- eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0
EV charger · Modbus register map
eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus register map
Updated 17 November 2026
eCharge Hardy Barth AC charging stations with the Salia controller run a Modbus TCP server on port 502 for EMS and SCADA control. Telemetry is in input registers, identity, configuration and control points in holding registers; floats and 32-bit values are big-endian with the high word first and need no scaling. Charging is controlled with a current target and a pause/allow register, with an optional heartbeat failsafe.
This page lists 77 Modbus registers for the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from eCharge Hardy Barth’s own free documentation (linked below) and checked against it.
- Manufacturer
- eCharge Hardy Barth
- Model
- eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0
- Equipment type
- EV charger
- Registers
- 77 (10 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 2.5.2 (MapVersion 2.3.0)
- Also known as
- cPH2, cPH22T22, Hardy Barth Salia, eCharge cPH2, Hardy Barth wallbox
Integration notes: eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0
Connect to port 502 at Unit ID 1. Set ChargeMode (40107) to MANUAL, then write the current target and Start_Stop_Charging together in one FC16 frame (40202-40203); poll EVCS_State, ErrorCode and the meter block from 30001/31001.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 201 | Set_Charge_Current_Target | UINT16 | Charge current target | Read/write |
| HR 202 | Start_Stop_Charging | UINT16 | Pause / allow energy | Read/write |
| IR 0 | EVCS_State | UINT16 | Station state | Read |
| IR 3 | ErrorCode | UINT16 | Error code | Read |
| IR 1014 | Power_Total | FLOAT32 ABCD | Charging power | Read |
| IR 1022 | Energy_Total | FLOAT32 ABCD | Meter energy total | Read |
| HR 207 | Heartbeat | UINT16 | Heartbeat for the failsafe | Write |
| HR 104 | MaxCurrent | UINT16 | Configured maximum current | Read/write |
Enable Modbus control & writes
The Modbus TCP server listens on port 502 by default. An installer may set an IP allow-list in the station's web configuration; ask for your EMS address to be added.
Communication loss & watchdog
Failsafe_Timeout (40204, 0 = off or 10-3600 s). If no accepted write to 40202, 40203, 40208 or 40209 arrives within the timeout, the station applies Failsafe_Current_Target (40206), sets Failsafe_Active (30027) and ErrorCode 7. Write Heartbeat (40208) at least every timeout/2.
Byte order & addressing
- Start (40203 = 1) is rejected with exception 03 while the current target is 0; write both in one FC16 frame.
- While 40203 = 0 the charger is offered 0 A whatever 40202 says.
- Temperature (30025) is a u32 integer, not a float.
- A change of charge mode resets the station's limit to its maximum and overrides the Modbus current target.
- Unit IDs 0 and 255 are refused with exception 0B.
Network setup
- Static IP or DHCP (default) on the station's Ethernet port; Modbus TCP port 502, Unit ID 1.
- Up to 32 connections total and 4 per source IP; 50 requests/s per IP (burst 100).
- Idle connections close after 5 minutes.
Watch out for
- Before an EMS stops controlling the station, write a current with 40203 = 1 and set 40204 = 0, or the station can stay limited to 0 A.
- Read-only integrations should keep the failsafe off (40204 = 0); stations updated from MapVersion 2.0.0 often keep a saved 20 s / 0 A failsafe.
- A phase switch (40209) only runs during an active session; confirm it at ActualPhase (30303).
eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | EVCS_State | Station state derived every 2 s. | UINT16 | Read | 0 = NOT_READY; 1 = READY; 2 = CHARGING; 3 = CHARGING_INTERRUPTED; 4 = ERROR; 5 = AUTH_REJECTED (reserved); 6 = RESERVED; 7 = PHASE_SWITCHING | |||
| IR | 1doc 30002 | Connector_State | UINT16 | Read | 0 = UNPLUGGED (not reported); 1 = PLUGGED_ON_STATION_ONLY; 2 = PLUGGED_ON_STATION_AND_VEHICLE; 3 = ERROR_UNAVAILABLE | ||||
| IR | 3doc 30004 | ErrorCode | Highest-priority active condition. | UINT16 | Read | 0 = No error; 1 = Internal hardware fault; 2 = Over-current or short circuit; 3 = Over- or under-voltage; 4 = Over-temperature (electronics); 5 = Energy meter communication failure; 6 = Lock/plug fault; 7 = Failsafe active | |||
| IR | 20doc 30021 | AuthorizationStatus | 1 when the station has authorised the session. | UINT16 | Read | 0 = No; 1 = Yes | |||
| IR | 21doc 30022 | AuthType | UINT16 | Read | 0 = FREE; 1 = RFID; 2 = KEYSWITCH; 3 = OCPP | ||||
| IR | 22doc 30023 | Uptime | Seconds since boot. | UINT32 | ABCD | s | Read | ||
| IR | 24doc 30025 | Temperature | Electronics temperature, whole degrees (not a float). | UINT32 | ABCD | °C | Read | ||
| IR | 26doc 30027 | Failsafe_Active | 1 while the communication-loss failsafe is active. | UINT16 | Read | 0 = No; 1 = Yes | |||
| IR | 49doc 30050 | DaemonStatus | Gateway health flags. | BITMAP16 | Read | bit 0 = units_ready - gateway ready; bit 1 = mqtt_connected - link to charger up; bit 2 = api_seed_succeeded; bit 3 = persistence_degraded - failsafe setting not yet saved; bit 4 = degraded_mode | |||
| IR | 100doc 30101 | Availability | 1 when the station reports operative. | UINT16 | Read | 0 = No; 1 = Yes | |||
| IR | 101doc 30102 | GridCurrentLimit | UINT16 | A | Read | ||||
| IR | 102doc 30103 | PhaseCount | 1 or 3. | UINT16 | Read | ||||
| IR | 103doc 30104 | PhysicalCurrentLimit | Hardware limit. | UINT16 | A | Read | |||
| IR | 104doc 30105 | OfferedCurrentLimit | Limit advertised to the vehicle. | UINT16 | A | Read | |||
| IR | 105doc 30106 | CurrentOfferedTotal | FLOAT32 | ABCD | A | Read | |||
| IR | 107doc 30108 | CurrentOfferedL1 | FLOAT32 | ABCD | A | Read | |||
| IR | 109doc 30110 | CurrentOfferedL2 | FLOAT32 | ABCD | A | Read | |||
| IR | 111doc 30112 | CurrentOfferedL3 | FLOAT32 | ABCD | A | Read | |||
| IR | 113doc 30114 | PowerOffered | FLOAT32 | ABCD | W | Read | |||
| IR | 200doc 30201 | EV_Present | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 201doc 30202 | Charging | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 202doc 30203 | CP_Status | IEC 61851 control pilot state. | UINT16 | Read | 0 = A - standby, no vehicle; 1 = B - connected, not requesting; 2 = C - charging requested; 3 = D - ventilation required; 4 = E - error; 5 = F - EVSE fault | |||
| IR | 203doc 30204 | CP_PWM_State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 204doc 30205 | CP_Duty_Cycle | FLOAT32 | ABCD | % | Read | |||
| IR | 219doc 30220 | Plug_Lock_Status | UINT16 | Read | 0 = Unlocked; 1 = Locked; 2 = Unknown | ||||
| IR | 220doc 30221 | Plug_State_Actual | UINT16 | Read | 0 = Unlock; 1 = Lock | ||||
| IR | 221doc 30222 | Plug_State_Target | UINT16 | Read | 0 = Unlock; 1 = Lock | ||||
| IR | 222doc 30223 | Plug_Error | Firmware-specific plug-lock fault; 0 = none. | UINT16 | Read | ||||
| IR | 223doc 30224 | Contactor_Status | UINT16 | Read | 0 = Opened; 1 = Closed; 2 = Unknown | ||||
| IR | 224doc 30225 | Contactor_State_Actual | UINT16 | Read | 0 = Open; 1 = Close | ||||
| IR | 225doc 30226 | Contactor_State_Target | UINT16 | Read | 0 = Open; 1 = Close | ||||
| IR | 226doc 30227 | Contactor_Error | Firmware-specific contactor fault; 0 = none. | UINT16 | Read | ||||
| IR | 227doc 30228 | PWM_Status | Mirror of CP_Duty_Cycle. | FLOAT32 | ABCD | % | Read | ||
| IR | 300doc 30301 | PhaseSwitchingEnabled | As read from the configuration at service start. | UINT16 | Read | 0 = No; 1 = Yes | |||
| IR | 301doc 30302 | PhaseSwitchingStatus | UINT16 | Read | 0 = IDLE; 1 = IN_PROGRESS | ||||
| IR | 302doc 30303 | ActualPhase | 0, 1 or 3 phases on the contactor; 0 when idle. | UINT16 | Read | ||||
| IR | 303doc 30304 | TargetPhase | 0, 1 or 3; last commanded phase count. | UINT16 | Read | ||||
| IR | 400doc 30401 | RFID_Available | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 417doc 30418 | RFID_LastTag | Last RFID tag seen, upper case. | STRING[32] | Read | ||||
| IR | 600doc 30601 | ChargeMode_Actual | Mode the station is actually running. | UINT16 | Read | 0 = ECO (PV surplus); 1 = POWER (maximum); 2 = MANUAL (EMS/user current) | |||
| IR | 601doc 30602 | EcoPlus_Actual | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 602doc 30603 | PauseCharging_Actual | 1 while the station itself or a user has paused charging. | UINT16 | Read | 0 = No; 1 = Yes | |||
| IR | 603doc 30604 | MaxCurrent_Actual | Live maximum, e.g. the load-management share. | UINT16 | A | Read | |||
| IR | 1000doc 31001 | MeterFrequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 1002doc 31003 | Voltage_L1 | FLOAT32 | ABCD | V | Read | |||
| IR | 1004doc 31005 | Voltage_L2 | FLOAT32 | ABCD | V | Read | |||
| IR | 1006doc 31007 | Voltage_L3 | FLOAT32 | ABCD | V | Read | |||
| IR | 1008doc 31009 | Current_L1 | FLOAT32 | ABCD | A | Read | |||
| IR | 1010doc 31011 | Current_L2 | FLOAT32 | ABCD | A | Read | |||
| IR | 1012doc 31013 | Current_L3 | FLOAT32 | ABCD | A | Read | |||
| IR | 1014doc 31015 | Power_Total | FLOAT32 | ABCD | W | Read | |||
| IR | 1016doc 31017 | Power_L1 | FLOAT32 | ABCD | W | Read | |||
| IR | 1018doc 31019 | Power_L2 | FLOAT32 | ABCD | W | Read | |||
| IR | 1020doc 31021 | Power_L3 | FLOAT32 | ABCD | W | Read | |||
| IR | 1022doc 31023 | Energy_Total | Lifetime meter total, not the session energy. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 0doc 40001 | MapVersion | Register-map version, e.g. 2.3.0. | STRING[16] | Read | ||||
| HR | 8doc 40009 | Model | Model designation, e.g. cPH22T22. | STRING[32] | Read | ||||
| HR | 24doc 40025 | SerialNumber | STRING[16] | Read | |||||
| HR | 32doc 40033 | Manufacturer | STRING[32] | Read | |||||
| HR | 48doc 40049 | FirmwareVersionStr | Firmware version text, e.g. 2.3.75. | STRING[16] | Read | ||||
| HR | 56doc 40057 | FirmwareVersionU32 | Packed version: one byte major, one byte minor, one word patch. | UINT32 | ABCD | Read | |||
| HR | 64doc 40065 | ModelType | Fixed text EV_CHARGING_STATION. | STRING[24] | Read | ||||
| HR | 100doc 40101 | FuseRating | Configured mains (house) fuse rating. | UINT16 | A | Read | |||
| HR | 101doc 40102 | EcoPlusTimeout | UINT16 | s | Read | ||||
| HR | 102doc 40103 | EcoReference | Grid power reference for ECO mode; may be negative. | INT16 | W | Read | |||
| HR | 103doc 40104 | MinCurrent | Configured minimum charge current 6-32 A; saved on write. | UINT16 | A | Read/write | |||
| HR | 104doc 40105 | MaxCurrent | Configured maximum 6-32 A, not above FuseRating; saved on write. | UINT16 | A | Read/write | |||
| HR | 105doc 40106 | EcoPlus | EMS setpoint; actual value at IR 30602. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 106doc 40107 | ChargeMode | EMS setpoint; actual value at IR 30601. | UINT16 | Read/write | 0 = ECO (PV surplus); 1 = POWER (maximum); 2 = MANUAL (EMS/user current) | |||
| HR | 201doc 40202 | Set_Charge_Current_Target | 0 stops; otherwise within MinCurrent-MaxCurrent. | UINT16 | A | Read/write | |||
| HR | 202doc 40203 | Start_Stop_Charging | Pauses or allows energy; never authorises a session. | UINT16 | Read/write | 0 = Pause energy; 1 = Allow energy | |||
| HR | 203doc 40204 | Failsafe_Timeout | 0 = off, or 10-3600 s. | UINT16 | s | Read/write | |||
| HR | 205doc 40206 | Failsafe_Current_Target | Current applied when the failsafe trips; 0 or within the window. | UINT16 | A | Read/write | |||
| HR | 207doc 40208 | Heartbeat | Write any value to keep the failsafe timer reset. | UINT16 | Write | ||||
| HR | 208doc 40209 | Target_Phase | 1 or 3; needs phase switching enabled; acts only during a session. | UINT16 | Read/write | ||||
| HR | 1024doc 41025 | MeterPhaseCount | 1 or 3. | UINT16 | Read | ||||
| HR | 1025doc 41026 | MeterAvailable | UINT16 | Read | 0 = No; 1 = Yes |
Notes on this map
- Official documentation from eCharge's own docs site (markdown page).
- Word order: the manual states big-endian word order (high word at the lower address) and big-endian bytes for all multi-register values; values are already in engineering units (scale 1).
- Left out: Mains/Battery block 30501-30527 (the manual says this firmware does not populate it), StatusWord 30003 (reserved, always 0), ChargingInfo 30005 (free text, not for parsing), PhaseSwitchDelay/Duration 30305/30306 (the manual says they are unreliable), meter identity strings 41001-41024, and the accepted-but-ignored control registers 40201, 40205, 40207 and 40210-40225.
- Unused addresses read 0 without an exception, so a wrong function code or an off-by-one address returns zeros; read MapVersion (40001) first to check addressing.
- Other Unit IDs on the same IP: 2-4 forward to linked slave stations, and 100 (if enabled) is a Fronius-style SunSpec meter emulation starting with 'SunS' at 40001.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0
What Modbus registers does the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 have?
This map lists 77 registers: 55 input registers, 22 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives the 3xxxx/4xxxx number and the zero-based PDU address; PDU = register - 30001 (input) or - 40001 (holding). The manual's example frame 06 00 C9 00 10 writes 16 A to 40202 at PDU 201.
What byte order does the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0?
Start with HR 201 Set_Charge_Current_Target (Charge current target); HR 202 Start_Stop_Charging (Pause / allow energy); IR 0 EVCS_State (Station state); IR 3 ErrorCode (Error code); IR 1014 Power_Total (Charging power); IR 1022 Energy_Total (Meter energy total); HR 207 Heartbeat (Heartbeat for the failsafe); HR 104 MaxCurrent (Configured maximum current).
How do I enable Modbus control of the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0?
The Modbus TCP server listens on port 502 by default. An installer may set an IP allow-list in the station's web configuration; ask for your EMS address to be added.
What happens when the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 loses Modbus communication?
Failsafe_Timeout (40204, 0 = off or 10-3600 s). If no accepted write to 40202, 40203, 40208 or 40209 arrives within the timeout, the station applies Failsafe_Current_Target (40206), sets Failsafe_Active (30027) and ErrorCode 7. Write Heartbeat (40208) at least every timeout/2.
Where is the official eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus documentation?
The source is Modbus TCP Documentation (Document version 2.3.0 (MapVersion 2.3.0)), revision 2026-11-05, published free by eCharge Hardy Barth at https://docs.echarge.de/modbus-tcp/documentation.md.
Source: Modbus TCP Documentation · Document version 2.3.0 (MapVersion 2.3.0) · rev. 2026-11-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.