Easy Modbus
  1. Home
  2. Modbus register maps
  3. Generator controllers

Equipment type

Generator controllers Modbus register maps

Updated 28 October 2026

7 generator controllers register maps from 4 manufacturers: ComAp, Datakom, SmartGen, Woodward.

7 of 7 shown

Generator controllers: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
InteliGen4 200RTU/TCP19600 baud, 8N1ABCD0-based10
D-300 / D-500 / D-700 genset controllersRTU/TCP18N116-bit only0-based29
HGM4010N / HGM4020NRTU19600 baud, 8N1CDAB0-based150
HGM6100N / HGM6100CAN SeriesRTU19600 baud, 8N116-bit only0-based145
HGM7100N SeriesRTUNot stated9600 baud, 8N116-bit only0-based81
HGM9510N / HGM9520N / HGM9530NRTU/TCP19600 baud, 8N1CDAB0-based134
easYgen-3000XT SeriesRTU/TCP119200 baud, 8N1ABCD0-based90