eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus register map

Updated 17 November 2026

Short answer

eCharge Hardy Barth AC charging stations with the Salia controller run a Modbus TCP server on port 502 for EMS and SCADA control. Telemetry is in input registers, identity, configuration and control points in holding registers; floats and 32-bit values are big-endian with the high word first and need no scaling. Charging is controlled with a current target and a pause/allow register, with an optional heartbeat failsafe.

This page lists 77 Modbus registers for the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from eCharge Hardy Barth’s own free documentation (linked below) and checked against it.

Manufacturer
eCharge Hardy Barth
Model
eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0
Equipment type
EV charger
Registers
77 (10 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
2.5.2 (MapVersion 2.3.0)
Also known as
cPH2, cPH22T22, Hardy Barth Salia, eCharge cPH2, Hardy Barth wallbox
Source document
Modbus TCP Documentation · Document version 2.3.0 (MapVersion 2.3.0) · rev. 2026-11-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0

Integration in brief

Connect to port 502 at Unit ID 1. Set ChargeMode (40107) to MANUAL, then write the current target and Start_Stop_Charging together in one FC16 frame (40202-40203); poll EVCS_State, ErrorCode and the meter block from 30001/31001.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 201Set_Charge_Current_TargetUINT16Charge current targetRead/write
HR 202Start_Stop_ChargingUINT16Pause / allow energyRead/write
IR 0EVCS_StateUINT16Station stateRead
IR 3ErrorCodeUINT16Error codeRead
IR 1014Power_TotalFLOAT32 ABCDCharging powerRead
IR 1022Energy_TotalFLOAT32 ABCDMeter energy totalRead
HR 207HeartbeatUINT16Heartbeat for the failsafeWrite
HR 104MaxCurrentUINT16Configured maximum currentRead/write

Enable Modbus control & writes

The Modbus TCP server listens on port 502 by default. An installer may set an IP allow-list in the station's web configuration; ask for your EMS address to be added.

Communication loss & watchdog

Failsafe_Timeout (40204, 0 = off or 10-3600 s). If no accepted write to 40202, 40203, 40208 or 40209 arrives within the timeout, the station applies Failsafe_Current_Target (40206), sets Failsafe_Active (30027) and ErrorCode 7. Write Heartbeat (40208) at least every timeout/2.

Byte order & addressing

Network setup

Watch out for

eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

77 of 77 shown
eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001EVCS_StateStation state derived every 2 s.UINT16Read0 = NOT_READY; 1 = READY; 2 = CHARGING; 3 = CHARGING_INTERRUPTED; 4 = ERROR; 5 = AUTH_REJECTED (reserved); 6 = RESERVED; 7 = PHASE_SWITCHING
IR1doc 30002Connector_StateUINT16Read0 = UNPLUGGED (not reported); 1 = PLUGGED_ON_STATION_ONLY; 2 = PLUGGED_ON_STATION_AND_VEHICLE; 3 = ERROR_UNAVAILABLE
IR3doc 30004ErrorCodeHighest-priority active condition.UINT16Read0 = No error; 1 = Internal hardware fault; 2 = Over-current or short circuit; 3 = Over- or under-voltage; 4 = Over-temperature (electronics); 5 = Energy meter communication failure; 6 = Lock/plug fault; 7 = Failsafe active
IR20doc 30021AuthorizationStatus1 when the station has authorised the session.UINT16Read0 = No; 1 = Yes
IR21doc 30022AuthTypeUINT16Read0 = FREE; 1 = RFID; 2 = KEYSWITCH; 3 = OCPP
IR22doc 30023UptimeSeconds since boot.UINT32ABCDsRead
IR24doc 30025TemperatureElectronics temperature, whole degrees (not a float).UINT32ABCD°CRead
IR26doc 30027Failsafe_Active1 while the communication-loss failsafe is active.UINT16Read0 = No; 1 = Yes
IR49doc 30050DaemonStatusGateway health flags.BITMAP16Readbit 0 = units_ready - gateway ready; bit 1 = mqtt_connected - link to charger up; bit 2 = api_seed_succeeded; bit 3 = persistence_degraded - failsafe setting not yet saved; bit 4 = degraded_mode
IR100doc 30101Availability1 when the station reports operative.UINT16Read0 = No; 1 = Yes
IR101doc 30102GridCurrentLimitUINT16ARead
IR102doc 30103PhaseCount1 or 3.UINT16Read
IR103doc 30104PhysicalCurrentLimitHardware limit.UINT16ARead
IR104doc 30105OfferedCurrentLimitLimit advertised to the vehicle.UINT16ARead
IR105doc 30106CurrentOfferedTotalFLOAT32ABCDARead
IR107doc 30108CurrentOfferedL1FLOAT32ABCDARead
IR109doc 30110CurrentOfferedL2FLOAT32ABCDARead
IR111doc 30112CurrentOfferedL3FLOAT32ABCDARead
IR113doc 30114PowerOfferedFLOAT32ABCDWRead
IR200doc 30201EV_PresentUINT16Read0 = No; 1 = Yes
IR201doc 30202ChargingUINT16Read0 = No; 1 = Yes
IR202doc 30203CP_StatusIEC 61851 control pilot state.UINT16Read0 = A - standby, no vehicle; 1 = B - connected, not requesting; 2 = C - charging requested; 3 = D - ventilation required; 4 = E - error; 5 = F - EVSE fault
IR203doc 30204CP_PWM_StateUINT16Read0 = Off; 1 = On
IR204doc 30205CP_Duty_CycleFLOAT32ABCD%Read
IR219doc 30220Plug_Lock_StatusUINT16Read0 = Unlocked; 1 = Locked; 2 = Unknown
IR220doc 30221Plug_State_ActualUINT16Read0 = Unlock; 1 = Lock
IR221doc 30222Plug_State_TargetUINT16Read0 = Unlock; 1 = Lock
IR222doc 30223Plug_ErrorFirmware-specific plug-lock fault; 0 = none.UINT16Read
IR223doc 30224Contactor_StatusUINT16Read0 = Opened; 1 = Closed; 2 = Unknown
IR224doc 30225Contactor_State_ActualUINT16Read0 = Open; 1 = Close
IR225doc 30226Contactor_State_TargetUINT16Read0 = Open; 1 = Close
IR226doc 30227Contactor_ErrorFirmware-specific contactor fault; 0 = none.UINT16Read
IR227doc 30228PWM_StatusMirror of CP_Duty_Cycle.FLOAT32ABCD%Read
IR300doc 30301PhaseSwitchingEnabledAs read from the configuration at service start.UINT16Read0 = No; 1 = Yes
IR301doc 30302PhaseSwitchingStatusUINT16Read0 = IDLE; 1 = IN_PROGRESS
IR302doc 30303ActualPhase0, 1 or 3 phases on the contactor; 0 when idle.UINT16Read
IR303doc 30304TargetPhase0, 1 or 3; last commanded phase count.UINT16Read
IR400doc 30401RFID_AvailableUINT16Read0 = No; 1 = Yes
IR417doc 30418RFID_LastTagLast RFID tag seen, upper case.STRING[32]Read
IR600doc 30601ChargeMode_ActualMode the station is actually running.UINT16Read0 = ECO (PV surplus); 1 = POWER (maximum); 2 = MANUAL (EMS/user current)
IR601doc 30602EcoPlus_ActualUINT16Read0 = Off; 1 = On
IR602doc 30603PauseCharging_Actual1 while the station itself or a user has paused charging.UINT16Read0 = No; 1 = Yes
IR603doc 30604MaxCurrent_ActualLive maximum, e.g. the load-management share.UINT16ARead
IR1000doc 31001MeterFrequencyFLOAT32ABCDHzRead
IR1002doc 31003Voltage_L1FLOAT32ABCDVRead
IR1004doc 31005Voltage_L2FLOAT32ABCDVRead
IR1006doc 31007Voltage_L3FLOAT32ABCDVRead
IR1008doc 31009Current_L1FLOAT32ABCDARead
IR1010doc 31011Current_L2FLOAT32ABCDARead
IR1012doc 31013Current_L3FLOAT32ABCDARead
IR1014doc 31015Power_TotalFLOAT32ABCDWRead
IR1016doc 31017Power_L1FLOAT32ABCDWRead
IR1018doc 31019Power_L2FLOAT32ABCDWRead
IR1020doc 31021Power_L3FLOAT32ABCDWRead
IR1022doc 31023Energy_TotalLifetime meter total, not the session energy.FLOAT32ABCDkWhRead
HR0doc 40001MapVersionRegister-map version, e.g. 2.3.0.STRING[16]Read
HR8doc 40009ModelModel designation, e.g. cPH22T22.STRING[32]Read
HR24doc 40025SerialNumberSTRING[16]Read
HR32doc 40033ManufacturerSTRING[32]Read
HR48doc 40049FirmwareVersionStrFirmware version text, e.g. 2.3.75.STRING[16]Read
HR56doc 40057FirmwareVersionU32Packed version: one byte major, one byte minor, one word patch.UINT32ABCDRead
HR64doc 40065ModelTypeFixed text EV_CHARGING_STATION.STRING[24]Read
HR100doc 40101FuseRatingConfigured mains (house) fuse rating.UINT16ARead
HR101doc 40102EcoPlusTimeoutUINT16sRead
HR102doc 40103EcoReferenceGrid power reference for ECO mode; may be negative.INT16WRead
HR103doc 40104MinCurrentConfigured minimum charge current 6-32 A; saved on write.UINT16ARead/write
HR104doc 40105MaxCurrentConfigured maximum 6-32 A, not above FuseRating; saved on write.UINT16ARead/write
HR105doc 40106EcoPlusEMS setpoint; actual value at IR 30602.UINT16Read/write0 = Off; 1 = On
HR106doc 40107ChargeModeEMS setpoint; actual value at IR 30601.UINT16Read/write0 = ECO (PV surplus); 1 = POWER (maximum); 2 = MANUAL (EMS/user current)
HR201doc 40202Set_Charge_Current_Target0 stops; otherwise within MinCurrent-MaxCurrent.UINT16ARead/write
HR202doc 40203Start_Stop_ChargingPauses or allows energy; never authorises a session.UINT16Read/write0 = Pause energy; 1 = Allow energy
HR203doc 40204Failsafe_Timeout0 = off, or 10-3600 s.UINT16sRead/write
HR205doc 40206Failsafe_Current_TargetCurrent applied when the failsafe trips; 0 or within the window.UINT16ARead/write
HR207doc 40208HeartbeatWrite any value to keep the failsafe timer reset.UINT16Write
HR208doc 40209Target_Phase1 or 3; needs phase switching enabled; acts only during a session.UINT16Read/write
HR1024doc 41025MeterPhaseCount1 or 3.UINT16Read
HR1025doc 41026MeterAvailableUINT16Read0 = No; 1 = Yes

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0

What Modbus registers does the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 have?

This map lists 77 registers: 55 input registers, 22 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives the 3xxxx/4xxxx number and the zero-based PDU address; PDU = register - 30001 (input) or - 40001 (holding). The manual's example frame 06 00 C9 00 10 writes 16 A to 40202 at PDU 201.

What byte order does the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0?

Start with HR 201 Set_Charge_Current_Target (Charge current target); HR 202 Start_Stop_Charging (Pause / allow energy); IR 0 EVCS_State (Station state); IR 3 ErrorCode (Error code); IR 1014 Power_Total (Charging power); IR 1022 Energy_Total (Meter energy total); HR 207 Heartbeat (Heartbeat for the failsafe); HR 104 MaxCurrent (Configured maximum current).

How do I enable Modbus control of the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0?

The Modbus TCP server listens on port 502 by default. An installer may set an IP allow-list in the station's web configuration; ask for your EMS address to be added.

What happens when the eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 loses Modbus communication?

Failsafe_Timeout (40204, 0 = off or 10-3600 s). If no accepted write to 40202, 40203, 40208 or 40209 arrives within the timeout, the station applies Failsafe_Current_Target (40206), sets Failsafe_Active (30027) and ErrorCode 7. Write Heartbeat (40208) at least every timeout/2.

Where is the official eCharge Hardy Barth eCharge EVCS (cPH2 / Salia controller), Modbus TCP map 2.3.0 Modbus documentation?

The source is Modbus TCP Documentation (Document version 2.3.0 (MapVersion 2.3.0)), revision 2026-11-05, published free by eCharge Hardy Barth at https://docs.echarge.de/modbus-tcp/documentation.md.