Manufacturer
ASCO Modbus register maps
Updated 17 November 2026
2 ASCO models, 97 registers in all, each re-typed from ASCO’s own free documentation and checked against it.
2 of 2 shown
- Transfer switch controller
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)
ASCO 7000 Series Group 5 controller, firmware 607540-023 (some bits 607540-033); document 381339-221 revision I. Power Manager Xp registers in the same document are not included.
Also known as: ASCO 7000 Group 5, Group 5 Controller, 381339-221 - Power meter (transfer switch metering)
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
ASCO Power Manager Xp, firmware FS611842-006 (some registers AS629262-004); document 381339-221 revision I.
Also known as: ASCO Power Manager Xp, Power Manager Xp, 381339-221
ASCO: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| 7000 Series Group 5 transfer switch controller (Modbus RTU) | RTU | Not stated | 8N1 | 16-bit only | Modicon | 35 |
| Power Manager Xp power meter for transfer switches (Modbus RTU) | RTU | Not stated | 8N1 | CDAB | Modicon | 62 |