- Home
- Modbus register maps
- ASCO
- 7000 Series Group 5 transfer switch controller (Modbus RTU)
Transfer switch controller · Modbus register map
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The Group 5 controller runs ASCO 7000 Series automatic transfer switches. Through its Modbus RTU interface it reports normal and emergency source voltages and frequencies, switch position, source availability, phase rotation, alarms, the transfer-sequence state with its timer value, active features and the event log.
This page lists 35 Modbus registers for the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ASCO’s own free documentation (linked below) and checked against it.
- Manufacturer
- ASCO
- Model
- 7000 Series Group 5 transfer switch controller (Modbus RTU)
- Equipment type
- Transfer switch controller
- Registers
- 35 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 607540-023 (bits marked 607540-033 need that version)
- Also known as
- ASCO 7000 Group 5, Group 5 Controller, 381339-221
Integration notes: ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)
Read 40015 (switch position and source availability), 40017-40024 (normal and emergency voltages), 40013/40014 (frequencies), 40040 (alarms) and 40041/40042 (transfer state and timer) with FC03, max 12 registers per read.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 14 | Switch position and source availability | BITMAP16 | Switch position and source availability | Read |
| HR 16 | NV_AB - normal voltage A-B | UINT16 | Normal voltage A-B | Read |
| HR 20 | EV_AB - emergency voltage A-B | UINT16 | Emergency voltage A-B | Read |
| HR 12 | NFRQ_0 - normal frequency | UINT16 | Normal frequency | Read |
| HR 39 | Alarm and lockout status | BITMAP16 | Alarm / lockout / engine running | Read |
| HR 40 | CPState - control panel state | UINT16 | Transfer sequence state | Read |
Enable Modbus control & writes
Address and baud rate are set on the Group 5 controller; this document does not describe how (it refers to the Group 5 Controller User's Guide 381333-126).
Byte order & addressing
- Maximum 12 registers per read; larger reads return an exception.
- RTU only, 8 data bits, no parity, 1 stop bit; replies within 50 ms.
Network setup
- Maximum 64 bytes per packet.
Watch out for
- Wire addresses 0-10 and 55-99 (40001-40011, 40056-40100) are undefined; avoid reads that span them.
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 11doc 40012 | PHASE_0 - phase shift normal vs emergency | INT16 | × 0.1 | ° | Read | |||
| HR | 12doc 40013 | NFRQ_0 - normal frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 13doc 40014 | EFRQ_0 - emergency frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 14doc 40015 | Switch position and source availability | BITMAP16 | Read | bit 0 = Main on normal; bit 1 = Main on emergency; bit 2 = Auxiliary on normal; bit 3 = Auxiliary on emergency; bit 4 = Normal source available; bit 5 = Emergency source available | ||||
| HR | 15doc 40016 | Phase rotation and exerciser status | BITMAP16 | Read | bit 0 = Normal rotation ABC; bit 1 = Normal rotation CBA; bit 2 = Emergency rotation ABC; bit 3 = Emergency rotation CBA; bit 4 = Engine exerciser with load active; bit 6 = External F17 active | ||||
| HR | 16doc 40017 | NV_AB - normal voltage A-B | UINT16 | V | Read | ||||
| HR | 17doc 40018 | NV_BC - normal voltage B-C | UINT16 | V | Read | ||||
| HR | 18doc 40019 | NV_CA - normal voltage C-A | UINT16 | V | Read | ||||
| HR | 19doc 40020 | NVUnbl - normal voltage unbalance | UINT16 | % | Read | ||||
| HR | 20doc 40021 | EV_AB - emergency voltage A-B | UINT16 | V | Read | ||||
| HR | 21doc 40022 | EV_BC - emergency voltage B-C | UINT16 | V | Read | ||||
| HR | 22doc 40023 | EV_CA - emergency voltage C-A | UINT16 | V | Read | ||||
| HR | 23doc 40024 | EVUnbl - emergency voltage unbalance | UINT16 | % | Read | ||||
| HR | 24doc 40025 | I_NOM_V - nominal voltage code | UINT16 | Read | 0 = 115 V; 1 = 120 V; 2 = 208 V; 3 = 220 V; 4 = 230 V; 5 = 240 V; 6 = 277 V; 7 = 380 V; 8 = 400 V; 9 = 415 V; 10 = 440 V; 11 = 460 V; 12 = 480 V; 13 = 550 V; 14 = 575 V; 15 = 600 V | ||||
| HR | 25doc 40026 | Switch configuration | Bits 3-4 = switch type: 0 OTTS, 1 DTTS, 2 CTTS, 3 OTTS. | BITMAP16 | Read | bit 0 = Nominal 60 Hz (else 50 Hz); bit 1 = Normal 3-phase sensing; bit 2 = Emergency 3-phase sensing; bit 3 = Switch type bit 0; bit 4 = Switch type bit 1; bit 5 = Bypass switch; bit 6 = Dual breaker (else transfer switch), FW 607540-033 | |||
| HR | 26doc 40027 | TSAmp - transfer switch amp rating code | UINT16 | Read | 0 = 30 A; 1 = 70 A; 2 = 100 A; 3 = 150 A; 4 = 260 A; 5 = 400 A; 6 = 600 A; 7 = 800 A; 8 = 1000 A; 9 = 1200 A; 10 = 1600 A; 11 = 2000 A; 12 = 3000 A; 13 = 4000 A; 14 = Other; 15 = Other | ||||
| HR | 27doc 40028 | LCD_CP_VER - control panel software version | 10-character string. | STRING[12] | Read | ||||
| HR | 33doc 40034 | LCD_CP_DATE - control panel software date | 10-character string. | STRING[12] | Read | ||||
| HR | 39doc 40040 | Alarm and lockout status | BITMAP16 | Read | bit 0 = Transfer switch locked out; bit 1 = CTTS extended parallel alarm; bit 2 = CTTS failure to synch alarm; bit 3 = DTTS load disconnect; bit 4 = External parameter lock active; bit 5 = Engine running; bit 6 = Normal breaker tripped (FW 607540-033); bit 7 = Emergency breaker tripped (FW 607540-033) | ||||
| HR | 40doc 40041 | CPState - control panel state | Transfer sequence state; N/E = switch position. | UINT16 | Read | 0 = N: load on normal, normal OK; 1 = N: timer 1C (TDES) running; 2 = N: waiting for emergency acceptable; 3 = N: transfer to E inhibited by F6Z; 4 = N: transfer to E inhibited by F34B; 5 = N: timer 2B (TDNE) running; 6 = N: timer 31F (pre-transfer N>E) running; 7 = N: in-phase monitor delay (OTTS N>E); 8 = N: waiting for in-phase (OTTS N>E); 9 = N: in-phase delay with load shed (OTTS N>E); 10 = N: waiting for in-phase with load shed (OTTS N>E); 11 = N: in-sync delay (CTTS N>E); 12 = N: waiting for in-sync (CTTS N>E); 13 = N: sources paralleled (CTTS N>E); 14 = N: load disconnected CT bypass (CTTS N>E); 15 = N: load disconnected (DTTS N>E); 16 = E: N>E load shed active; 17 = E: timer 31M (post-transfer N>E) running; 18 = E: load on emergency, waiting for transfer requests to clear; 19 = E: timer 3A (TDEN) running; 20 = E: transfer to N inhibited by G6C; 21 = E: transfer to N inhibited by F34A; 22 = E: timer 31G (pre-transfer E>N) running; 23 = E: in-phase delay (OTTS E>N); 24 = E: waiting for in-phase (OTTS E>N); 25 = E: in-phase delay with load shed (OTTS E>N); 26 = E: waiting for in-phase with load shed (OTTS E>N); 27 = E: in-sync delay (CTTS E>N); 28 = E: waiting for in-sync (CTTS E>N); 29 = E: sources paralleled (CTTS E>N); 30 = E: load disconnected CT bypass (CTTS E>N); 31 = E: load disconnected (DTTS); 32 = N: E>N load shed active; 33 = N: timer 31N (post-transfer E>N) running; 34 = N: timer 2E (TDEC) running; 35 = N: timer 1C while timer 2E running; 36 = Power-up inhibit; 255 = Transition state (keep last state) | |||
| HR | 41doc 40042 | CPStateData - state data | Seconds or minutes left, or phase difference x 10, depending on state. | UINT16 | Read | ||||
| HR | 42doc 40043 | Features active (1) | BITMAP16 | Read | bit 0 = Feature 6B; bit 1 = Feature 6C; bit 2 = Feature 17; bit 4 = Feature 29; bit 5 = Feature 30; bit 6 = Feature 34A; bit 7 = Feature 34B | ||||
| HR | 43doc 40044 | Features active (2) | BITMAP16 | Read | bit 0 = Feature 89; bit 1 = CT bypass; bit 2 = Alarm reset; bit 3 = Feature 6D; bit 4 = Feature 5; bit 5 = Feature 6Z; bit 6 = Feature 34T | ||||
| HR | 44doc 40045 | LogNum - event number to read | Write 0-99 to select an event log entry. | UINT16 | Read/write | ||||
| HR | 45doc 40046 | LogYear - event year | UINT16 | Read | |||||
| HR | 46doc 40047 | LogMonth - event month | UINT16 | Read | |||||
| HR | 47doc 40048 | LogDayM - event day of month | UINT16 | Read | |||||
| HR | 48doc 40049 | LogDayW - event day of week | UINT16 | Read | |||||
| HR | 49doc 40050 | LogHour - event hour | UINT16 | Read | |||||
| HR | 50doc 40051 | LogMin - event minute | UINT16 | Read | |||||
| HR | 51doc 40052 | LogSec - event second | UINT16 | Read | |||||
| HR | 52doc 40053 | LogType - event type | UINT16 | Read | 1 = Engine start; 2 = Transfer N>E; 3 = Transfer E>N; 4 = Engine stop; 5 = Emergency acceptable; 6 = Emergency not acceptable; 7 = Normal acceptable; 8 = Normal not acceptable; 9 = Transfer abort; 10 = Breaker trip; 11 = YY primary fail | ||||
| HR | 53doc 40054 | LogCause - event cause | UINT16 | Read | 1 = Load shed; 2 = Normal fail; 3 = Manual transfer; 4 = Test 5; 5 = Test 17; 6 = Communication; 7 = Engine exerciser; 8 = Emergency fail; 9 = Normal under voltage; 10 = Normal over voltage; 11 = Normal under frequency; 12 = Normal over frequency; 13 = Normal phase rotation; 14 = Normal voltage unbalance; 15 = Emergency under voltage; 16 = Emergency over voltage; 17 = Emergency under frequency; 18 = Emergency over frequency; 19 = Emergency phase rotation; 20 = Emergency voltage unbalance; 21 = Feature 6; 22 = Normal breaker; 23 = Emergency breaker | ||||
| HR | 54doc 40055 | LogEntNr - number of event log entries | Bits 0-6, 0-99. | UINT16 | Read | ||||
| HR | 100doc 40101 | Soft load controller status | Bits 0-5 mode (0 none, 1 islanding, 2 parallel base load, 3 import/export); bit 6/7 N/E breaker open. | UINT16 | Read |
Notes on this map
- Host: copy hosted by Contemporary Controls. Schneider Electric lists a newer revision (381339-221Q, document ASC-TS-UM-7000-PWRMNMDBS) on se.com, but the download is behind a bot check and was not opened; differences from revision I are unknown.
- Readable addresses (decimal, wire): 11-54, 100, 105-173; at most 12 registers per FC03 read. Writable with FC06: 44 and 101-173 (time delays and settings, not listed here because their table is not in this revision's map).
- All values are 16-bit. Voltages are whole volts, frequencies Hz x 100, phase shift degrees x 10 (signed).
- The Power Manager Xp section of the same document (meter registers, LO/HO kWh words) is a separate device and is not part of this map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)
What Modbus registers does the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) have?
This map lists 35 registers: 35 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map says the address sent is the map address minus 40001, and the supported-address list (11-54, 100) matches the map's defined block 40012-40055 and 40101. The read example sends start address 0x0010 and gets the three normal voltages, which the map lists from 40017. The example prose names registers one lower (40016), but its hex addresses follow the map rule.
What are the minimum Modbus registers to integrate the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)?
Start with HR 14 Switch position and source availability (Switch position and source availability); HR 16 NV_AB - normal voltage A-B (Normal voltage A-B); HR 20 EV_AB - emergency voltage A-B (Emergency voltage A-B); HR 12 NFRQ_0 - normal frequency (Normal frequency); HR 39 Alarm and lockout status (Alarm / lockout / engine running); HR 40 CPState - control panel state (Transfer sequence state).
How do I enable Modbus control of the ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)?
Address and baud rate are set on the Group 5 controller; this document does not describe how (it refers to the Group 5 Controller User's Guide 381333-126).
Where is the official ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU) Modbus documentation?
The source is Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus (381339-221 I). ASCO doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Asco%207000%20Group%205.pdf. It may be an older revision, so check it against the live unit.
More ASCO Modbus register maps
Other generator controllers register maps
- Generator controller
Datakom D-300 / D-500 / D-700 genset controllers
Datakom D-300, D-500 and D-700 controllers, Modbus application manual V5.6 (firmware 5.6 era).
Also known as: D-300, D-500, D-700, D300, D500, D700 - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
SmartGen HGM6100N / HGM6100CAN Series
HGM6100N and HGM6100CAN genset controllers (HGM6110 auto-start and HGM6120 AMF variants), protocol document v1.7.
Also known as: HGM6100CAN, HGM6110N, HGM6120N, HGM6110CAN, HGM6120CAN - Generator controller (utility-tie master synchronizer)
Woodward MSLC-2 Master Synchronizer and Load Control
MSLC-2, data protocol 5200, per manual 37444G.
Also known as: MSLC2, MSLC-2 master synchronizer
All generator controllers Modbus register maps →
Source: Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.