  4. PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)

Generator controller · Modbus register map

Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

PowerCommand 2.x/3.x are Cummins genset controls with a Modbus RTU slave port. Section 2 of the Cummins register mapping gives the switch position, active fault, genset AC metering and energy counters, engine data, and on PC 3.x also utility and genset-bus metering for paralleling. This map covers the monitoring block from 40010 to 40596 plus the Modbus remote start and fault reset.

This page lists 152 Modbus registers for the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cummins’s own free documentation (linked below) and checked against it.

Manufacturer
Cummins
Model
PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)
Equipment type
Generator controller
Registers
152 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
PowerCommand 2.2, PowerCommand 2.3, PowerCommand 3.3, PC2.2, PC2.3, PC3.3
Source document
Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)

Integration in brief

Poll 40010 (switch position), 40012/40013 (most recent fault and its type), 40018-40043 for genset AC values and 40061-40068 for engine data. Remote start is 40300 = 1 and fault reset 40301 = 1.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9Control Switch PositionUINT16Control switch positionRead
HR 11Most Recent Fault or WarningUINT16Most recent fault codeRead
HR 12Fault type of most recent faultUINT16Fault typeRead
HR 24Genset LL Average VoltageUINT16Average L-L voltageRead
HR 28Genset Average CurrentUINT16Average currentRead
HR 33Genset Total kWINT16Total kWRead
HR 67Average Engine SpeedUINT16Engine speedRead
HR 299Remote Start Switch(Modbus)UINT16Remote startRead/write

Enable Modbus control & writes

The section gives no enable parameter; the control's Modbus port settings are made at the control (see the control documentation).

Byte order & addressing

Network setup

Watch out for

Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

152 of 152 shown
Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9doc 40010Control Switch PositionUINT16Read0 = Off; 1 = Auto; 2 = Manual
HR11doc 40012Most Recent Fault or WarningMost recent fault or warning code.UINT16Read
HR12doc 40013Fault type of most recent faultUINT16Read0 = None; 1 = Warning; 2 = Shutdown
HR13doc 40014Genset % Standby Total kWINT16× 0.01%Read
HR15doc 40016NFPA 110 Logical StatusNFPA 110 bit map, section 4 Table 4-1.BITMAP16Read
HR16doc 40017Extended NFPA 110 Logical StatusExtended annunciation bit map, Table 4-2.BITMAP16Read
HR17doc 40018Genset L1N VoltageUINT16VRead
HR18doc 40019Genset L2N VoltageUINT16VRead
HR19doc 40020Genset L3N VoltageUINT16VRead
HR21doc 40022Genset L1L2 VoltageUINT16VRead
HR22doc 40023Genset L2L3 VoltageUINT16VRead
HR23doc 40024Genset L3L1 VoltageUINT16VRead
HR24doc 40025Genset LL Average VoltageUINT16VRead
HR25doc 40026Genset L1 CurrentUINT16ARead
HR26doc 40027Genset L2 CurrentUINT16ARead
HR27doc 40028Genset L3 CurrentUINT16ARead
HR28doc 40029Genset Average CurrentUINT16ARead
HR29doc 40030Genset Neutral CurrentPC 3.x only.UINT16ARead
HR30doc 40031Genset L1 kWINT16kWRead
HR31doc 40032Genset L2 kWINT16kWRead
HR32doc 40033Genset L3 kWINT16kWRead
HR33doc 40034Genset Total kWINT16kWRead
HR34doc 40035Genset L1 kVARINT16kVARRead
HR35doc 40036Genset L2 kVARINT16kVARRead
HR36doc 40037Genset L3 kVARINT16kVARRead
HR37doc 40038Genset Total kVARINT16kVARRead
HR39doc 40040Genset L1 kVAUINT16kVARead
HR40doc 40041Genset L2 kVAUINT16kVARead
HR41doc 40042Genset L3 kVAUINT16kVARead
HR42doc 40043Genset Total kVAUINT16kVARead
HR45doc 40046-40047Genset Total Negative kWhUINT32ABCDkWhRead
HR47doc 40048-40049Genset Total Positive kWhUINT32ABCDkWhRead
HR49doc 40050-40051Genset Total Net kWhINT32ABCDkWhRead
HR51doc 40052-40053Genset Total Negative kVARhUINT32ABCDkVARhRead
HR53doc 40054-40055Genset Total Positive kVARhUINT32ABCDkVARhRead
HR57doc 40058Genset % Standby L1 CurrentUINT16× 0.1%Read
HR58doc 40059Genset % Standby L2 CurrentUINT16× 0.1%Read
HR59doc 40060Genset % Standby L3 CurrentUINT16× 0.1%Read
HR60doc 40061Battery VoltageUINT16× 0.1VRead
HR61doc 40062Oil PressureUINT16kPaRead
HR62doc 40063Oil TemperatureINT16× 0.1°FRead
HR63doc 40064Coolant TemperatureINT16× 0.1°CRead
HR64doc 40065Intake Manifold TemperatureINT16× 0.1°FRead
HR65doc 40066Fuel TemperatureINT16× 0.1°FRead
HR66doc 40067Fuel RateUINT16× 0.05gal/hrRead
HR67doc 40068Average Engine SpeedUINT16rpmRead
HR69doc 40070-40071Engine Running TimeUINT32ABCD× 0.1sRead
HR71doc 40072-40073Total Fuel ConsumptionUINT32ABCD× 0.1galRead
HR73doc 40074-40075Total Number of RunsUINT32ABCDRead
HR117doc 40118Utility L1N VoltagePC 3.x only.UINT16VRead
HR118doc 40119Utility L2N VoltagePC 3.x only.UINT16VRead
HR119doc 40120Utility L3N VoltagePC 3.x only.UINT16VRead
HR121doc 40122Utility L1L2 VoltagePC 3.x only.UINT16VRead
HR122doc 40123Utility L2L3 VoltagePC 3.x only.UINT16VRead
HR123doc 40124Utility L3L1 VoltagePC 3.x only.UINT16VRead
HR124doc 40125Utility LL Average VoltagePC 3.x only.UINT16VRead
HR125doc 40126Utility L1 CurrentPC 3.x only.UINT16ARead
HR126doc 40127Utility L2 CurrentPC 3.x only.UINT16ARead
HR127doc 40128Utility L3 CurrentPC 3.x only.UINT16ARead
HR130doc 40131Utility L1 kWPC 3.x only.INT16kWRead
HR131doc 40132Utility L2 kWPC 3.x only.INT16kWRead
HR132doc 40133Utility L3 kWPC 3.x only.INT16kWRead
HR133doc 40134Utility Total kWPC 3.x only.INT16kWRead
HR134doc 40135Utility L1 kVARPC 3.x only.INT16kVARRead
HR135doc 40136Utility L2 kVARPC 3.x only.INT16kVARRead
HR136doc 40137Utility L3 kVARPC 3.x only.INT16kVARRead
HR137doc 40138Utility Total kVARPC 3.x only.INT16kVARRead
HR139doc 40140Utility L1 kVAPC 3.x only.UINT16kVARead
HR140doc 40141Utility L2 kVAPC 3.x only.UINT16kVARead
HR141doc 40142Utility L3 kVAPC 3.x only.UINT16kVARead
HR142doc 40143Utility Total kVAPC 3.x only.UINT16kVARead
HR143doc 40144-40145Utility FrequencyPC 3.x only.UINT32ABCD× 0.001HzRead
HR145doc 40146-40147Utility Total Negative kWhPC 3.x only.UINT32ABCDkWhRead
HR147doc 40148-40149Utility Total Positive kWhPC 3.x only.UINT32ABCDkWhRead
HR149doc 40150-40151Utility Total Net kWhPC 3.x only.INT32ABCDkWhRead
HR151doc 40152-40153Utility Total Negative kVARhPC 3.x only.UINT32ABCDkVARhRead
HR153doc 40154-40155Utility Total Positive kVARhPC 3.x only.UINT32ABCDkVARhRead
HR155doc 40156-40157Utility Total Net kVARhPC 3.x only.INT32ABCDkVARhRead
HR157doc 40158Genset Bus L1N VoltagePC 3.x only.UINT16VRead
HR158doc 40159Genset Bus L2N VoltagePC 3.x only.UINT16VRead
HR159doc 40160Genset Bus L3N VoltagePC 3.x only.UINT16VRead
HR161doc 40162Genset Bus L1L2 VoltagePC 3.x only.UINT16VRead
HR162doc 40163Genset Bus L2L3 VoltagePC 3.x only.UINT16VRead
HR163doc 40164Genset Bus L3L1 VoltagePC 3.x only.UINT16VRead
HR164doc 40165Genset Bus LL Average VoltagePC 3.x only.UINT16VRead
HR165doc 40166Genset Bus L1 CurrentPC 3.x only.UINT16ARead
HR166doc 40167Genset Bus L2 CurrentPC 3.x only.UINT16ARead
HR167doc 40168Genset Bus L3 CurrentPC 3.x only.UINT16ARead
HR170doc 40171Genset Bus L1 kWPC 3.x only.INT16kWRead
HR171doc 40172Genset Bus L2 kWPC 3.x only.INT16kWRead
HR172doc 40173Genset Bus L3 kWPC 3.x only.INT16kWRead
HR173doc 40174Genset Bus Total kWPC 3.x only.INT16kWRead
HR174doc 40175Genset Bus L1 kVARPC 3.x only.INT16kVARRead
HR175doc 40176Genset Bus L2 kVARPC 3.x only.INT16kVARRead
HR176doc 40177Genset Bus L3 kVARPC 3.x only.INT16kVARRead
HR177doc 40178Genset Bus Total kVARPC 3.x only.INT16kVARRead
HR179doc 40180Genset Bus L1 kVAPC 3.x only.UINT16kVARead
HR180doc 40181Genset Bus L2 kVAPC 3.x only.UINT16kVARead
HR181doc 40182Genset Bus L3 kVAPC 3.x only.UINT16kVARead
HR182doc 40183Genset Bus Total kVAPC 3.x only.UINT16kVARead
HR183doc 40184-40185Genset Bus FrequencyPC 3.x only.UINT32ABCD× 0.001HzRead
HR185doc 40186-40187Genset Bus Total Negative kWhPC 3.x only.UINT32ABCDkWhRead
HR187doc 40188-40189Genset Bus Total Positive kWhPC 3.x only.UINT32ABCDkWhRead
HR189doc 40190-40191Genset Bus Total Net kWhPC 3.x only.INT32ABCDkWhRead
HR191doc 40192-40193Genset Bus Total Negative kVARhPC 3.x only.UINT32ABCDkVARhRead
HR193doc 40194-40195Genset Bus Total Positive kVARhPC 3.x only.UINT32ABCDkVARhRead
HR195doc 40196-40197Genset Bus Total Net kVARhPC 3.x only.INT32ABCDkVARhRead
HR197doc 40198Ground CurrentPC 3.x only.UINT16× 0.1ARead
HR198doc 40199Genset Negative Sequence Current %PC 3.x only.UINT16× 0.01%Read
HR200doc 40201Coolant Temperature Sensor TypeUINT16Read0 = PGBU; 1 = EBU
HR206doc 40207Battery Charger Alternator Flash VoltageUINT16× 0.001VRead
HR209doc 40210External Speed Bias InputINT16× 0.01%Read
HR210doc 40211External Voltage Bias InputINT16× 0.01%Read
HR225doc 40226Speed Bias Output / Configurable Analog output #1 Output PredictorPC 3.x only.INT16× 0.01VRead
HR226doc 40227Voltage Bias Output / Configurable Analog output #2 Output PredictorPC 3.x only.INT16× 0.01VRead
HR227doc 40228Amber Warning Lamp StatusUINT16Read0 = Inactive; 1 = Active
HR228doc 40229Barometric absolute pressureUINT16× 0.1psiRead
HR229doc 40230Boost PressureUINT16× 0.1psiRead
HR230doc 40231CAN Datalink StatusUINT16Read0 = Inactive; 1 = Active; 2 = Failed
HR231doc 40232Crankcase PressureINT16× 0.1psiRead
HR234doc 40235ECM Derate RequestUINT16Read0 = No Derate Request; 1 = Derate Request; 2 = Error; 3 = Don’t Care
HR235doc 40236Engine Application TypeUINT16Read0 = ECM; 1 = Hydro-Mechanical
HR241doc 40242Aftercooler TemperatureINT16× 0.1°FRead
HR253doc 40254Fuel Supply PressureUINT16× 0.1psiRead
HR257doc 40258-40259Fuel Outlet PressureUINT32ABCD× 0.1psiRead
HR259doc 40260Intake Manifold 2 TemperatureINT16× 0.1°FRead
HR260doc 40261Intake Manifold 3 TemperatureINT16× 0.1°FRead
HR263doc 40264Percent Engine Torque/Duty CycleINT16%Read
HR275doc 40276Post-Filter Oil PressureUINT16× 0.1psiRead
HR276doc 40277Pre-Filter Oil PressureUINT16× 0.1psiRead
HR277doc 40278Configurable Input #14 SwitchUINT16Read0 = Inactive; 1 = Active
HR278doc 40279-40280Turbocharger 1 SpeedUINT32ABCDrpmRead
HR280doc 40281Turbocharger 2 Boost PressureUINT16× 0.1psiRead
HR281doc 40282Water in Fuel IndicatorUINT16Read0 = No; 1 = Yes
HR282doc 40283Controller ModeUINT16Read0 = Off; 1 = Ready; 2 = Setup; 3 = Starting; 4 = Idle; 5 = Rated; 6 = Stop Normal; 7 = Stop Emergency; 8 = Factory Test; 9 = Wait to Power Down
HR284doc 40285Power Down Mode TimerUINT16sRead
HR297doc 40298-40299Runs Since ResetUINT32ABCDRead
HR299doc 40300Remote Start Switch(Modbus)Write 1 to start the genset remotely, 0 to release.UINT16Read/write0 = Inactive; 1 = Active
HR300doc 40301Fault Reset (Modbus)Write 1 to reset faults.UINT16Read/write0 = Inactive; 1 = Active
HR499doc 40500Low Fuel SwitchUINT16Read0 = Inactive; 1 = Active
HR500doc 40501Low Fuel/Configurable Input #6 SwitchUINT16Read0 = Inactive; 1 = Active
HR508doc 40509PTC Mode SwitchPC 3.x only.UINT16Read0 = Inactive; 1 = Active
HR509doc 40510Extended Parallel/Configurable Input #32 SwitchPC 3.x only.UINT16Read0 = Inactive; 1 = Active
HR564doc 40565Common Warning Event StatusUINT16Read0 = Inactive; 1 = Active
HR569doc 40570Fault Reset CommandUINT16Read0 = Inactive; 1 = Active
HR576doc 40577-40578Base FrequencyUINT32ABCD× 0.001HzRead
HR585doc 40586Excitation StateUINT16Read0 = Disabled; 1 = Enabled
HR586doc 40587Exercise CommandUINT16Read0 = Inactive; 1 = Active; 2 = Reserved; 3 = Not Available
HR588doc 40589Exercise Time RemainingUINT16× 0.1hRead
HR591doc 40592Battle Short CommandUINT16Read0 = Inactive; 1 = Active
HR594doc 40595-40596Final Frequency ReferenceUINT32ABCD× 0.001HzRead
HR40055doc 40056-40057Genset Total Net kVARhINT32ABCDkVARhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)

What Modbus registers does the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) have?

This map lists 152 registers: 152 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as Modicon 4xxxx holding-register numbers; 40010 is wire address 9.

What byte order does the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)?

Start with HR 9 Control Switch Position (Control switch position); HR 11 Most Recent Fault or Warning (Most recent fault code); HR 12 Fault type of most recent fault (Fault type); HR 24 Genset LL Average Voltage (Average L-L voltage); HR 28 Genset Average Current (Average current); HR 33 Genset Total kW (Total kW); HR 67 Average Engine Speed (Engine speed); HR 299 Remote Start Switch(Modbus) (Remote start).

How do I enable Modbus control of the Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)?

The section gives no enable parameter; the control's Modbus port settings are made at the control (see the control documentation).

Where is the official Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU) Modbus documentation?

The source is Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) (A029X159 Issue 7), revision 2012-04. Cummins doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/modbus2300.pdf. It may be an older revision, so check it against the live unit.

More Cummins Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.