DEIF SGC 120 / SGC 121 Single Genset Controller Modbus register map
Updated 19 November 2026
The SGC 120 and SGC 121 are DEIF's small auto-start and AMF genset controllers. They act as a Modbus RTU server on one RS-485 port, and every value is a holding register read with function 03. This map covers the 16-bit generator, mains and load readings, engine values, start and trip counters, the packed alarm-state, I/O and genset-status words, and the mode-change command.
This page lists 66 Modbus registers for the DEIF SGC 120 / SGC 121 Single Genset Controller — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- SGC 120 / SGC 121 Single Genset Controller
- Equipment type
- Generator controller
- Registers
- 66 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- Application software 9.04 (user manual 4189341340B)
- Also known as
- SGC 120, SGC 121, SGC120, SGC121
- Source document
- SGC 120 and SGC 121 Modbus tables · 4189341357
Integration notes: DEIF SGC 120 / SGC 121 Single Genset Controller
Poll holding registers 1-59 with function 03 for live values and 78 for genset status. To start or stop remotely, write 2 (START) or 1 (STOP) to register 0 with function 16; write 4 to go to AUTO.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Generator L1-N voltage | UINT16 | Generator L1-N voltage | Read |
| HR 7 | Generator R frequency | UINT16 | Generator frequency | Read |
| HR 23 | Load L1 current | UINT16 | Load L1 current | Read |
| HR 29 | Load total active power | INT16 | Total kW | Read |
| HR 56 | Battery voltage | UINT16 | Battery voltage | Read |
| HR 78 | DG status word | UINT16 | Genset status flags | Read |
| HR 0 | Protocol revision (read) / DG mode command (write) | UINT16 | Mode-change command | Read/write |
Enable Modbus control & writes
Set Communication mode to Modbus in the RS485 COMM menu, then set the server ID (1-247), baud rate and parity.
Byte order & addressing
- Only functions 03 and 16 are supported.
- Register 0 reads back the protocol revision but accepts mode-key writes.
Network setup
- Baud 1200-115200 selectable; parity None/Even/Odd; stop bits 1 or 2.
- RS-485 is on terminals 15 (B) and 16 (A); the port has a built-in 120 ohm termination resistor.
- Up to 255 registers per request; the manual gives a 250 ms no-response timeout.
Watch out for
- Phase frequencies are labelled R, Y, B (L1, L2, L3).
DEIF SGC 120 / SGC 121 Single Genset Controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Protocol revision (read) / DG mode command (write) | FC03 returns the protocol revision; FC16 writes one key code. | UINT16 | Read/write | 1 = STOP key; 2 = START key; 4 = AUTO key; 64 = ACK key | |||
| HR | 1 | Generator L1-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 2 | Generator L2-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 3 | Generator L3-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 4 | Generator L1-L2 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 5 | Generator L2-L3 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 6 | Generator L3-L1 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 7 | Generator R frequency | Phase R (L1) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8 | Generator Y frequency | Phase Y (L2) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 9 | Generator B frequency | Phase B (L3) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 10 | Generator power factor L1 | INT16 | × 0.01 | Read | ||||
| HR | 11 | Generator power factor L2 | INT16 | × 0.01 | Read | ||||
| HR | 12 | Generator power factor L3 | INT16 | × 0.01 | Read | ||||
| HR | 13 | Generator average power factor | INT16 | × 0.01 | Read | ||||
| HR | 14 | Mains L1-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 15 | Mains L2-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 16 | Mains L3-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 17 | Mains L1-L2 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 18 | Mains L2-L3 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 19 | Mains L3-L1 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 20 | Mains R frequency | Phase R (L1) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 21 | Mains Y frequency | Phase Y (L2) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 22 | Mains B frequency | Phase B (L3) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 23 | Load L1 current | UINT16 | × 0.1 | A | Read | |||
| HR | 24 | Load L2 current | UINT16 | × 0.1 | A | Read | |||
| HR | 25 | Load L3 current | UINT16 | × 0.1 | A | Read | |||
| HR | 26 | Load L1 active power | INT16 | × 0.1 | kW | Read | |||
| HR | 27 | Load L2 active power | INT16 | × 0.1 | kW | Read | |||
| HR | 28 | Load L3 active power | INT16 | × 0.1 | kW | Read | |||
| HR | 29 | Load total active power | INT16 | × 0.1 | kW | Read | |||
| HR | 30 | Percentage Load | Load as a percentage of rating. | INT16 | % | Read | |||
| HR | 31 | Load L1 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 32 | Load L2 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 33 | Load L3 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 34 | Load total apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 35 | Load L1 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 36 | Load L2 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 37 | Load L3 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 38 | Load total reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 51 | Oil pressure | UINT16 | × 0.1 | bar | Read | |||
| HR | 52 | Coolant temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 53 | Fuel level | UINT16 | % | Read | ||||
| HR | 54 | Fuel level in litres | UINT16 | × 0.1 | L | Read | |||
| HR | 55 | Charge alternator voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 56 | Battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 57 | Engine speed | UINT16 | rpm | Read | ||||
| HR | 58 | No of starts | UINT16 | Read | |||||
| HR | 59 | No of trips | UINT16 | Read | |||||
| HR | 62 | Eng run min | UINT16 | min | Read | ||||
| HR | 63 | Mains run hrs | UINT16 | h | Read | ||||
| HR | 64 | Mains run min | UINT16 | min | Read | ||||
| HR | 65 | Alarm states word 1 | Oil pressure, coolant temp, fuel level, water level states. | UINT16 | Read | ||||
| HR | 66 | Alarm states word 2 | Under/over speed, fail to start, fail to stop states. | UINT16 | Read | ||||
| HR | 67 | Alarm states word 3 | Reverse power, low load, gen low/high frequency states. | UINT16 | Read | ||||
| HR | 68 | Alarm states word 4 | Gen high current, overload, unbalanced load, emergency stop states. | UINT16 | Read | ||||
| HR | 69 | Alarm states word 5 | Charge alternator, maintenance due, AFT timeout, ash load states. | UINT16 | Read | ||||
| HR | 70 | Alarm states word 6 | Battery low/high voltage, temperature circuit open, LOP short states. | UINT16 | Read | ||||
| HR | 71 | Alarm states word 7 | Fuel theft, pickup fault, oil pressure open circuit, aux input I. | UINT16 | Read | ||||
| HR | 72 | Alarm states word 8 | Auxiliary inputs A-D states. | UINT16 | Read | ||||
| HR | 73 | Alarm states word 9 | Auxiliary inputs E-H states. | UINT16 | Read | ||||
| HR | 74 | Alarm states word 10 | Gen L1 and L2 low and high voltage states. | UINT16 | Read | ||||
| HR | 75 | Alarm states word 11 | Gen L3 low/high voltage, DG and mains phase rotation. | UINT16 | Read | ||||
| HR | 76 | Alarm states word 12 | Fuel level open circuit, V-belt broken, high oil pressure. | UINT16 | Read | ||||
| HR | 77 | Digital input/output status word | Inputs A-I and outputs A-F packed one per bit; see notes. | UINT16 | Read | ||||
| HR | 78 | DG status word | Mode, mains healthy, load position, running and common alarm flags; see notes. | UINT16 | Read | ||||
| HR | 82 | Current time stamp: year | UINT16 | Read |
Notes on this map
- Left out: the 32-bit energy counters (39-50) and engine run hours (60-61). The tables give each as a two-register range with no word order, so they cannot be decoded with certainty.
- Scaling is a multiplier: 0.1 means the raw value is in tenths.
- Alarm words 65-76 each pack four alarms as 4-bit fields. The table numbers bits 1-16 and puts the first-listed alarm in bits 13-16, the next in 9-12, then 5-8 and 1-4. It does not say whether bit 1 is the least significant bit, so the fields are not split here. Each field holds 0 = disabled, 1 = not active, 2 = warning, 3 = shutdown, 4 = electrical trip, 5 = notification.
- Word 77 packs digital inputs A-I (table bits 16 down to 8) and outputs A-F (bits 7 down to 2). Word 78 packs, from table bit 16 down: SGC mode, mains healthy, operation mode (bits 14-12: 110 scheduler, 101 auto, 100 manual), load on mains, load on DG, DG running/stopped, stopped normally, stopped with fault, fail to start, gen available, common shutdown, common electric trip, common warning, common notification. The same bit-numbering caveat applies.
- Registers 79-81 hold the time stamp as packed hex bytes (minute/second, weekday/hour, month/day) and are not listed; 82 holds the year.
- Mode-change writes use function 16 to register 0 with one key code at a time.
- RS-485 settings come from the SGC 120 user manual 4189341340B (https://deif-cdn-umbraco.azureedge.net/media/1ajpbyvp/sgc-120-user-manual-4189341340-uk.pdf).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF SGC 120 / SGC 121 Single Genset Controller
What Modbus registers does the DEIF SGC 120 / SGC 121 Single Genset Controller have?
This map lists 66 registers: 66 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF SGC 120 / SGC 121 Single Genset Controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print plain register numbers starting at 0, and the user manual's frame layouts put the register address from the map straight into the request. Read generator L1-N voltage at 1, not 40002.
What are the minimum Modbus registers to integrate the DEIF SGC 120 / SGC 121 Single Genset Controller?
Start with HR 1 Generator L1-N voltage (Generator L1-N voltage); HR 7 Generator R frequency (Generator frequency); HR 23 Load L1 current (Load L1 current); HR 29 Load total active power (Total kW); HR 56 Battery voltage (Battery voltage); HR 78 DG status word (Genset status flags); HR 0 Protocol revision (read) / DG mode command (write) (Mode-change command).
How do I enable Modbus control of the DEIF SGC 120 / SGC 121 Single Genset Controller?
Set Communication mode to Modbus in the RS485 COMM menu, then set the server ID (1-247), baud rate and parity.
Where is the official DEIF SGC 120 / SGC 121 Single Genset Controller Modbus documentation?
The source is SGC 120 and SGC 121 Modbus tables (4189341357), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/pawhllhf/sgc-120-sgc-121-modbus-tables-4189341357.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
Other generator controllers register maps
- Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
SmartGen HGM6100N / HGM6100CAN Series
HGM6100N and HGM6100CAN genset controllers (HGM6110 auto-start and HGM6120 AMF variants), protocol document v1.7.
Also known as: HGM6100CAN, HGM6110N, HGM6120N, HGM6110CAN, HGM6120CAN - Generator controller (utility-tie master synchronizer)
Woodward MSLC-2 Master Synchronizer and Load Control
MSLC-2, data protocol 5200, per manual 37444G.
Also known as: MSLC2, MSLC-2 master synchronizer - Generator controller
Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)
Cummins PowerCommand 2.x and 3.x generator set controls (PC 2.2, 2.3, 3.3), per section 2 of A029X159 Issue 7; registers marked PC 3.x only are absent on PC 2.x.
Also known as: PowerCommand 2.2, PowerCommand 2.3, PowerCommand 3.3, PC2.2, PC2.3, PC3.3 - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC
All generator controllers Modbus register maps →
Source: SGC 120 and SGC 121 Modbus tables · 4189341357. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.