Generator controller · Modbus register map
DEIF AGC-4 Mk II Automatic Genset Controller Modbus register map
Updated 19 November 2026
The AGC-4 Mk II is DEIF's second-generation paralleling and power-management genset controller. It serves Modbus TCP on its built-in Ethernet and Modbus RTU through option H2 (RS-485) or H9 (RS-232). This map lists the genset-variant AC measurements, energy and hour counters, DC readings, mode and status flags, and the control command words for remote start, stop, breaker and mode commands.
This page lists 184 Modbus registers for the DEIF AGC-4 Mk II Automatic Genset Controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- AGC-4 Mk II Automatic Genset Controller
- Equipment type
- Generator controller
- Registers
- 184 (19 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 6.31.0
- Also known as
- AGC-4 Mk2, AGC-4 MkII
- Source document
- AGC-4 Mk II Modbus tables · 4189341272 rev. N
Integration notes: DEIF AGC-4 Mk II Automatic Genset Controller
Read generator values from input registers 501 upward with function 04 and the active mode from 1019. Write a command word to holding register 5 or 6 with bit 0 set plus the wanted command bit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 501 | Generator voltage L1-L2 | INT16 | Generator voltage L1-L2 | Read |
| IR 507 | Generator frequency L1 | INT16 | Generator frequency | Read |
| IR 513 | Generator current L1 | INT16 | Generator current L1 | Read |
| IR 519 | Generator power | INT16 | Generator active power | Read |
| IR 554 | Absolute running hours | INT32 ABCD | Running hours | Read |
| IR 1019 | Mode flags word 1019 | BITMAP16 | Active mode | Read |
| HR 5 | Control command word 5 | BITMAP16 | Remote start/stop and breaker commands | Write |
Enable Modbus control & writes
Modbus TCP uses the controller's Ethernet port. For RTU fit option H2 (RS-485) or H9 (RS-232); communication parameters are 7500-7520.
Byte order & addressing
- A command word is ignored unless bit 0 is 1 in the same write.
- Function 04 addresses 0-499 are a user-configurable copy area.
Network setup
- Option H2 RS-485: 9600 or 19200 bit/s, 8 data bits, no parity, 1 stop bit.
Watch out for
- AC voltages, currents and powers are whole units (scale 1); frequency and power factor use 0.01, and DC supply voltage uses 0.1.
DEIF AGC-4 Mk II Automatic Genset Controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0 | GB position ON | BIT | Read | |||||
| DI | 1 | MB Position ON (Single DG) | BIT | Read | |||||
| DI | 3 | Running | BIT | Read | |||||
| DI | 4 | Generator voltage/frequency OK | BIT | Read | |||||
| DI | 5 | Mains failure (Single DG) | BIT | Read | |||||
| DI | 6 | BLOCK mode | BIT | Read | |||||
| DI | 7 | No Regulation mode | BIT | Read | |||||
| DI | 8 | MANUAL mode | BIT | Read | |||||
| DI | 9 | AUTO mode | BIT | Read | |||||
| DI | 10 | TEST mode | BIT | Read | |||||
| DI | 11 | GB position OFF | BIT | Read | |||||
| DI | 12 | MB position OFF | BIT | Read | |||||
| DI | 13 | Island | BIT | Read | |||||
| DI | 14 | Automatic mains failure (AMF) | BIT | Read | |||||
| DI | 15 | Peak shaving | BIT | Read | |||||
| DI | 16 | Fixed power | BIT | Read | |||||
| DI | 17 | Mains power export (MPE) | BIT | Read | |||||
| DI | 18 | Load takeover (LTO) | BIT | Read | |||||
| DI | 19 | Power management | BIT | Read | |||||
| DI | 20 | Any alarm on PMS ID1 | BIT | Read | |||||
| DI | 21 | Any alarm on PMS ID2 | BIT | Read | |||||
| DI | 22 | Any alarm on PMS ID3 | BIT | Read | |||||
| DI | 23 | Any alarm on PMS ID4 | BIT | Read | |||||
| DI | 24 | Any alarm on PMS ID5 | BIT | Read | |||||
| DI | 25 | Any alarm on PMS ID6 | BIT | Read | |||||
| DI | 26 | Any alarm on PMS ID7 | BIT | Read | |||||
| DI | 27 | Any alarm on PMS ID8 | BIT | Read | |||||
| DI | 28 | Any alarm mains (Mains Command Unit) | BIT | Read | |||||
| DI | 29 | Battery test | BIT | Read | |||||
| DI | 31 | Ready AUTO-start GEN1 | BIT | Read | |||||
| DI | 32 | Ready AUTO-start GEN2 | BIT | Read | |||||
| DI | 33 | Ready AUTO-start GEN3 | BIT | Read | |||||
| DI | 34 | Ready AUTO-start GEN4 | BIT | Read | |||||
| DI | 35 | Ready AUTO-start GEN5 | BIT | Read | |||||
| DI | 36 | Ready AUTO-start GEN6 | BIT | Read | |||||
| DI | 37 | Ready AUTO-start GEN7 | BIT | Read | |||||
| DI | 38 | Ready AUTO-start GEN8 | BIT | Read | |||||
| DI | 39 | Ramp up | BIT | Read | |||||
| DI | 40 | Ramp down or deload | BIT | Read | |||||
| DI | 53 | Mains sync. inhibit | BIT | Read | |||||
| DI | 54 | Any mains sync. inhibit | BIT | Read | |||||
| DI | 771 | 3rd party loadshare status | BIT | Read | |||||
| DI | 772 | 3rd party digital loadshare protocol | BIT | Read | |||||
| DI | 773 | 3rd party loadshare active power setpoint | BIT | Read | |||||
| DI | 774 | 3rd party loadshare reactive power setpoint | BIT | Read | |||||
| DI | 775 | 3rd party loadshare number of units | BIT | Read | |||||
| DI | 776 | 3rd party loadshare number of active units | BIT | Read | |||||
| IR | 500 | Application version | INT16 | Read | |||||
| IR | 501 | Generator voltage L1-L2 | INT16 | V | Read | ||||
| IR | 502 | Generator voltage L2-L3 | INT16 | V | Read | ||||
| IR | 503 | Generator voltage L3-L1 | INT16 | V | Read | ||||
| IR | 504 | Generator voltage L1-N | INT16 | V | Read | ||||
| IR | 505 | Generator voltage L2-N | INT16 | V | Read | ||||
| IR | 506 | Generator voltage L3-N | INT16 | V | Read | ||||
| IR | 507 | Generator frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 508 | Generator frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 509 | Generator frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 510 | Generator voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 511 | Generator voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 512 | Generator voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 513 | Generator current L1 | INT16 | A | Read | ||||
| IR | 514 | Generator current L2 | INT16 | A | Read | ||||
| IR | 515 | Generator current L3 | INT16 | A | Read | ||||
| IR | 516 | Generator power L1 | INT16 | kW | Read | ||||
| IR | 517 | Generator power L2 | INT16 | kW | Read | ||||
| IR | 518 | Generator power L3 | INT16 | kW | Read | ||||
| IR | 519 | Generator power | INT16 | kW | Read | ||||
| IR | 520 | Generator reactive power L1 | INT16 | kvar | Read | ||||
| IR | 521 | Generator reactive power L2 | INT16 | kvar | Read | ||||
| IR | 522 | Generator reactive power L3 | INT16 | kvar | Read | ||||
| IR | 523 | Generator reactive power | INT16 | kvar | Read | ||||
| IR | 524 | Generator apparent power L1 | INT16 | kVA | Read | ||||
| IR | 525 | Generator apparent power L2 | INT16 | kVA | Read | ||||
| IR | 526 | Generator apparent power L3 | INT16 | kVA | Read | ||||
| IR | 527 | Generator apparent power | INT16 | kVA | Read | ||||
| IR | 528 | Generator Export reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 530 | Generator Export, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 532 | Generator Export, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 534 | Generator Export, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 536 | Generator Export, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 538 | Generator PF | INT16 | × 0.01 | Read | ||||
| IR | 539 | Bus B voltage L1-L2 | INT16 | V | Read | ||||
| IR | 540 | Bus B voltage L2-L3 | INT16 | V | Read | ||||
| IR | 541 | Bus B voltage L3-L1 | INT16 | V | Read | ||||
| IR | 542 | Bus B voltage L1-N | INT16 | V | Read | ||||
| IR | 543 | Bus B voltage L2-N | INT16 | V | Read | ||||
| IR | 544 | Bus B voltage L3-N | INT16 | V | Read | ||||
| IR | 545 | Bus B frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 546 | Bus B frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 547 | Bus B frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 548 | Bus B voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 549 | Bus B voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 550 | Bus B voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 551 | U BB L1 - U GEN L1 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 552 | U BB L2 - U GEN L2 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 553 | U BB L3 - U GEN L3 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 554 | Absolute running hours | INT32 | ABCD | Read | ||||
| IR | 556 | Relative running hours | INT32 | ABCD | Read | ||||
| IR | 558 | No. of alarms | INT16 | Read | |||||
| IR | 559 | No. of unacknowledged alarms | INT16 | Read | |||||
| IR | 560 | No. of active acknowledged alarms | INT16 | Read | |||||
| IR | 561 | Running minute counter, shutdown override | INT16 | Read | |||||
| IR | 562 | Running hour counter, shutdown override | INT16 | Read | |||||
| IR | 563 | No. of GB operations | INT16 | Read | |||||
| IR | 564 | No. of MB operations | INT16 | Read | |||||
| IR | 566 | Start attempts | INT16 | Read | |||||
| IR | 567 | DC supply term. 1-2 | INT16 | × 0.1 | V | Read | |||
| IR | 568 | DC supply term. 98-99 | INT16 | × 0.1 | V | Read | |||
| IR | 569 | Service timer 1 running hours | INT16 | Read | |||||
| IR | 570 | Service timer 1 running days | INT16 | Read | |||||
| IR | 571 | Service timer 2 running hours | INT16 | Read | |||||
| IR | 572 | Service timer 2 running days | INT16 | Read | |||||
| IR | 573 | Cos-phi | INT16 | × 0.01 | Read | ||||
| IR | 574 | cos phi inductive/capacitive | INT16 | Read | 0 = Inductive; 1 = Capacitive | ||||
| IR | 576 | RPM (revolutions per minute) | INT16 | rpm | Read | ||||
| IR | 577 | Running hours load profile | INT32 | ABCD | Read | ||||
| IR | 590 | Internal Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 684 | Service timer 3 running hours | INT16 | Read | |||||
| IR | 685 | Service timer 3 running days | INT16 | Read | |||||
| IR | 686 | Service timer 4 running hours | INT16 | Read | |||||
| IR | 687 | Service timer 4 running days | INT16 | Read | |||||
| IR | 689 | Power derate value | INT16 | × 0.1 | % | Read | |||
| IR | 700 | Actual nominal power (Includes derate etc.) | INT16 | Read | |||||
| IR | 747 | Generator power (% of nominal) | INT16 | % | Read | ||||
| IR | 748 | Generator reactive power (% of nominal) | INT16 | % | Read | ||||
| IR | 756 | Generator average frequency | INT16 | × 0.01 | Hz | Read | |||
| IR | 757 | Busbar average frequency | INT16 | × 0.01 | Hz | Read | |||
| IR | 760 | Absolute running minutes | INT16 | min | Read | ||||
| IR | 765 | Active Power Load | INT32 | ABCD | kW | Read | |||
| IR | 790 | Generator Export reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 792 | Generator Export reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 794 | Generator Export reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 796 | Generator Import active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 798 | Generator Import active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 800 | Generator Import active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 802 | Generator Import active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 804 | Generator Import reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 806 | Generator Import reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 808 | Generator Import reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 810 | Generator Import reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 816 | Demand of peak current 1 | INT16 | Read | |||||
| IR | 817 | Demand of peak current 2 | INT16 | Read | |||||
| IR | 818 | Demand of peak current 3 | INT16 | Read | |||||
| IR | 819 | Demand of avg. peak current 1 | INT16 | Read | |||||
| IR | 820 | Demand of avg. peak current 2 | INT16 | Read | |||||
| IR | 821 | Demand of avg. peak current 3 | INT16 | Read | |||||
| IR | 822 | Start attempts standard | INT16 | Read | |||||
| IR | 823 | Start attempts double starter | INT16 | Read | |||||
| IR | 833 | P ref actual | INT16 | Read | |||||
| IR | 1018 | Status flags word 1018 | One flag per bit. | BITMAP16 | Read | bit 0 = Mains failure (Single DG); bit 1 = MB position ON (Single DG); bit 2 = DG ramp down; bit 3 = Start GOV/AVR regulation; bit 4 = GB position ON; bit 5 = GB synchronising; bit 6 = Engine running; bit 7 = Running detected, timer expired; bit 8 = DG Hz/V OK, timer expired; bit 9 = Battery test ongoing; bit 10 = Shutdown override active; bit 11 = GB position OFF; bit 12 = MB position OFF; bit 13 = BB Hz/V OK; bit 14 = Single DG, MB synchronising; bit 15 = Dry mode | |||
| IR | 1019 | Mode flags word 1019 | Active running mode and plant mode, one bit each. | BITMAP16 | Read | bit 0 = BLOCK mode; bit 1 = No Regulation mode; bit 2 = MANUAL mode; bit 3 = AUTO mode; bit 4 = TEST; bit 5 = Island; bit 6 = AMF; bit 7 = Peak shaving; bit 8 = Fixed power; bit 9 = Mains power export; bit 10 = Load takeover; bit 11 = Power management; bit 15 = AMF active | |||
| IR | 1278 | Mlogic event counter 1 | INT16 | Read | |||||
| IR | 1279 | Mlogic event counter 2 | INT16 | Read | |||||
| IR | 1280 | Mlogic event counter 3 | INT16 | Read | |||||
| IR | 1281 | Mlogic event counter 4 | INT16 | Read | |||||
| IR | 1282 | Mlogic event counter 5 | INT16 | Read | |||||
| IR | 1283 | Mlogic event counter 6 | INT16 | Read | |||||
| IR | 1284 | Mlogic event counter 7 | INT16 | Read | |||||
| IR | 1285 | Mlogic event counter 8 | INT16 | Read | |||||
| IR | 1900 | General purpose PID 1 prioritized input | INT16 | Read | |||||
| IR | 1901 | General purpose PID 2 prioritized input | INT16 | Read | |||||
| IR | 1902 | General purpose PID 3 prioritized input | INT16 | Read | |||||
| IR | 1903 | General purpose PID 4 prioritized input | INT16 | Read | |||||
| IR | 1904 | General purpose PID 5 prioritized input | INT16 | Read | |||||
| IR | 1905 | General purpose PID 6 prioritized input | INT16 | Read | |||||
| HR | 0 | Power regulator setpoint | 0 to 100 % of nominal power; activated in menu 7501. | INT16 | Read/write | ||||
| HR | 1 | cosPhi regulator setpoint | 60-100 means cos phi x 100 (100 = 1.00). Menu 7504. | INT16 | Read/write | ||||
| HR | 2 | Reactive power regulator setpoint | -100 to +100 % of nominal; negative = capacitive. Menu 7505. | INT16 | Read/write | ||||
| HR | 3 | Frequency regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502. | INT16 | Read/write | ||||
| HR | 4 | Voltage regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503. | INT16 | Read/write | ||||
| HR | 5 | Control command word 5 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start+sync. (MANUAL); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload/stop (MANUAL) | |||
| HR | 6 | Control command word 6 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load take-over (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = No Regulation mode; bit 13 = AUTO mode; bit 14 = MANUAL mode; bit 15 = TEST mode | |||
| HR | 7 | Control command word 7 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m. | |||
| HR | 8 | Control command word 8 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 1; bit 2 = Virtual event 2; bit 3 = Virtual event 3; bit 4 = Virtual event 4; bit 5 = Virtual event 5; bit 6 = Virtual event 6; bit 7 = Virtual event 7; bit 8 = Virtual event 8; bit 9 = Virtual event 9; bit 10 = Virtual event 10; bit 11 = Virtual event 11; bit 12 = Virtual event 12; bit 13 = Virtual event 13; bit 14 = Virtual event 14; bit 15 = Virtual event 15 | |||
| HR | 9 | Control command word 9 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 16; bit 2 = Virtual event 17; bit 3 = Virtual event 18; bit 4 = Virtual event 19; bit 5 = Virtual event 20; bit 6 = Virtual event 21; bit 7 = Virtual event 22; bit 8 = Virtual event 23; bit 9 = Virtual event 24; bit 10 = Virtual event 25; bit 11 = Virtual event 26; bit 12 = Virtual event 27; bit 13 = Virtual event 28; bit 14 = Virtual event 29; bit 15 = Virtual event 30 | |||
| HR | 10 | Control command word 10 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits; bit 6 = Nominal setting 5; bit 7 = Nominal setting 6 | |||
| HR | 13 | Control command word 13 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn | |||
| HR | 58000 | Year (2003-2099) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58001 | Month (1-12) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58002 | Date (1-31) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58003 | Day (1-7, Monday - Sunday) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58004 | Hour (0-23) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58005 | Min (0-59) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58006 | Sec (0-59) | Controller clock; write to set. | INT16 | Read/write |
Notes on this map
- The source is an Excel workbook. Each row has a scaling exponent x; the value is raw x 10^-x, so x=2 means scale 0.01. Units are as printed.
- 32-bit values: the tables mark every 32-bit register with data format ABCD (high word at the lower address); DEIF's AGC 150 Modbus server manual (4189341435, section 3.4) uses the same notation with that meaning.
- Only rows marked for the GEN application are listed; BTB, MAINS, GROUP and PLANT controllers reuse addresses for other values.
- Left out: the configurable area 0-499, analogue/multi-inputs and CIO values (meaning set by configuration), alarm bits, EIC engine data (including the 26000 block), DAVR, power-management, PMS lite and plant-config blocks, and the command-flag coils. All are in the workbook.
- Parameters are reached through address areas plus the parameter's USW address; see Option H2 and H9 Modbus communication AGC-4 Mk II (4189341279).
- Left out: input 767 (reactive power load, printed with unit kW) and 830 (IEEE Q(U) reference, unit printed as 0.01% with no scaling) because the printed units do not settle how to read them.
- Command bit words read back 0; their state can be read on input registers 642-655 (not listed).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF AGC-4 Mk II Automatic Genset Controller
What Modbus registers does the DEIF AGC-4 Mk II Automatic Genset Controller have?
This map lists 184 registers: 47 discrete inputs, 118 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF AGC-4 Mk II Automatic Genset Controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 'Modbus address' column is the address sent in the request. The tables also print a 6-digit PLC address one higher (input 501 = PLC 300502).
What byte order does the DEIF AGC-4 Mk II Automatic Genset Controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the DEIF AGC-4 Mk II Automatic Genset Controller?
Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator frequency L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 554 Absolute running hours (Running hours); IR 1019 Mode flags word 1019 (Active mode); HR 5 Control command word 5 (Remote start/stop and breaker commands).
How do I enable Modbus control of the DEIF AGC-4 Mk II Automatic Genset Controller?
Modbus TCP uses the controller's Ethernet port. For RTU fit option H2 (RS-485) or H9 (RS-232); communication parameters are 7500-7520.
Where is the official DEIF AGC-4 Mk II Automatic Genset Controller Modbus documentation?
The source is AGC-4 Mk II Modbus tables (4189341272 rev. N), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/u2blk5ge/agc-4-mk-ii-modbus-tables-4189341272-uk.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
Other generator controllers register maps
- Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
SmartGen HGM4010N / HGM4020N
HGM4010N (auto start) and HGM4020N (AMF) genset controllers, HGM4000N communication protocol v1.2.
Also known as: HGM4010N, HGM4000N - Generator controller
Woodward easYgen-3000XT Series
easYgen-3100XT-P1 / 3200XT-P1 / 3200XT-P1-LT, release 2.17-0, default Modbus data protocol 5010 (Basic Visualization).
Also known as: easYgen-3100XT-P1, easYgen-3200XT-P1, easYgen-3200XT-P1-LT, easYgen-3100XT, easYgen-3200XT - Generator controller
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Cummins PCC 1301 and PowerCommand 1.1/1.2 generator set controls on their RS-485 Modbus RTU port, per section 1 of A029X159 Issue 7.
Also known as: PCC 1301, PCC1301, PowerCommand 1.1, PowerCommand 1.2, PC1.1, PC1.2 - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller
All generator controllers Modbus register maps →
Source: AGC-4 Mk II Modbus tables · 4189341272 rev. N. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.