Generator controller · Modbus register map

DEIF SGC 120 / SGC 121 Single Genset Controller Modbus register map

Updated 19 November 2026

Short answer

The SGC 120 and SGC 121 are DEIF's small auto-start and AMF genset controllers. They act as a Modbus RTU server on one RS-485 port, and every value is a holding register read with function 03. This map covers the 16-bit generator, mains and load readings, engine values, start and trip counters, the packed alarm-state, I/O and genset-status words, and the mode-change command.

This page lists 66 Modbus registers for the DEIF SGC 120 / SGC 121 Single Genset Controller — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.

Manufacturer
DEIF
Model
SGC 120 / SGC 121 Single Genset Controller
Equipment type
Generator controller
Registers
66 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
0-based (the number printed is the address on the wire)
Firmware
Application software 9.04 (user manual 4189341340B)
Also known as
SGC 120, SGC 121, SGC120, SGC121
Source document
SGC 120 and SGC 121 Modbus tables · 4189341357
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DEIF SGC 120 / SGC 121 Single Genset Controller

Integration in brief

Poll holding registers 1-59 with function 03 for live values and 78 for genset status. To start or stop remotely, write 2 (START) or 1 (STOP) to register 0 with function 16; write 4 to go to AUTO.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Generator L1-N voltageUINT16Generator L1-N voltageRead
HR 7Generator R frequencyUINT16Generator frequencyRead
HR 23Load L1 currentUINT16Load L1 currentRead
HR 29Load total active powerINT16Total kWRead
HR 56Battery voltageUINT16Battery voltageRead
HR 78DG status wordUINT16Genset status flagsRead
HR 0Protocol revision (read) / DG mode command (write)UINT16Mode-change commandRead/write

Enable Modbus control & writes

Set Communication mode to Modbus in the RS485 COMM menu, then set the server ID (1-247), baud rate and parity.

Byte order & addressing

Network setup

Watch out for

DEIF SGC 120 / SGC 121 Single Genset Controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

66 of 66 shown
DEIF SGC 120 / SGC 121 Single Genset Controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Protocol revision (read) / DG mode command (write)FC03 returns the protocol revision; FC16 writes one key code.UINT16Read/write1 = STOP key; 2 = START key; 4 = AUTO key; 64 = ACK key
HR1Generator L1-N voltageUINT16× 0.1VRead
HR2Generator L2-N voltageUINT16× 0.1VRead
HR3Generator L3-N voltageUINT16× 0.1VRead
HR4Generator L1-L2 voltageUINT16× 0.1VRead
HR5Generator L2-L3 voltageUINT16× 0.1VRead
HR6Generator L3-L1 voltageUINT16× 0.1VRead
HR7Generator R frequencyPhase R (L1) frequency.UINT16× 0.1HzRead
HR8Generator Y frequencyPhase Y (L2) frequency.UINT16× 0.1HzRead
HR9Generator B frequencyPhase B (L3) frequency.UINT16× 0.1HzRead
HR10Generator power factor L1INT16× 0.01Read
HR11Generator power factor L2INT16× 0.01Read
HR12Generator power factor L3INT16× 0.01Read
HR13Generator average power factorINT16× 0.01Read
HR14Mains L1-N voltageUINT16× 0.1VRead
HR15Mains L2-N voltageUINT16× 0.1VRead
HR16Mains L3-N voltageUINT16× 0.1VRead
HR17Mains L1-L2 voltageUINT16× 0.1VRead
HR18Mains L2-L3 voltageUINT16× 0.1VRead
HR19Mains L3-L1 voltageUINT16× 0.1VRead
HR20Mains R frequencyPhase R (L1) frequency.UINT16× 0.1HzRead
HR21Mains Y frequencyPhase Y (L2) frequency.UINT16× 0.1HzRead
HR22Mains B frequencyPhase B (L3) frequency.UINT16× 0.1HzRead
HR23Load L1 currentUINT16× 0.1ARead
HR24Load L2 currentUINT16× 0.1ARead
HR25Load L3 currentUINT16× 0.1ARead
HR26Load L1 active powerINT16× 0.1kWRead
HR27Load L2 active powerINT16× 0.1kWRead
HR28Load L3 active powerINT16× 0.1kWRead
HR29Load total active powerINT16× 0.1kWRead
HR30Percentage LoadLoad as a percentage of rating.INT16%Read
HR31Load L1 apparent powerUINT16× 0.1kVARead
HR32Load L2 apparent powerUINT16× 0.1kVARead
HR33Load L3 apparent powerUINT16× 0.1kVARead
HR34Load total apparent powerUINT16× 0.1kVARead
HR35Load L1 reactive powerUINT16× 0.1kvarRead
HR36Load L2 reactive powerUINT16× 0.1kvarRead
HR37Load L3 reactive powerUINT16× 0.1kvarRead
HR38Load total reactive powerUINT16× 0.1kvarRead
HR51Oil pressureUINT16× 0.1barRead
HR52Coolant temperatureINT16× 0.1°CRead
HR53Fuel levelUINT16%Read
HR54Fuel level in litresUINT16× 0.1LRead
HR55Charge alternator voltageUINT16× 0.1VRead
HR56Battery voltageUINT16× 0.1VRead
HR57Engine speedUINT16rpmRead
HR58No of startsUINT16Read
HR59No of tripsUINT16Read
HR62Eng run minUINT16minRead
HR63Mains run hrsUINT16hRead
HR64Mains run minUINT16minRead
HR65Alarm states word 1Oil pressure, coolant temp, fuel level, water level states.UINT16Read
HR66Alarm states word 2Under/over speed, fail to start, fail to stop states.UINT16Read
HR67Alarm states word 3Reverse power, low load, gen low/high frequency states.UINT16Read
HR68Alarm states word 4Gen high current, overload, unbalanced load, emergency stop states.UINT16Read
HR69Alarm states word 5Charge alternator, maintenance due, AFT timeout, ash load states.UINT16Read
HR70Alarm states word 6Battery low/high voltage, temperature circuit open, LOP short states.UINT16Read
HR71Alarm states word 7Fuel theft, pickup fault, oil pressure open circuit, aux input I.UINT16Read
HR72Alarm states word 8Auxiliary inputs A-D states.UINT16Read
HR73Alarm states word 9Auxiliary inputs E-H states.UINT16Read
HR74Alarm states word 10Gen L1 and L2 low and high voltage states.UINT16Read
HR75Alarm states word 11Gen L3 low/high voltage, DG and mains phase rotation.UINT16Read
HR76Alarm states word 12Fuel level open circuit, V-belt broken, high oil pressure.UINT16Read
HR77Digital input/output status wordInputs A-I and outputs A-F packed one per bit; see notes.UINT16Read
HR78DG status wordMode, mains healthy, load position, running and common alarm flags; see notes.UINT16Read
HR82Current time stamp: yearUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DEIF SGC 120 / SGC 121 Single Genset Controller

What Modbus registers does the DEIF SGC 120 / SGC 121 Single Genset Controller have?

This map lists 66 registers: 66 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DEIF SGC 120 / SGC 121 Single Genset Controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print plain register numbers starting at 0, and the user manual's frame layouts put the register address from the map straight into the request. Read generator L1-N voltage at 1, not 40002.

What are the minimum Modbus registers to integrate the DEIF SGC 120 / SGC 121 Single Genset Controller?

Start with HR 1 Generator L1-N voltage (Generator L1-N voltage); HR 7 Generator R frequency (Generator frequency); HR 23 Load L1 current (Load L1 current); HR 29 Load total active power (Total kW); HR 56 Battery voltage (Battery voltage); HR 78 DG status word (Genset status flags); HR 0 Protocol revision (read) / DG mode command (write) (Mode-change command).

How do I enable Modbus control of the DEIF SGC 120 / SGC 121 Single Genset Controller?

Set Communication mode to Modbus in the RS485 COMM menu, then set the server ID (1-247), baud rate and parity.

Where is the official DEIF SGC 120 / SGC 121 Single Genset Controller Modbus documentation?

The source is SGC 120 and SGC 121 Modbus tables (4189341357), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/pawhllhf/sgc-120-sgc-121-modbus-tables-4189341357.xlsx.

More DEIF Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: SGC 120 and SGC 121 Modbus tables · 4189341357. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.