Solar inverter · Modbus register map

Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA Modbus register map

Updated 28 October 2026

Short answer

Schneider's Conext CL is a three-phase grid-tie string inverter with two MPPT inputs and Modbus RTU on RS-485 plus Modbus TCP. All data are holding registers in a vendor map that also embeds SunSpec models 1, 103 and 160 from 0x9C40. This map covers identity strings, lifetime energy, operating state, temperatures, grid voltages, currents, power and frequency, PV input values, the alarm code, the remote on/off command and the active-power limit.

This page lists 51 Modbus registers for the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
Conext CL three-phase PV inverter 18/20/25 kVA
Equipment type
Solar inverter
Registers
51 (6 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
10
Default serial
9600 baud, 8N1
TCP port
502
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA
Source document
Modbus Registers Map - Conext CL Three Phase PV Inverter 20/25kVA · 503-0243-01-01 Rev 1.5 · rev. 2016-03-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA

Integration in brief

Read 0x1700 for the operating state, 0x1828 for the alarm, 0x17FE for output power and 0x0802 for lifetime energy with function 3. Limit export by writing 0xFA19 (kW x10) or 0xFAF1 (%), and switch the inverter off or on line by writing 0x6B43 / 0x6B44 to 0xEFFE.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 5888Operational mode stateUINT16Operating stateRead
HR 6184Inverter alarm codeUINT16Active alarm codeRead
HR 6142Active powerINT16AC output powerRead
HR 2050Energy produced (lifetime)UINT32 ABCDLifetime energyRead
HR 6146Grid frequencyUINT16Grid frequencyRead
HR 6139Grid current L1INT16Phase L1 currentRead
HR 64241User active power percentageUINT16Active power limit %Read/write
HR 61438Remote disable/enableUINT16Remote on/off commandRead/write

Enable Modbus control & writes

No enable step is described; the RS-485 port answers at the configured address (default 10). Modbus TCP needs the IP address, port 502 and slave address.

Byte order & addressing

Network setup

Watch out for

Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

51 of 51 shown
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0x0001 - 0x0009Product model designationInverter + BOS model as null-terminated ASCII, e.g. PVSCL25E301E.STRING[18]Read
HR20doc 0x0014 - 0x001DProduct serial numberNull-terminated ASCII.STRING[20]Read
HR40doc 0x0028 - 0x0031Inverter model designationNull-terminated ASCII, e.g. PVSCL25E.STRING[20]Read
HR2050doc 0x0802 (H word) - 0x0803 (L word)Energy produced (lifetime)Energy produced since commissioning.UINT32ABCD× 0.1kWhRead
HR5888doc 0x1700Operational mode stateVendor operating state (hex codes 15h-17h).UINT16Read2 = Reconnecting to grid; 3 = Online and producing power; 21 = No PV (15h); 22 = Offline due to services/errors (16h); 23 = Power derate (17h)
HR5889doc 0x1701Control board temperature (ambient)INT16× 0.1°CRead
HR5890doc 0x1702DC module 1-2 temperatureINT16× 0.1°CRead
HR5891doc 0x1703DC module 3-4 temperatureINT16× 0.1°CRead
HR5893doc 0x1705Grid current (sum of phases)UINT16× 0.1ARead
HR5894doc 0x1706Inverter module A temperatureINT16× 0.1°CRead
HR5895doc 0x1707Inverter module B temperatureINT16× 0.1°CRead
HR5896doc 0x1708Inverter module C temperatureINT16× 0.1°CRead
HR5897doc 0x1709Phase A to neutral voltageINT16× 0.1VRead
HR5898doc 0x170APhase B to neutral voltageINT16× 0.1VRead
HR5899doc 0x170BPhase C to neutral voltageINT16× 0.1VRead
HR6129doc 0x17F1Grid apparent powerUINT16× 0.1kVARead
HR6132doc 0x17F4Grid reactive powerINT16× 0.1kvarRead
HR6136doc 0x17F8Grid voltage L1-L2INT16× 0.1VRead
HR6137doc 0x17F9Grid voltage L2-L3INT16× 0.1VRead
HR6138doc 0x17FAGrid voltage L3-L1INT16× 0.1VRead
HR6139doc 0x17FBGrid current L1Inverter phase A output current.INT16× 0.1ARead
HR6140doc 0x17FCGrid current L2Inverter phase B output current.INT16× 0.1ARead
HR6141doc 0x17FDGrid current L3Inverter phase C output current.INT16× 0.1ARead
HR6142doc 0x17FEActive powerInverter real output power.INT16× 0.1kWRead
HR6143doc 0x17FFPV1 voltageINT16× 0.1VRead
HR6144doc 0x1800PV1 currentINT16× 0.1ARead
HR6145doc 0x1801PV1 powerINT16× 0.1kWRead
HR6146doc 0x1802Grid frequencyUINT16× 0.1HzRead
HR6168doc 0x1818Phase A frequencyUINT16× 0.1HzRead
HR6169doc 0x1819Phase B frequencyUINT16× 0.1HzRead
HR6170doc 0x181APhase C frequencyUINT16× 0.1HzRead
HR6171doc 0x181BPhase A real powerINT16× 0.1kWRead
HR6172doc 0x181CPhase B real powerINT16× 0.1kWRead
HR6173doc 0x181DPhase C real powerINT16× 0.1kWRead
HR6184doc 0x1828Inverter alarm codeActive alarm number; 0000 = none. Code table is in section 4 of the map.UINT16Read
HR6185doc 0x1829PV2 voltageINT16× 0.1VRead
HR6186doc 0x182APV2 currentINT16× 0.1ARead
HR6191doc 0x182FPV2 powerINT16× 0.1kWRead
HR32771doc 0x8003Modbus slave address1-247, default 10; power-cycle the unit to apply.UINT16Read/write
HR32784doc 0x8010Modbus baud rateMay need a power cycle to apply.UINT16Read/write0 = 9600; 1 = 19200; 2 = 38400; 3 = 57600; 4 = 115200
HR40072doc 0x9C88SunSpec AC currentTotal AC current (SunSpec model 103).UINT16× 10^SF (HR 40076)ARead
HR40076doc 0x9C8CSunSpec AC current scale factorPower-of-ten exponent for 0x9C88-0x9C8B; documented as -1.INT16Read
HR40084doc 0x9C94SunSpec AC powerINT16× 10^SF (HR 40085)WRead
HR40085doc 0x9C95SunSpec AC power scale factorPower-of-ten exponent for 0x9C94; documented as 2.INT16Read
HR40086doc 0x9C96SunSpec AC frequencyUINT16× 10^SF (HR 40087)HzRead
HR40087doc 0x9C97SunSpec AC frequency scale factorPower-of-ten exponent for 0x9C96; documented as -1.INT16Read
HR40108doc 0x9CACSunSpec operating statusUINT16Read1 = Off; 3 = Starting; 4 = MPPT; 5 = Throttled; 7 = Fault
HR61438doc 0xEFFERemote disable/enableWrite a command code to reset the inverter or take it off/on line.UINT16Read/write0 = Normal operation (default after reboot); 27458 = Reset inverter (0x6B42, no reply); 27459 = Inverter offline (0x6B43); 27460 = Inverter online (0x6B44)
HR64025doc 0xFA19User active power limitOutput power cap, 0-25 kW entered as 0-250.UINT16× 0.1kWRead/write
HR64144doc 0xFA90Inverter modeGrid-tie or local-consumption (PV hybrid) behaviour.UINT16Read/write0 = Grid tie mode (default); 27461 = Local consumption mode (0x6B45)
HR64241doc 0xFAF1User active power percentageOutput power cap as % of rating, default 100.UINT16%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA

What Modbus registers does the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA have?

This map lists 51 registers: 51 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints addresses in hex and says they are 0-based ('on the wire') addresses, not 1-based. So 0x17FE (active power) is requested as 6142 decimal with no offset.

What byte order does the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA?

Start with HR 5888 Operational mode state (Operating state); HR 6184 Inverter alarm code (Active alarm code); HR 6142 Active power (AC output power); HR 2050 Energy produced (lifetime) (Lifetime energy); HR 6146 Grid frequency (Grid frequency); HR 6139 Grid current L1 (Phase L1 current); HR 64241 User active power percentage (Active power limit %); HR 61438 Remote disable/enable (Remote on/off command).

How do I enable Modbus control of the Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA?

No enable step is described; the RS-485 port answers at the configured address (default 10). Modbus TCP needs the IP address, port 502 and slave address.