Generator controller (utility-tie master synchronizer) · Modbus register map

Woodward MSLC-2 Master Synchronizer and Load Control Modbus register map

Updated 17 November 2026

Short answer

The MSLC-2 sits at the utility tie or bus breaker of a DSLC-2 generator plant: it synchronises the plant bus to the utility and runs import/export, base-load and process control for the DSLC-2 units. It is a Modbus RTU slave on RS-485 and a Modbus/TCP slave on Ethernet. Measurements and states come from data protocol 5200 at Modicon 450001; interface setpoints and remote discrete-input commands are parameters. This map covers system A/B frequencies and phase angle, 32-bit system A power, voltage and current, energy, control modes, flags, alarms, relays and inputs.

This page lists 69 Modbus registers for the Woodward MSLC-2 Master Synchronizer and Load Control — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.

Manufacturer
Woodward
Model
MSLC-2 Master Synchronizer and Load Control
Equipment type
Generator controller (utility-tie master synchronizer)
Registers
69 (6 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
MSLC2, MSLC-2 master synchronizer
Source document
MSLC-2 Master Synchronizer and Load Control - Manual · 37444G · rev. 2022-02-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Woodward MSLC-2 Master Synchronizer and Load Control

Integration in brief

Block-read up to 128 holding registers from wire address 50000 for frequencies, phase angle, modes, flags and alarms, and from 50100 for 32-bit system A power, voltages and currents. Release functions to the interface in 7645, switch them in 7644, and write setpoints to 7640-7642 and 7780.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 50010System A frequencyINT16System A (utility) frequencyRead
HR 50023System B frequencyINT16System B (bus) frequencyRead
HR 50032Phase Angle System A / System BINT16Phase angle A / BRead
HR 50056Sync Control StateINT16Synchronizer stateRead
HR 50057Load Control ModeINT16Load control modeRead
HR 50075Alarms 1BITMAP16Alarms 1Read
HR 50100Total System A powerINT32 ABCDTotal system A power (32-bit)Read
HR 50156P SumINT32 ABCDP sumRead

Enable Modbus control & writes

RS-485 (serial interface 2): Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network A/B Modbus/TCP slave IDs are 5351/5451 (default 255).

Communication loss & watchdog

No timeout parameter is given. After an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' hands all functions back to hardware control and clears the control bits.

Byte order & addressing

Network setup

Watch out for

Woodward MSLC-2 Master Synchronizer and Load Control Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

69 of 69 shown
Woodward MSLC-2 Master Synchronizer and Load Control Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR7640doc 7640 (47641)Interface power factor setpoint-500 (capacitive) to 1000 to 500 (inductive); used when 7635 = Interface.INT16× 0.001Read/write
HR7641doc 7641 (47642)Interface frequency setpoint0-7000; used when parameter 7783 = Interface.UINT16× 0.01HzRead/write
HR7642doc 7642 (47643)Interface active power setpoint (import/export)Positive only; used when 7634 = Interface. Manual example: 1000 kW = 1000.INT32ABCDkWRead/write
HR7644doc 7644 (47645)Discrete inputs over interfaceBit field (bits 01-16, see notes) switching functions released by 7645.UINT16Read/write
HR7645doc 7645 (47646)Release discrete inputs to interfaceSame bit list as 7644; 1 = interface controlled, 0 = hardware input.UINT16Read/write
HR7780doc 7780 (47781)Interface voltage setpoint50-650000 V; used when 7784 = Interface.UINT32ABCDVRead/write
HR50000Protocol IDReads 5200.INT16Read
HR50010System A frequencyINT16× 0.01HzRead
HR50013System A power factorINT16× 0.001Read
HR50023System B frequencyINT16× 0.01HzRead
HR50025Auxiliary System B frequencyINT16× 0.01HzRead
HR50032Phase Angle System A / System BINT16× 0.1°Read
HR50033Active Setpoint frequency to DSLCINT16× 0.01HzRead
HR50034Active Setpoint voltage to DSLCINT16× 0.01%Read
HR50035Active Setpoint load level to DSLCINT16× 0.01%Read
HR50036Active Setpoint reactive load level to DSLCINT16× 0.01%Read
HR50044Battery voltageINT16× 0.1VRead
HR50056Sync Control StateINT16Read0 = Off; 1 = Check mode active; 2 = Permissive mode active; 3 = Run mode active; 4 = Close Timer runs; 5 = Sync Timer runs; 6 = Breaker synchronized; 7 = Auto-Off position; 8 = Manual
HR50057Load Control ModeINT16Read0 = Off; 1 = Inactive; 2 = Off line; 3 = Frequency control; 4 = Base load control; 5 = Import/Export control; 6 = Process control; 7 = Remote process control; 8 = Peak load control (reserved); 9 = Zero power control (reserved); 10 = Load share (reserved); 11 = Process slave (reserved)
HR50058Reactive Load Control ModeINT16Read0 = Off; 1 = Inactive; 2 = Off line; 3 = Voltage control; 4 = Reactive load control; 5 = Import/Export reactive load; 6 = Const.Gen Power Factor; 7 = Remote process control (reserved); 8 = (reserved); 9 = Zero power control (reserved); 10 = Reactive load share (reserved); 11 = Process slave (reserved)
HR50059Condition Flags 1BITMAP16Readbit 1 = System A clock wise system is recognized; bit 2 = System A counter clock wise system is recognized; bit 5 = Aux. System B clock wise system is recognized; bit 6 = Aux. System B anti clock wise system is recognized; bit 7 = System A is ok; bit 8 = System B is Dead (in same segment); bit 9 = System A is Dead; bit 10 = System B is ok (in same segment); bit 11 = Utility breaker is closed (in same segment)
HR50060Condition Flags 2BITMAP16Readbit 10 = Breaker dead busbar closure request active
HR50061Condition Flags 3BITMAP16Readbit 2 = Unloading system is active; bit 6 = Closing Breaker is active; bit 7 = Opening Breaker is active; bit 8 = Synchronization Breaker is active; bit 11 = Breaker is closed
HR50067Interface Control SwitchBITMAP16Readbit 0 = Source: Synchronization GCB check switch; bit 1 = Source: Synchronization GCB permissive switch; bit 2 = Source: Synchronization GCB run switch; bit 3 = Source: CB Aux contact switch; bit 4 = Source: Raise voltage switch; bit 5 = Source: Lower voltage switch; bit 6 = Source: Base load switch; bit 7 = Source: Load/ Unload switch; bit 8 = Source: Ramp pause switch; bit 9 = Source: Raise load switch; bit 10 = Source: Lower load switch; bit 11 = Source: Process switch; bit 12 = Source: Droop switch; bit 13 = Source: Modbus reset switch; bit 14 = Source: System update switch
HR50071Relay Outputs 1BITMAP16Readbit 0 = Alarm Relay (R1); bit 2 = High Limit Relay (R3); bit 3 = Low Limit Relay (R4); bit 4 = Breaker Open Relay (R5); bit 5 = Breaker Close Relay (R6); bit 6 = LCL/Gen breaker open (R7); bit 7 = Alarm 1 (R8); bit 8 = Alarm 2 (R9); bit 9 = Alarm 3 (R10); bit 10 = Load switch 1 (R11); bit 11 = Load switch 2 (R12)
HR50075Alarms 1BITMAP16Readbit 0 = Synchronizer Timeout; bit 1 = Breaker Close Failure; bit 2 = High Load Limit; bit 3 = Low Load Limit; bit 4 = High Process Limit; bit 5 = Low Process Limit; bit 6 = Low Voltage Limit; bit 7 = High Voltage Limit; bit 8 = Voltage Range Limit; bit 9 = Communication Error NW A; bit 11 = Missing member; bit 12 = Centralized Alarms; bit 13 = GCB Open Failure; bit 14 = Deadbus closure mismatch
HR50081Discrete Inputs 1BITMAP16Readbit 0 = Synchronization Check switch is active (DI1); bit 1 = Synchronization Permissive switch is active (DI2); bit 2 = Synchronization Run switch is active (DI3); bit 3 = Circuit Breaker Aux. is closed (DI4); bit 4 = Voltage Raise Switch (DI5); bit 5 = Voltage Lower Switch (DI6); bit 6 = Base Load Control Switch (DI7); bit 7 = Load/Unload Switch (DI8) (Energized=Load); bit 8 = Ramp Pause Switch (DI9); bit 9 = Load Raise Switch (DI10); bit 10 = Load Lower Switch (DI11); bit 11 = Process Control Switch (DI12)
HR50082Digital Inputs 2BITMAP16Readbit 0 = Segment connection 12 is closed (DI13); bit 1 = Segment connection 23 is closed (DI14); bit 2 = Segment connection 34 is closed (DI15); bit 3 = Segment connection 45 is closed (DI16); bit 4 = Segment connection 56 is closed (DI17); bit 5 = Segment connection 67 is closed (DI18); bit 6 = Segment connection 78 is closed (DI19); bit 7 = Segment connection 81 is closed (DI20); bit 8 = Import/Export Control Switch (DI13); bit 9 = Modbus reset (DI22); bit 10 = System update (DI23)
HR50083Alarms 5BITMAP16Readbit 0 = Busbar mismatch; bit 1 = Phase rotation mismatch; bit 2 = Communication Error NW B; bit 3 = Network A Error; bit 4 = Network B Error; bit 5 = Devices not matched
HR50100Total System A powerINT32ABCDWRead
HR50102Total System A reactive powerINT32ABCDvarRead
HR50104Total System A apparent powerINT32ABCDVARead
HR50106Average System A Wye-VoltageINT32ABCD× 0.1VRead
HR50108Average System A Delta-VoltageINT32ABCD× 0.1VRead
HR50110Average System B Delta-VoltageINT32ABCD× 0.1VRead
HR50112Average System A CurrentINT32ABCD× 0.001ARead
HR50114System A current 1INT32ABCD× 0.001ARead
HR50116System A current 2INT32ABCD× 0.001ARead
HR50118System A current 3INT32ABCD× 0.001ARead
HR50120System A voltage L1-L2INT32ABCD× 0.1VRead
HR50122System A voltage L2-L3INT32ABCD× 0.1VRead
HR50124System A voltage L3-L1INT32ABCD× 0.1VRead
HR50126System A voltage L1-NINT32ABCD× 0.1VRead
HR50128System A voltage L2-NINT32ABCD× 0.1VRead
HR50130System A voltage L3-NINT32ABCD× 0.1VRead
HR50132System A active power 1-NINT32ABCDWRead
HR50134System A active power 2-NINT32ABCDWRead
HR50136System A active power 3-NINT32ABCDWRead
HR50138System B voltage (L1-N) L1-L2INT32ABCD× 0.1VRead
HR50140Average Aux.System B Wye-VoltageINT32ABCD× 0.1VRead
HR50142Average Aux.System B Delta-VoltageINT32ABCD× 0.1VRead
HR50144Aux.System B voltage L1-L2INT32ABCD× 0.1VRead
HR50146Aux.System B voltage L2-L3INT32ABCD× 0.1VRead
HR50148Aux.System B voltage L3-L1INT32ABCD× 0.1VRead
HR50150Aux.System B voltage L1-NINT32ABCD× 0.1VRead
HR50152Aux.System B voltage L2-NINT32ABCD× 0.1VRead
HR50154Aux.System B voltage L3-NINT32ABCD× 0.1VRead
HR50156P SumINT32ABCD× 0.001kWRead
HR50158Q SumINT32ABCD× 0.001kvarRead
HR50160Import/Export referenceINT32ABCD× 0.1kWRead
HR50162Reactive load referenceINT32ABCD× 0.1kvarRead
HR50164Process reference inputINT32ABCD× 0.1Read
HR50166Process signal inputINT32ABCD× 0.1Read
HR50168Process reference toolkitINT32ABCD× 0.1Read
HR50170Remote load reference inputINT32ABCD× 0.1kWRead
HR50174Syst.A.pos.act.energyINT32ABCD× 0.01MWhRead
HR50176Syst.A.neg.act.energyINT32ABCD× 0.01MWhRead
HR50178Syst.A.pos.react.energyINT32ABCD× 0.01MvarhRead
HR50180Syst.A.neg.react.energyINT32ABCD× 0.01MvarhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Woodward MSLC-2 Master Synchronizer and Load Control

What Modbus registers does the Woodward MSLC-2 Master Synchronizer and Load Control have?

This map lists 69 registers: 69 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Woodward MSLC-2 Master Synchronizer and Load Control Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 5200 table prints both the bus address (50000) and the Modicon address (450001); this map records and sends the bus address. Parameters use Modicon 40000 + (parameter ID + 1), so parameter 7642 is Modicon 47643 = wire address 7642. The manual's ModScan32 screenshot for parameter 7642 uses address 7643 (1-based), which confirms this; its worked example prints '407642', a typo that does not follow the rule.

What byte order does the Woodward MSLC-2 Master Synchronizer and Load Control use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Woodward MSLC-2 Master Synchronizer and Load Control?

Start with HR 50010 System A frequency (System A (utility) frequency); HR 50023 System B frequency (System B (bus) frequency); HR 50032 Phase Angle System A / System B (Phase angle A / B); HR 50056 Sync Control State (Synchronizer state); HR 50057 Load Control Mode (Load control mode); HR 50075 Alarms 1 (Alarms 1); HR 50100 Total System A power (Total system A power (32-bit)); HR 50156 P Sum (P sum).

How do I enable Modbus control of the Woodward MSLC-2 Master Synchronizer and Load Control?

RS-485 (serial interface 2): Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network A/B Modbus/TCP slave IDs are 5351/5451 (default 255).

What happens when the Woodward MSLC-2 Master Synchronizer and Load Control loses Modbus communication?

No timeout parameter is given. After an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' hands all functions back to hardware control and clears the control bits.

Where is the official Woodward MSLC-2 Master Synchronizer and Load Control Modbus documentation?