Easy Modbus
  1. Home
  2. Modbus register maps
  3. ASCO
  4. 7000 Series Group 5 transfer switch controller (Modbus RTU)

Transfer switch controller · Modbus register map

ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Group 5 controller runs ASCO 7000 Series automatic transfer switches. Through its Modbus RTU interface it reports normal and emergency source voltages and frequencies, switch position, source availability, phase rotation, alarms, the transfer-sequence state with its timer value, active features and the event log.

This page lists 35 Modbus registers for the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ASCO’s own free documentation (linked below) and checked against it.

Manufacturer
ASCO
Model
7000 Series Group 5 transfer switch controller (Modbus RTU)
Equipment type
Transfer switch controller
Registers
35 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
607540-023 (bits marked 607540-033 need that version)
Also known as
ASCO 7000 Group 5, Group 5 Controller, 381339-221
Source document
Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)

Integration in brief

Read 40015 (switch position and source availability), 40017-40024 (normal and emergency voltages), 40013/40014 (frequencies), 40040 (alarms) and 40041/40042 (transfer state and timer) with FC03, max 12 registers per read.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 14Switch position and source availabilityBITMAP16Switch position and source availabilityRead
HR 16NV_AB - normal voltage A-BUINT16Normal voltage A-BRead
HR 20EV_AB - emergency voltage A-BUINT16Emergency voltage A-BRead
HR 12NFRQ_0 - normal frequencyUINT16Normal frequencyRead
HR 39Alarm and lockout statusBITMAP16Alarm / lockout / engine runningRead
HR 40CPState - control panel stateUINT16Transfer sequence stateRead

Enable Modbus control & writes

Address and baud rate are set on the Group 5 controller; this document does not describe how (it refers to the Group 5 Controller User's Guide 381333-126).

Byte order & addressing

Network setup

Watch out for

ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

35 of 35 shown
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR11doc 40012PHASE_0 - phase shift normal vs emergencyINT16× 0.1°Read
HR12doc 40013NFRQ_0 - normal frequencyUINT16× 0.01HzRead
HR13doc 40014EFRQ_0 - emergency frequencyUINT16× 0.01HzRead
HR14doc 40015Switch position and source availabilityBITMAP16Readbit 0 = Main on normal; bit 1 = Main on emergency; bit 2 = Auxiliary on normal; bit 3 = Auxiliary on emergency; bit 4 = Normal source available; bit 5 = Emergency source available
HR15doc 40016Phase rotation and exerciser statusBITMAP16Readbit 0 = Normal rotation ABC; bit 1 = Normal rotation CBA; bit 2 = Emergency rotation ABC; bit 3 = Emergency rotation CBA; bit 4 = Engine exerciser with load active; bit 6 = External F17 active
HR16doc 40017NV_AB - normal voltage A-BUINT16VRead
HR17doc 40018NV_BC - normal voltage B-CUINT16VRead
HR18doc 40019NV_CA - normal voltage C-AUINT16VRead
HR19doc 40020NVUnbl - normal voltage unbalanceUINT16%Read
HR20doc 40021EV_AB - emergency voltage A-BUINT16VRead
HR21doc 40022EV_BC - emergency voltage B-CUINT16VRead
HR22doc 40023EV_CA - emergency voltage C-AUINT16VRead
HR23doc 40024EVUnbl - emergency voltage unbalanceUINT16%Read
HR24doc 40025I_NOM_V - nominal voltage codeUINT16Read0 = 115 V; 1 = 120 V; 2 = 208 V; 3 = 220 V; 4 = 230 V; 5 = 240 V; 6 = 277 V; 7 = 380 V; 8 = 400 V; 9 = 415 V; 10 = 440 V; 11 = 460 V; 12 = 480 V; 13 = 550 V; 14 = 575 V; 15 = 600 V
HR25doc 40026Switch configurationBits 3-4 = switch type: 0 OTTS, 1 DTTS, 2 CTTS, 3 OTTS.BITMAP16Readbit 0 = Nominal 60 Hz (else 50 Hz); bit 1 = Normal 3-phase sensing; bit 2 = Emergency 3-phase sensing; bit 3 = Switch type bit 0; bit 4 = Switch type bit 1; bit 5 = Bypass switch; bit 6 = Dual breaker (else transfer switch), FW 607540-033
HR26doc 40027TSAmp - transfer switch amp rating codeUINT16Read0 = 30 A; 1 = 70 A; 2 = 100 A; 3 = 150 A; 4 = 260 A; 5 = 400 A; 6 = 600 A; 7 = 800 A; 8 = 1000 A; 9 = 1200 A; 10 = 1600 A; 11 = 2000 A; 12 = 3000 A; 13 = 4000 A; 14 = Other; 15 = Other
HR27doc 40028LCD_CP_VER - control panel software version10-character string.STRING[12]Read
HR33doc 40034LCD_CP_DATE - control panel software date10-character string.STRING[12]Read
HR39doc 40040Alarm and lockout statusBITMAP16Readbit 0 = Transfer switch locked out; bit 1 = CTTS extended parallel alarm; bit 2 = CTTS failure to synch alarm; bit 3 = DTTS load disconnect; bit 4 = External parameter lock active; bit 5 = Engine running; bit 6 = Normal breaker tripped (FW 607540-033); bit 7 = Emergency breaker tripped (FW 607540-033)
HR40doc 40041CPState - control panel stateTransfer sequence state; N/E = switch position.UINT16Read0 = N: load on normal, normal OK; 1 = N: timer 1C (TDES) running; 2 = N: waiting for emergency acceptable; 3 = N: transfer to E inhibited by F6Z; 4 = N: transfer to E inhibited by F34B; 5 = N: timer 2B (TDNE) running; 6 = N: timer 31F (pre-transfer N>E) running; 7 = N: in-phase monitor delay (OTTS N>E); 8 = N: waiting for in-phase (OTTS N>E); 9 = N: in-phase delay with load shed (OTTS N>E); 10 = N: waiting for in-phase with load shed (OTTS N>E); 11 = N: in-sync delay (CTTS N>E); 12 = N: waiting for in-sync (CTTS N>E); 13 = N: sources paralleled (CTTS N>E); 14 = N: load disconnected CT bypass (CTTS N>E); 15 = N: load disconnected (DTTS N>E); 16 = E: N>E load shed active; 17 = E: timer 31M (post-transfer N>E) running; 18 = E: load on emergency, waiting for transfer requests to clear; 19 = E: timer 3A (TDEN) running; 20 = E: transfer to N inhibited by G6C; 21 = E: transfer to N inhibited by F34A; 22 = E: timer 31G (pre-transfer E>N) running; 23 = E: in-phase delay (OTTS E>N); 24 = E: waiting for in-phase (OTTS E>N); 25 = E: in-phase delay with load shed (OTTS E>N); 26 = E: waiting for in-phase with load shed (OTTS E>N); 27 = E: in-sync delay (CTTS E>N); 28 = E: waiting for in-sync (CTTS E>N); 29 = E: sources paralleled (CTTS E>N); 30 = E: load disconnected CT bypass (CTTS E>N); 31 = E: load disconnected (DTTS); 32 = N: E>N load shed active; 33 = N: timer 31N (post-transfer E>N) running; 34 = N: timer 2E (TDEC) running; 35 = N: timer 1C while timer 2E running; 36 = Power-up inhibit; 255 = Transition state (keep last state)
HR41doc 40042CPStateData - state dataSeconds or minutes left, or phase difference x 10, depending on state.UINT16Read
HR42doc 40043Features active (1)BITMAP16Readbit 0 = Feature 6B; bit 1 = Feature 6C; bit 2 = Feature 17; bit 4 = Feature 29; bit 5 = Feature 30; bit 6 = Feature 34A; bit 7 = Feature 34B
HR43doc 40044Features active (2)BITMAP16Readbit 0 = Feature 89; bit 1 = CT bypass; bit 2 = Alarm reset; bit 3 = Feature 6D; bit 4 = Feature 5; bit 5 = Feature 6Z; bit 6 = Feature 34T
HR44doc 40045LogNum - event number to readWrite 0-99 to select an event log entry.UINT16Read/write
HR45doc 40046LogYear - event yearUINT16Read
HR46doc 40047LogMonth - event monthUINT16Read
HR47doc 40048LogDayM - event day of monthUINT16Read
HR48doc 40049LogDayW - event day of weekUINT16Read
HR49doc 40050LogHour - event hourUINT16Read
HR50doc 40051LogMin - event minuteUINT16Read
HR51doc 40052LogSec - event secondUINT16Read
HR52doc 40053LogType - event typeUINT16Read1 = Engine start; 2 = Transfer N>E; 3 = Transfer E>N; 4 = Engine stop; 5 = Emergency acceptable; 6 = Emergency not acceptable; 7 = Normal acceptable; 8 = Normal not acceptable; 9 = Transfer abort; 10 = Breaker trip; 11 = YY primary fail
HR53doc 40054LogCause - event causeUINT16Read1 = Load shed; 2 = Normal fail; 3 = Manual transfer; 4 = Test 5; 5 = Test 17; 6 = Communication; 7 = Engine exerciser; 8 = Emergency fail; 9 = Normal under voltage; 10 = Normal over voltage; 11 = Normal under frequency; 12 = Normal over frequency; 13 = Normal phase rotation; 14 = Normal voltage unbalance; 15 = Emergency under voltage; 16 = Emergency over voltage; 17 = Emergency under frequency; 18 = Emergency over frequency; 19 = Emergency phase rotation; 20 = Emergency voltage unbalance; 21 = Feature 6; 22 = Normal breaker; 23 = Emergency breaker
HR54doc 40055LogEntNr - number of event log entriesBits 0-6, 0-99.UINT16Read
HR100doc 40101Soft load controller statusBits 0-5 mode (0 none, 1 islanding, 2 parallel base load, 3 import/export); bit 6/7 N/E breaker open.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)

What Modbus registers does the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) have?

This map lists 35 registers: 35 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map says the address sent is the map address minus 40001, and the supported-address list (11-54, 100) matches the map's defined block 40012-40055 and 40101. The read example sends start address 0x0010 and gets the three normal voltages, which the map lists from 40017. The example prose names registers one lower (40016), but its hex addresses follow the map rule.

What are the minimum Modbus registers to integrate the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)?

Start with HR 14 Switch position and source availability (Switch position and source availability); HR 16 NV_AB - normal voltage A-B (Normal voltage A-B); HR 20 EV_AB - emergency voltage A-B (Emergency voltage A-B); HR 12 NFRQ_0 - normal frequency (Normal frequency); HR 39 Alarm and lockout status (Alarm / lockout / engine running); HR 40 CPState - control panel state (Transfer sequence state).

How do I enable Modbus control of the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)?

Address and baud rate are set on the Group 5 controller; this document does not describe how (it refers to the Group 5 Controller User's Guide 381333-126).

Where is the official ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus documentation?

The source is Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus (381339-221 I). ASCO doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Asco%207000%20Group%205.pdf. It may be an older revision, so check it against the live unit.

More ASCO Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.