503DHW set-pointHot water setpoint; °C or °F per register 98.UINT16× 0.1°C/°FRead/write
HR504Reset curve boiler designSupply temperature at outdoor design condition.UINT16× 0.1°C/°FRead/write
HR505Reset curve boiler mild weatherSupply temperature at mild outdoor condition.UINT16× 0.1°C/°FRead/write
HR508Warm weather shutdownOutdoor temperature above which heating stops.UINT16× 0.1°C/°FRead/write
HR509Reset curve boiler maximumUINT16× 0.1°C/°FRead/write
HR510Reset curve boiler minimumUINT16× 0.1°C/°FRead/write
HR511Night setbackUINT16× 0.1°C/°FRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Buderus SSB condensing boilers (built-in Modbus RTU)

What Modbus registers does the Buderus SSB condensing boilers (built-in Modbus RTU) have?

This map lists 50 registers: 50 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Buderus SSB condensing boilers (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document prints decimal register numbers with their hex form (98 = 0x0062) and says to use them as printed when the master counts from 0x0000, and to add 1 only if the master counts from 0x0001. So register 100 is wire address 100.

What are the minimum Modbus registers to integrate the Buderus SSB condensing boilers (built-in Modbus RTU)?

Start with HR 101 Status (Boiler status); HR 102 Error code (Error code); HR 120 Supply temperature (Supply temperature); HR 121 Return temperature (Return temperature); HR 140 Firing rate (Firing rate); HR 502 CH set-point (CH setpoint); HR 503 DHW set-point (DHW setpoint); HR 99 Control register (Write enable / lockout reset).

How do I enable Modbus control of the Buderus SSB condensing boilers (built-in Modbus RTU)?

Writes are refused unless register 99 bit 0 (Write Enable) is set. The bit clears itself after each write sequence or after 4 seconds, so set it again before every write.

What happens when the Buderus SSB condensing boilers (built-in Modbus RTU) loses Modbus communication?

If no Modbus read or write arrives for more than 4 seconds the control register 99 is cleared. No other comm-loss behaviour is documented.

Where is the official Buderus SSB condensing boilers (built-in Modbus RTU) Modbus documentation?

The source is Modbus for Buderus SSB Boilers - Installation and Service Instructions for Contractors (6720818450 (2015/10) US Rev.0), revision 2015-10, published free by Buderus at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/6720818450_ssb_boiler_modbus_installation_instructions_en_10.2015_us_us.pdf.

More Buderus Modbus register maps

Source: Modbus for Buderus SSB Boilers - Installation and Service Instructions for Contractors · 6720818450 (2015/10) US Rev.0 · rev. 2015-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.