Easy Modbus
  1. Home
  2. Modbus register maps
  3. Woodward
  4. easYgen-3000XT Series

Generator controller · Modbus register map

Woodward easYgen-3000XT Series Modbus register map

Updated 24 October 2026

Short answer

The easYgen-3000XT is Woodward's genset controller for standby, AMF, peak-shaving and mains-parallel plants. It is a Modbus RTU slave on RS-485 and a Modbus TCP server on Ethernet. Measurements, status and alarm flags are read from a fixed telegram (protocol 5010) starting at address 50000; remote start/stop, acknowledge and interface setpoints are written to parameter addresses 503-511. This page covers generator, mains and engine values, the main status and alarm words, and the remote-control words.

This page lists 90 Modbus registers for the Woodward easYgen-3000XT Series — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.

Manufacturer
Woodward
Model
easYgen-3000XT Series
Equipment type
Generator controller
Registers
90 (8 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Release 2.17-0
Also known as
easYgen-3100XT-P1, easYgen-3200XT-P1, easYgen-3200XT-P1-LT, easYgen-3100XT, easYgen-3200XT
Source document
Manual easYgen-3000XT Series Genset Control, Release 2.17-0 · B37574 Revision U · rev. 2025
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Woodward easYgen-3000XT Series

Integration in brief

Block-read holding registers from 50000 (up to 128 per request) for status and alarms, and the 32-bit generator and mains values at 50322-50411. To start or stop the set, write parameter 503 with 0 and then the start (bit 0) or stop (bit 1) bit; acknowledge alarms by pulsing bit 4 twice.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 50099Control modeBITMAP16Operating mode (AUTO/STOP/MANUAL/TEST)Read
HR 50104Control bits 3BITMAP16GCB / MCB closed flagsRead
HR 50114Alarm generalBITMAP16Latched alarm classes A-FRead
HR 50009Generator frequencyINT16Generator frequencyRead
HR 50322Total generator active powerINT32 ABCDTotal generator active power (32-bit)Read
HR 50346Generator voltage L1-L2INT32 ABCDGenerator voltage L1-L2 (32-bit)Read
HR 50336Generator current 1INT32 ABCDGenerator current 1 (32-bit)Read
HR 50052Battery voltageINT16Battery voltageRead
HR 503Remote control word 1BITMAP16Remote start / stop / acknowledgeRead/write

Enable Modbus control & writes

RS-485: set Modbus slave ID (parameter 3188, default 1; 0 disables Modbus) and baud/parity/stop bits (3170-3172). Ethernet: set Modbus/TCP slave ID (7485) and the Ethernet A IP settings, then turn on the matching 'Set IP address' parameter. Protocol number 3184 must stay 5010 for this map; a change needs a reboot. For a remote start, the LogicsManager start request must include 04.13 Remote request.

Communication loss & watchdog

No Modbus communication timeout is documented. Bits 2 and 3 of parameter 503 must always be 0; the manual reserves them for a watchdog. A remote start request (04.13) stays set until a stop bit arrives or power is lost.

Byte order & addressing

Network setup

Watch out for

Woodward easYgen-3000XT Series Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

90 of 90 shown
Woodward easYgen-3000XT Series Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR503doc 40504 (parameter 503)Remote control word 1Start, stop, acknowledge and shutdown on rising edges; write 0 then 1.BITMAP16Read/writebit 0 = Start (rising edge); bit 1 = Stop (rising edge); bit 2 = Must always be 0; bit 3 = Must always be 0; bit 4 = External acknowledge (rising edge, needed twice); bit 9 = Shutdown command (rising edge)
HR504doc 40505 (parameter 504)Remote control word 2Selects setpoint 2 instead of setpoint 1 for P, PF, frequency, voltage.BITMAP16Read/writebit 4 = Request voltage setpoint 2 (04.37); bit 5 = Request frequency setpoint 2 (04.38); bit 6 = Request power factor setpoint 2 (04.39); bit 7 = Request active power setpoint 2 (04.40)
HR505doc 40506 (parameter 505)Remote control word 3Sixteen free remote-control bits for LogicsManager use.BITMAP16Read/writebit 0 = Remote control bit 1 (04.44); bit 1 = Remote control bit 2 (04.45); bit 2 = Remote control bit 3 (04.46); bit 3 = Remote control bit 4 (04.47); bit 4 = Remote control bit 5 (04.48); bit 5 = Remote control bit 6 (04.49); bit 6 = Remote control bit 7 (04.50); bit 7 = Remote control bit 8 (04.51); bit 8 = Remote control bit 9 (04.52); bit 9 = Remote control bit 10 (04.53); bit 10 = Remote control bit 11 (04.54); bit 11 = Remote control bit 12 (04.55); bit 12 = Remote control bit 13 (04.56); bit 13 = Remote control bit 14 (04.57); bit 14 = Remote control bit 15 (04.58); bit 15 = Remote control bit 16 (04.59)
HR507doc 40508 (parameter 507)Remote active power setpointInterface P setpoint (05.56), kW x 10. Write 2 registers at this address; used only if an AnalogManager selects it.INT32ABCD× 0.1kWRead/write
HR508doc 40509 (parameter 508)Remote power factor setpointInterface PF setpoint (05.12); 1000 = 1.00, +710 inductive, -710 capacitive. Separate from 507.INT16× 0.001Read/write
HR509doc 40510 (parameter 509)Remote frequency setpointInterface frequency setpoint (05.53); 5000 = 50.00 Hz. Its own parameter.INT16× 0.01HzRead/write
HR510doc 40511 (parameter 510)Remote voltage setpointInterface voltage setpoint (05.59); 400 = 400 V. Write 2 registers at this address.UINT32ABCDVRead/write
HR511doc 40512 (parameter 511)Remote reactive power setpointInterface kvar setpoint (05.83), signed; 1000 = 100.0 kvar. Write 2 registers at this address.INT32ABCD× 0.1kvarRead/write
HR50000Protocol IDAlways reads 5010 when the default visualization protocol is active.INT16Read
HR50009Generator frequencyINT16× 0.01HzRead
HR50012Generator power factorTransmitted as PF x 1000.INT16× 0.001Read
HR50022Busbar 1 frequencyINT16× 0.01HzRead
HR50030Mains frequencyINT16× 0.01HzRead
HR50033Mains power factorTransmitted as PF x 1000.INT16× 0.001Read
HR50045Nominal real power in systemINT16× 0.01%Read
HR50046Real power in systemINT16× 0.01%Read
HR50047Reserve real power in systemINT16× 0.01%Read
HR50051Engine pickup speedSpeed from the magnetic pickup input.INT16rpmRead
HR50052Battery voltageINT16× 0.1VRead
HR50053Auxiliary excitation D+Charging alternator D+ voltage.INT16× 0.1VRead
HR50054Engine number of start requestsINT16Read
HR50055Hours until next maintenanceINT16hRead
HR50094Days until next maintenanceINT16daysRead
HR50099Control modeActive operating mode; only the low four bits (mask 000Fh) are used.BITMAP16Readbit 0 = AUTO; bit 1 = STOP; bit 2 = MANUAL; bit 3 = TEST
HR50100Status messageIndex of the current status text; see the manual's status messages chapter.INT16Read
HR50102Control bits 1Engine sequence flags: start/stop requests, cooldown, engine release.BITMAP16Readbit 0 = 04.61 Lamp test request; bit 1 = 03.31 Auxiliary services postrun active; bit 2 = 03.30 Auxiliary services prerun active; bit 3 = 03.06 Engine release is active; bit 4 = 04.27 Critical mode is active; bit 5 = 03.25 Engine shall run; bit 6 = 03.08 Breaker delay timer expired; bit 7 = 03.07 Engine monitoring delay expired; bit 8 = 03.01 Auxiliary services active; bit 9 = 04.10 Cooldown is active; bit 10 = Manual STOP requested; bit 11 = Manual START requested; bit 12 = 04.64 Key activation; bit 13 = 04.12 Start without closing GCB; bit 14 = 04.15 Idle run is active; bit 15 = Idle mode or ramp to rated active
HR50103Control bits 2Starter, ignition, emergency mode and mains-parallel flags.BITMAP16Readbit 0 = Increment engine start counter; bit 1 = 03.36 Free PID 1 raise; bit 2 = 03.37 Free PID 1 lower; bit 3 = Genset runs mains parallel; bit 5 = 03.27 Stop solenoid is active; bit 6 = 03.34 Free PID 2 raise; bit 7 = 03.35 Free PID 2 lower; bit 8 = 03.32 Free PID 3 raise; bit 9 = 03.33 Free PID 3 lower; bit 10 = 03.40 Remote shutdown (ID 503 bit 9); bit 11 = 04.09 Emergency mode is active; bit 12 = 04.11 Mains settling; bit 13 = 03.04 Preglow or ignition is active; bit 14 = 03.28 Operating magnet / gas relay active; bit 15 = 03.02 Starter / crank is active
HR50104Control bits 3Breaker states and synchronising / open / close commands.BITMAP16Readbit 0 = 04.30 Power limited prerun; bit 1 = 04.29 Unloading mains active; bit 2 = 04.28 Unloading generator active; bit 3 = 04.23 Close command MCB active; bit 4 = 04.22 Open command MCB active; bit 5 = 04.21 MCB synchronisation active; bit 6 = 04.20 Close command GCB active; bit 7 = 04.19 Opening GCB relay active; bit 8 = 04.18 GCB synchronisation active; bit 9 = 05.16 Derating active; bit 10 = 04.07 MCB is closed; bit 11 = 04.06 GCB is closed; bit 12 = 03.23 3-pos. controller volt./reactive power lower; bit 13 = 03.22 3-pos. controller volt./reactive power raise; bit 14 = 03.21 3-pos. controller freq./power lower; bit 15 = 03.20 3-pos. controller freq./power raise
HR50106Control bits 5Remote request / acknowledge echo, droop and sync-mode flags.BITMAP16Readbit 3 = 04.70 Opening GCB active; bit 4 = 02.39 Mains decoupling enabled; bit 5 = 86.42 LDSS MOP reserve power 2 ready; bit 6 = 86.41 LDSS IOP reserve power 2 ready; bit 7 = 86.85 LM Enable MCB; bit 8 = Sync mode Run active; bit 9 = Sync mode Permissive active; bit 10 = Sync mode Check active; bit 11 = 86.26 LM voltage droop active; bit 12 = 86.25 LM frequency droop active; bit 13 = 05.17 Uprating active; bit 14 = 04.14 Remote acknowledge; bit 15 = 04.13 Remote start request
HR50108Relay outputs 1State of relay outputs 1-12.BITMAP16Readbit 4 = Relay 12; bit 5 = Relay 11; bit 6 = Relay 10; bit 7 = Relay 9; bit 8 = Relay 8; bit 9 = Relay 7; bit 10 = Relay 6; bit 11 = Relay 5; bit 12 = Relay 4; bit 13 = Relay 3; bit 14 = Relay 2; bit 15 = Relay 1 (self-test relay)
HR50114Alarm generalNew-alarm flag and latched alarm classes A-F.BITMAP16Readbit 0 = 01.01 Alarm class A latched; bit 1 = 01.02 Alarm class B latched; bit 2 = 01.03 Alarm class C latched; bit 3 = 01.04 Alarm class D latched; bit 4 = 01.05 Alarm class E latched; bit 5 = 01.06 Alarm class F latched; bit 15 = 01.11 New alarm triggered
HR50115Alarms 2 latchedUnacknowledged sync timeouts, breaker 50BF failures, ECU lamp alarms.BITMAP16Readbit 0 = 05.14 ECU amber lamp alarm; bit 1 = 05.13 ECU red lamp alarm; bit 2 = 08.48 MCB plausibility; bit 3 = 08.17 Missing members; bit 4 = 08.16 Parameter alignment LDSS; bit 5 = 08.19 CANopen error CAN interface 2; bit 6 = 05.23 ECU emission alarm; bit 7 = 05.22 ECU protect alarm; bit 8 = 08.46 GCB failure 50BF; bit 9 = 08.47 MCB failure 50BF; bit 10 = 08.45 CPU overload R1 trip; bit 11 = Operating range failure 12; bit 12 = 05.11 Charge fail (D+); bit 14 = 08.31 Timeout synchronisation MCB; bit 15 = 08.30 Timeout synchronisation GCB
HR50120Alarms 1 latched (engine)Unacknowledged engine, start-fail, breaker-fail and maintenance alarms.BITMAP16Readbit 0 = 08.18 CANopen error CAN interface 1; bit 1 = 05.10 Maintenance hours exceeded; bit 2 = 05.09 Maintenance days exceeded; bit 3 = 05.08 Start fail detected; bit 4 = 08.10 General CAN-J1939 fault; bit 5 = 08.08 MCB fail to open; bit 6 = 08.07 MCB fail to close; bit 7 = 08.06 GCB fail to open; bit 8 = 08.05 GCB fail to close; bit 9 = 05.06 Shutdown malfunction detected; bit 10 = 05.07 Speed detection alarm; bit 11 = 05.05 Unintended stop detected; bit 12 = 05.04 Engine underspeed 2; bit 13 = 05.03 Engine underspeed 1; bit 14 = 05.02 Engine overspeed 2; bit 15 = 05.01 Engine overspeed 1
HR50122Alarms AI 1 latched (battery)Unacknowledged battery voltage and charging alternator alarms.BITMAP16Readbit 0 = 08.03 Battery undervoltage 1; bit 1 = 08.01 Battery overvoltage 1; bit 2 = 08.04 Battery undervoltage 2; bit 3 = 08.02 Battery overvoltage 2; bit 4 = 05.11 Failure charging alternator (D+)
HR50126Alarms generator latchedUnacknowledged generator frequency, voltage, current and power alarms.BITMAP16Readbit 1 = 06.15 Gen overload IOP 2; bit 2 = 06.14 Gen overload IOP 1; bit 3 = 06.13 Reverse / reduced power 2; bit 4 = 06.12 Reverse / reduced power 1; bit 5 = 06.11 Gen overcurrent 3; bit 6 = 06.10 Gen overcurrent 2; bit 7 = 06.09 Gen overcurrent 1; bit 8 = 06.08 Gen undervoltage 2; bit 9 = 06.07 Gen undervoltage 1; bit 10 = 06.06 Gen overvoltage 2; bit 11 = 06.05 Gen overvoltage 1; bit 12 = 06.04 Gen underfrequency 2; bit 13 = 06.03 Gen underfrequency 1; bit 14 = 06.02 Gen overfrequency 2; bit 15 = 06.01 Gen overfrequency 1
HR50128Alarms generator 1 latchedUnacknowledged unbalance, ground fault, rotation, overload MOP and PF alarms.BITMAP16Readbit 0 = 06.28 Gen PF leading 2; bit 1 = 06.27 Gen PF leading 1; bit 2 = 06.26 Gen PF lagging 2; bit 3 = 06.25 Gen PF lagging 1; bit 4 = 06.24 Gen overload MOP 2; bit 5 = 06.23 Gen overload MOP 1; bit 6 = 06.31 Operating range failed; bit 7 = 06.22 Inverse time overcurrent; bit 8 = 06.30 Gen unloading mismatch; bit 9 = 06.29 Gen active power mismatch; bit 10 = 06.21 Gen phase rotation mismatch; bit 11 = 06.20 Ground fault 2; bit 12 = 06.19 Ground fault 1; bit 13 = 06.18 Gen voltage asymmetry; bit 14 = 06.17 Gen unbalanced load 2; bit 15 = 06.16 Gen unbalanced load 1
HR50132Alarms mains latchedUnacknowledged mains frequency, voltage, phase shift and decoupling alarms.BITMAP16Readbit 2 = 07.05 Mains phase rotation mismatch; bit 5 = 07.32 Mains AC wiring; bit 6 = 07.25 Mains decoupling; bit 7 = 07.14 Mains phase shift; bit 8 = 07.13 Mains undervoltage 2; bit 9 = 07.12 Mains undervoltage 1; bit 10 = 07.11 Mains overvoltage 2; bit 11 = 07.10 Mains overvoltage 1; bit 12 = 07.09 Mains underfrequency 2; bit 13 = 07.08 Mains underfrequency 1; bit 14 = 07.07 Mains overfrequency 2; bit 15 = 07.06 Mains overfrequency 1
HR50133Alarms mains activeSame mains alarms as 50132, showing the currently active state.BITMAP16Readbit 2 = Mains phase rotation mismatch; bit 5 = Mains AC wiring; bit 6 = Mains decoupling; bit 7 = Mains phase shift; bit 8 = Mains undervoltage 2; bit 9 = Mains undervoltage 1; bit 10 = Mains overvoltage 2; bit 11 = Mains overvoltage 1; bit 12 = Mains underfrequency 2; bit 13 = Mains underfrequency 1; bit 14 = Mains overfrequency 2; bit 15 = Mains overfrequency 1
HR50138Alarms DI 1 latchedUnacknowledged alarms from discrete inputs 1-12 (inputs with alarm class Control show here only if parameter 8854 allows it).BITMAP16Readbit 4 = 09.12 Discrete input 12; bit 5 = 09.11 Discrete input 11; bit 6 = 09.10 Discrete input 10; bit 7 = 09.09 Discrete input 9; bit 8 = 09.08 Discrete input 8; bit 9 = 09.07 Discrete input 7; bit 10 = 09.06 Discrete input 6; bit 11 = 09.05 Discrete input 5; bit 12 = 09.04 Discrete input 4; bit 13 = 09.03 Discrete input 3; bit 14 = 09.02 Discrete input 2; bit 15 = 09.01 Discrete input 1
HR50159Alarms AI wire break latchedWire-break alarms for analog inputs 1-3; bit 0 is unused here.BITMAP16Readbit 1 = 10.01 Analog input 1 wire break; bit 2 = 10.02 Analog input 2 wire break; bit 3 = 10.03 Analog input 3 wire break
HR50191J1939 lamp status DM1ECU lamp states from the active-fault (DM1) message.BITMAP16Readbit 0 = Protect lamp off; bit 1 = Protect lamp on; bit 4 = Amber warning lamp off; bit 5 = Amber warning lamp on; bit 8 = Red stop lamp off; bit 9 = Red stop lamp on; bit 12 = Malfunction lamp off; bit 13 = Malfunction lamp on
HR50201J1939 engine speed (SPN 190)From the engine ECU over J1939; needs the ECU connected.INT16rpmRead
HR50202J1939 coolant temperature (SPN 110)From the engine ECU over J1939; needs the ECU connected.INT16°CRead
HR50203J1939 fuel temperature (SPN 174)From the engine ECU over J1939; needs the ECU connected.INT16°CRead
HR50204J1939 engine oil temperature 1 (SPN 175)From the engine ECU over J1939; needs the ECU connected.INT16× 0.1°CRead
HR50205J1939 engine oil pressure (SPN 100)From the engine ECU over J1939; needs the ECU connected.INT16kPaRead
HR50206J1939 fuel rate (SPN 183)From the engine ECU over J1939; needs the ECU connected.INT16× 0.1L/hRead
HR50207J1939 coolant level (SPN 111)From the engine ECU over J1939; needs the ECU connected.INT16× 0.1%Read
HR50209J1939 load at current speed (SPN 92)From the engine ECU over J1939; needs the ECU connected.INT16%Read
HR50211J1939 boost pressure (SPN 102)From the engine ECU over J1939; needs the ECU connected.INT16kPaRead
HR50216J1939 exhaust gas temperature (SPN 173)From the engine ECU over J1939; needs the ECU connected.INT16× 0.1°CRead
HR50322Total generator active powerINT32ABCDWRead
HR50324Total generator reactive powerINT32ABCDvarRead
HR50326Total generator apparent powerINT32ABCDVARead
HR50328Average generator wye voltageAverage line-to-neutral voltage.INT32ABCD× 0.1VRead
HR50330Average generator delta voltageAverage line-to-line voltage.INT32ABCD× 0.1VRead
HR50332Average busbar 1 delta voltageINT32ABCD× 0.1VRead
HR50334Average generator currentINT32ABCD× 0.001ARead
HR50336Generator current 1INT32ABCD× 0.001ARead
HR50338Generator current 2INT32ABCD× 0.001ARead
HR50340Generator current 3INT32ABCD× 0.001ARead
HR50342Measured ground currentINT32ABCD× 0.001ARead
HR50346Generator voltage L1-L2INT32ABCD× 0.1VRead
HR50348Generator voltage L2-L3INT32ABCD× 0.1VRead
HR50350Generator voltage L3-L1INT32ABCD× 0.1VRead
HR50352Generator voltage L1-NINT32ABCD× 0.1VRead
HR50354Generator voltage L2-NINT32ABCD× 0.1VRead
HR50356Generator voltage L3-NINT32ABCD× 0.1VRead
HR50358Generator active power L1-NINT32ABCDWRead
HR50360Generator active power L2-NINT32ABCDWRead
HR50362Generator active power L3-NINT32ABCDWRead
HR50364Busbar 1 voltage L1-L2INT32ABCD× 0.1VRead
HR50366Generator real energyActive energy counter.INT32ABCD× 0.01MWhRead
HR50368Generator positive reactive energyINT32ABCD× 0.01MvarhRead
HR50370Generator hours of operationRun-hours counter kept by the controller.INT32ABCD× 0.01hRead
HR50372Setpoint active powerActive power setpoint currently in use.INT32ABCD× 0.1kWRead
HR50374Setpoint voltageVoltage setpoint currently in use.INT32ABCDVRead
HR50384Total mains active powerINT32ABCDWRead
HR50386Total mains reactive powerINT32ABCDvarRead
HR50388Average mains wye voltageINT32ABCD× 0.1VRead
HR50390Average mains delta voltageINT32ABCD× 0.1VRead
HR50392Average mains currentINT32ABCD× 0.001ARead
HR50394Mains current L1INT32ABCD× 0.001ARead
HR50400Mains voltage L1-L2INT32ABCD× 0.1VRead
HR50402Mains voltage L2-L3INT32ABCD× 0.1VRead
HR50404Mains voltage L3-L1INT32ABCD× 0.1VRead
HR50406Mains voltage L1-NINT32ABCD× 0.1VRead
HR50408Mains voltage L2-NINT32ABCD× 0.1VRead
HR50410Mains voltage L3-NINT32ABCD× 0.1VRead
HR50444J1939 total engine hoursEngine hours reported by the ECU (J1939 HOURS).UINT32ABCDhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Woodward easYgen-3000XT Series

What Modbus registers does the Woodward easYgen-3000XT Series have?

This map lists 90 registers: 90 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Woodward easYgen-3000XT Series Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol 5010 table in the appendix prints wire addresses (Protocol ID at 50000). The Modbus chapter shows the same block Modicon-style from 450001 and says 450001 can become bus address 50000. Parameters (remote control, setpoints) use Modicon address = 40000 + (parameter ID + 1), so parameter 503 is 40504 and wire address 503. The manual warns some PC tools need a shift of one (e.g. 504); if a write has no effect, try the neighbour.

What byte order does the Woodward easYgen-3000XT Series use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Woodward easYgen-3000XT Series?

Start with HR 50099 Control mode (Operating mode (AUTO/STOP/MANUAL/TEST)); HR 50104 Control bits 3 (GCB / MCB closed flags); HR 50114 Alarm general (Latched alarm classes A-F); HR 50009 Generator frequency (Generator frequency); HR 50322 Total generator active power (Total generator active power (32-bit)); HR 50346 Generator voltage L1-L2 (Generator voltage L1-L2 (32-bit)); HR 50336 Generator current 1 (Generator current 1 (32-bit)); HR 50052 Battery voltage (Battery voltage); HR 503 Remote control word 1 (Remote start / stop / acknowledge).

How do I enable Modbus control of the Woodward easYgen-3000XT Series?

RS-485: set Modbus slave ID (parameter 3188, default 1; 0 disables Modbus) and baud/parity/stop bits (3170-3172). Ethernet: set Modbus/TCP slave ID (7485) and the Ethernet A IP settings, then turn on the matching 'Set IP address' parameter. Protocol number 3184 must stay 5010 for this map; a change needs a reboot. For a remote start, the LogicsManager start request must include 04.13 Remote request.

What happens when the Woodward easYgen-3000XT Series loses Modbus communication?

No Modbus communication timeout is documented. Bits 2 and 3 of parameter 503 must always be 0; the manual reserves them for a watchdog. A remote start request (04.13) stays set until a stop bit arrives or power is lost.

Where is the official Woodward easYgen-3000XT Series Modbus documentation?

The source is Manual easYgen-3000XT Series Genset Control, Release 2.17-0 (B37574 Revision U), revision 2025, published free by Woodward at https://www.woodward.com/products/wp-content/uploads/sites/3/2025/04/B37574_U.pdf.

Source: Manual easYgen-3000XT Series Genset Control, Release 2.17-0 · B37574 Revision U · rev. 2025. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.