Generator controller (paralleling master control) · Modbus register map

Cummins MCM3320 master control module (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The MCM3320 is a Cummins master control for paralleled gensets and utility transfer pairs. Over Modbus RTU it reports genset-bus and utility metering, system and transfer state, breaker positions, load add/shed and load-demand status, and exposes system settings such as topology, transition type and kW/kVAR setpoints. This map covers the 42xxx master-control registers.

This page lists 224 Modbus registers for the Cummins MCM3320 master control module (Modbus RTU) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cummins’s own free documentation (linked below) and checked against it.

Manufacturer
Cummins
Model
MCM3320 master control module (Modbus RTU)
Equipment type
Generator controller (paralleling master control)
Registers
224 (41 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
MCM3320, MCM 3320, PowerCommand MCM3320
Source document
Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Cummins MCM3320 master control module (Modbus RTU)

Integration in brief

Poll 42210 (system state), 42224 (PTC state), 42218/42219 (genset and utility breaker positions), 42033 and 42133 (genset and utility kW) and 42012 (active fault). Settings in 42300-42334 are read/write; write 42004 = 1 to keep changes after power loss.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2209System StateUINT16System stateRead
HR 2223PTC StateUINT16PTC stateRead
HR 2217Gen CB Position StatusUINT16Genset breaker positionRead
HR 2218Util CB Position StatusUINT16Utility breaker positionRead
HR 2032Genset Total kWINT16Genset total kWRead
HR 2132Utility Total kWINT16Utility total kWRead
HR 2011Current Fault StatusUINT16Active faultRead

Enable Modbus control & writes

Modbus RTU is on the RS-485 port; defaults are node 1, 19200 baud, 8 data bits, even parity, 1 stop bit, changeable through MON and PCCnet logicals.

Byte order & addressing

Network setup

Watch out for

Cummins MCM3320 master control module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

224 of 224 shown
Cummins MCM3320 master control module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2003doc 42004Save AdjustmentsWrite 1 to save adjustments to non-volatile memory.UINT16Read/write0 = Do Nothing; 1 = Save Trims
HR2008doc 42009Device TypeFixed device type id 52 (0x0034).UINT16Read
HR2009doc 42010Software VersionUINT16× 0.0001Read
HR2010doc 42011Genset Run Sequence StateUINT16Read0 = Time Delay Start; 1 = Time Delay Stop; 2 = Stop; 3 = Run
HR2011doc 42012Current Fault StatusMost recent fault that is still active.UINT16Read
HR2016doc 42017Genset Bus StatusUINT16Read0 = Unavailable; 1 = Dead; 2 = Live
HR2017doc 42018Genset L1N VoltageUINT16VRead
HR2018doc 42019Genset L2N VoltageUINT16VRead
HR2019doc 42020Genset L3N VoltageUINT16VRead
HR2020doc 42021Genset LN Average VoltageUINT16VRead
HR2021doc 42022Genset L1L2 VoltageUINT16VRead
HR2022doc 42023Genset L2L3 VoltageUINT16VRead
HR2023doc 42024Genset L3L1 VoltageUINT16VRead
HR2024doc 42025Genset LL Average VoltageUINT16VRead
HR2025doc 42026Genset L1 CurrentUINT16ARead
HR2026doc 42027Genset L2 CurrentUINT16ARead
HR2027doc 42028Genset L3 CurrentUINT16ARead
HR2028doc 42029Genset Average CurrentUINT16ARead
HR2029doc 42030Genset L1 kWINT16kWRead
HR2030doc 42031Genset L2 kWINT16kWRead
HR2031doc 42032Genset L3 kWINT16kWRead
HR2032doc 42033Genset Total kWINT16kWRead
HR2033doc 42034Genset L1 kVARINT16kVARRead
HR2034doc 42035Genset L2 kVARINT16kVARRead
HR2035doc 42036Genset L3 kVARINT16kVARRead
HR2036doc 42037Genset Total kVARINT16kVARRead
HR2038doc 42039Genset L1 kVAUINT16kVARead
HR2039doc 42040Genset L2 kVAUINT16kVARead
HR2040doc 42041Genset L3 kVAUINT16kVARead
HR2041doc 42042Genset Total kVAUINT16kVARead
HR2042doc 42043MB Genset FrequencyUINT16× 0.1HzRead
HR2043doc 42044Genset Total Negative kWhUINT32ABCDkWhRead
HR2045doc 42046Genset Total Positive kWhUINT32ABCDkWhRead
HR2047doc 42048Genset Total Net kWhINT32ABCDkWhRead
HR2049doc 42050Genset Total Negative kVARhUINT32ABCDkVARhRead
HR2053doc 42054Genset Total Net kVARhINT32ABCDkVARhRead
HR2057doc 42058Genset Available CurrentUINT16ARead
HR2058doc 42059Genset L1 Current PercentINT16× 0.1%Read
HR2059doc 42060Genset L2 Current PercentUINT16× 0.1%Read
HR2060doc 42061Genset L3 Current PercentUINT16× 0.1%Read
HR2061doc 42062Genset Total kW PercentINT16× 0.1%Read
HR2062doc 42063Genset Frequency PercentUINT16× 0.1%Read
HR2063doc 42064Genset L1L2 Voltage%UINT16× 0.1%Read
HR2064doc 42065Genset L2L3 Voltage%UINT16× 0.1%Read
HR2065doc 42066Genset L3L1 Voltage%UINT16× 0.1%Read
HR2069doc 42070Genset Total kW_32bitINT32ABCDkWRead
HR2071doc 42072Genset Total kVAR_32bitINT32ABCDkVARRead
HR2073doc 42074Genset Total kVA_32bitUINT32ABCDkVARead
HR2116doc 42117Utility Bus StatusUINT16Read0 = Unavailable; 1 = Dead; 2 = Live
HR2117doc 42118Utility L1N VoltageUINT16VRead
HR2118doc 42119Utility L2N VoltageUINT16VRead
HR2119doc 42120Utility L3N VoltageUINT16VRead
HR2120doc 42121Utility LN Average VoltageUINT16VRead
HR2121doc 42122Utility L1L2 VoltageUINT16VRead
HR2122doc 42123Utility L2L3 VoltageUINT16VRead
HR2123doc 42124Utility L3L1 VoltageUINT16VRead
HR2124doc 42125Utility LL Average VoltageUINT16VRead
HR2125doc 42126Utility L1 CurrentUINT16ARead
HR2126doc 42127Utility L2 CurrentUINT16ARead
HR2127doc 42128Utility L3 CurrentUINT16ARead
HR2128doc 42129Utility Average CurrentUINT16ARead
HR2129doc 42130Utility L1 kWINT16kWRead
HR2130doc 42131Utility L2 kWINT16kWRead
HR2131doc 42132Utility L3 kWINT16kWRead
HR2132doc 42133Utility Total kWINT16kWRead
HR2133doc 42134Utility L1 kVARINT16kVARRead
HR2134doc 42135Utility L2 kVARINT16kVARRead
HR2135doc 42136Utility L3 kVARINT16kVARRead
HR2136doc 42137Utility Total kVARINT16kVARRead
HR2138doc 42139Utility L1 kVAUINT16kVARead
HR2139doc 42140Utility L2 kVAUINT16kVARead
HR2140doc 42141Utility L3 kVAUINT16kVARead
HR2141doc 42142Utility Total kVAUINT16kVARead
HR2142doc 42143MB Utility FrequencyUINT16HzRead
HR2143doc 42144Utility Total Negative kWhUINT32ABCDkWhRead
HR2145doc 42146Utility Total Positive kWhUINT32ABCDkWhRead
HR2147doc 42148Utility Total Net kWhINT32ABCDkWhRead
HR2149doc 42150Utility Total NegativeUINT32ABCDkVARhRead
HR2151doc 42152Utility Total Positive kVARhUINT32ABCDkVARhRead
HR2153doc 42154Utility Total Net kVARhINT32ABCDkVARhRead
HR2155doc 42156Utility Total kVAhUINT32ABCDkVAhRead
HR2157doc 42158System Total kWINT16kWRead
HR2158doc 42159System Total kVARINT16kVARRead
HR2159doc 42160System Total Power FactorINT16× 0.01Read
HR2160doc 42161System Total kVAUINT16kVARead
HR2161doc 42162Utility L1 Current PercentUINT16× 0.1%Read
HR2162doc 42163Utility L2 Current PercentUINT16× 0.1%Read
HR2163doc 42164Utility L3 Current PercentUINT16× 0.1%Read
HR2164doc 42165Utility Total kW PercentINT16× 0.1%Read
HR2165doc 42166Utility Frequency PercentUINT16× 0.1%Read
HR2166doc 42167Utility L1L2 Voltage %UINT16× 0.1%Read
HR2167doc 42168Utility L2L3 Voltage %UINT16× 0.1%Read
HR2168doc 42169Utility L3L1 Voltage %UINT16× 0.1%Read
HR2169doc 42170Utility Total kW _32 bitINT32ABCDkWRead
HR2171doc 42172Utility total kVAR_32 bitINT32ABCDkVARRead
HR2173doc 42174Utility total kVA_32 bitUINT32ABCDkVARead
HR2175doc 42176System Total kW_32 bitINT32ABCDkWRead
HR2177doc 42178System Total kVAR_32 bitINT32ABCDkVARRead
HR2179doc 42180System Total kVA_32 bitUINT32ABCDkVARead
HR2199doc 42200Total Number of GensetsUINT16Read
HR2200doc 42201Total System CapacityUINT16kWRead
HR2201doc 42202Total Online CapacityINT16kWRead
HR2202doc 42203Programmed Transition TimerUINT16× 0.1sRead
HR2203doc 42204Transfer TimerUINT16× 0.1sRead
HR2204doc 42205Retransfer TimerUINT16× 0.1sRead
HR2205doc 42206Maximum Parallel TimerUINT16× 0.1sRead
HR2206doc 42207kW ReferenceINT16kWRead
HR2207doc 42208Utility Unloaded StatusUINT16Read0 = Not Available; 1 = Not Unloaded; 2 = Unloaded
HR2208doc 42209Genset Unloaded StatusUINT16Read0 = Not Available; 1 = Not Unloaded; 2 = Unloaded
HR2209doc 42210System StateUINT16Read0 = Not Available; 1 = TD Start; 2 = TD Stop; 3 = TD Programmed Transition; 4 = TD Transfer; 5 = TD Retransfer; 6 = Synchronizing; 7 = Sync Check OK; 8 = Inhibit; 9 = Unassigned; 10 = Ramp Unload (printed "Ramp Upload"); 11 = Ramp Load; 12 = Manual; 13 = Utility Failure; 14 = Test; 15 = Standby; 16 = Factory Test; 17 = Extended Parallel
HR2210doc 42211PTC Operating ModeUINT16Read0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel
HR2211doc 42212Active Transition TimerUINT16× 0.1sRead
HR2212doc 42213Hardware VersionUINT16Read
HR2213doc 42214Controller On TimeUINT32ABCDsRead
HR2215doc 42216Genset Availability StatusUINT16Read0 = Not Available; 1 = Available; 2 = Unknown
HR2216doc 42217Utility Availability StatusUINT16Read0 = Not Available; 1 = Available; 2 = Unknown
HR2217doc 42218Gen CB Position StatusUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2218doc 42219Util CB Position StatusUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2219doc 42220kVAR Load ReferenceINT16kVARRead
HR2220doc 42221kVAR Load Setpoint Engr Units Display ValueUINT16× 0.01%Read
HR2221doc 42222kW Load Setpoint Engr Units Display ValueINT16× 0.01%Read
HR2222doc 42223Power Factor SetpointINT16× 0.01Read
HR2223doc 42224PTC StateUINT16Read0 = Not Enabled; 1 = No Source Connected; 2 = Utility Connected; 3 = Genset Connected; 4 = Paralleled
HR2224doc 42225Sync Check Close AllowedUINT16Read0 = Not Allowed; 1 = Allowed
HR2225doc 42226Sync Phase DifferenceINT16× 0.01°Read
HR2226doc 42227Synchronizer StatusUINT16Read0 = Synchronizer Off; 1 = Synchronizer On
HR2227doc 42228System Lockout StatusUINT16Read0 = Inactive; 1 = Active
HR2228doc 42229Breaker 1 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2229doc 42230Breaker 2 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2230doc 42231Breaker 3 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2231doc 42232Breaker 4 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2232doc 42233Breaker 5 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2233doc 42234Breaker 6 PositionUINT16Read0 = Open; 1 = Closed; 2 = Not Available
HR2234doc 42235Breaker 1 Trip StatusUINT16Read0 = Not Available; 1 = Normal; 2 = Tripped
HR2235doc 42236Breaker 2 Trip StatusUINT16Read0 = Not Available; 1 = Normal; 2 = Tripped
HR2245doc 42246PositionUINT16Read0 = Not Available; 1 = No Source Connected; 2 = Source 1 Connected; 3 = Source 2 Connected; 4 = Paralleled
HR2246doc 42247SID1 StatusUINT16Read0 = Missing; 1 = Good; 2 = Connecting; 3 = No EXP Board; 4 = Not Applicable
HR2247doc 42248SID0 StatusUINT16Read0 = Missing; 1 = Good; 2 = Connecting; 3 = No EXP Board; 4 = Not Applicable
HR2248doc 42249Expansion Board CommunicationsUINT16Read0 = Disable; 1 = Enable
HR2249doc 42250Current Add LevelUINT16Read
HR2250doc 42251Current Shed LevelUINT16Read
HR2251doc 42252Add Level 1 CommandUINT16Read0 = Do Nothing; 1 = Add Level
HR2252doc 42253Add Level 2 CommandUINT16Read0 = Do Nothing; 1 = Add Level
HR2253doc 42254Add Level 3 CommandUINT16Read0 = Do Nothing; 1 = Add Level
HR2254doc 42255Add Level 4 CommandUINT16Read0 = Do Nothing; 1 = Add Level
HR2255doc 42256Add Level 5 CommandUINT16Read0 = Do Nothing; 1 = Add Level
HR2286doc 42287Shed Load 3 CommandValues printed as Do Nothing / Add Level in the manual.UINT16Read0 = Do Nothing; 1 = Add Level
HR2287doc 42288Shed Load 4 CommandValues printed as Do Nothing / Add Level in the manual.UINT16Read0 = Do Nothing; 1 = Add Level
HR2288doc 42289Shed Load 5 CommandValues printed as Do Nothing / Add Level in the manual.UINT16Read0 = Do Nothing; 1 = Add Level
HR2289doc 42290Shed Load 6 CommandValues printed as Do Nothing / Add Level in the manual.UINT16Read0 = Do Nothing; 1 = Add Level
HR2290doc 42291Battery Voltage Engr Units Display ValueUINT16× 0.01VRead
HR2291doc 42292kVAR Master Load Control Output Predictor ValueINT16× 0.01VRead
HR2292doc 42293kW Master Load Control Output Predictor ValueINT16× 0.01VRead
HR2293doc 42294Master Frequency Bias Output Predictor ValueINT16× 0.01VRead
HR2294doc 42295Master Voltage Bias Output Predictor ValueINT16× 0.01VRead
HR2295doc 42296PTC Genset Operating ModeUINT16Read0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel
HR2296doc 42297PTC Transfer Pair Operating ModeUINT16Read0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel
HR2297doc 42298PTC Operating Transition TypeUINT16Read0 = Open Transition; 1 = Hard Closed Transition; 2 = Soft Closed Transition
HR2298doc 42299Expansion Board Communications 1UINT16Read0 = Disabled; 1 = Enabled
HR2299doc 42300System TopologyUINT16Read/write0 = Master Synchronize Only; 1 = Isolated Bus w/ out GM; 2 = Isolated Bus w/GM; 3 = Common Bus; 4 = Transfer Pair; 5 = Component Mode
HR2300doc 42301Transition TypeUINT16Read/write0 = Open Transition; 1 = Hard Closed Transition; 2 = Soft Closed Transition
HR2301doc 42302Extended Parallel EnableUINT16Read/write0 = Disabled; 1 = Enabled
HR2302doc 42303Load Demand TypeUINT16Read/write0 = None; 1 = Fixed Sequence; 2 = Run Hours
HR2303doc 42304Priority Control MethodUINT16Read/write0 = Manual; 1 = Automatic
HR2304doc 42305Genset 01 kW RatingINT16kWRead/write
HR2305doc 42306Genset 02 kW RatingINT16kWRead/write
HR2306doc 42307Genset 03 kW RatingINT16kWRead/write
HR2307doc 42308Genset 04 kW RatingINT16kWRead/write
HR2308doc 42309Genset 05 kW RatingINT16kWRead/write
HR2309doc 42310Genset 06 kW RatingINT16kWRead/write
HR2310doc 42311Genset 07 kW RatingINT16kWRead/write
HR2311doc 42312Genset 08 kW RatingINT16kWRead/write
HR2312doc 42313Genset 09 kW RatingINT16kWRead/write
HR2313doc 42314Genset 10 kW RatingINT16kWRead/write
HR2314doc 42315Genset 11 kW RatingINT16kWRead/write
HR2315doc 42316Genset 12 kW RatingINT16kWRead/write
HR2316doc 42317Programmed Transition Delay (TDPT)UINT16× 0.1sRead/write
HR2317doc 42318Transfer Delay (TDNE)UINT16× 0.1sRead/write
HR2318doc 42319Retransfer Delay (TDEN)UINT16× 0.1sRead/write
HR2319doc 42320Maximum Parallel Time (TDMP)UINT16× 0.1sRead/write
HR2320doc 42321Genset Bus %kW SetpointINT16× 0.01%Read/write
HR2321doc 42322Genset Nominal VoltageUINT16VRead/write
HR2322doc 42323Utility Nominal VoltageUINT16VRead/write
HR2323doc 42324Genset Center FrequencyUINT16× 0.1HzRead/write
HR2324doc 42325Utility Center FrequencyUINT16× 0.1HzRead/write
HR2325doc 42326test With Load EnableUINT16Read/write0 = Disable; 1 = Enable
HR2326doc 42327System FrequencyUINT16× 0.1HzRead/write
HR2327doc 42328Genset Bus kW Setpoint SourceUINT16Read/write0 = Internal; 1 = Analog Input
HR2328doc 42329Genset Bus kVAR Setpoint SourceUINT16Read/write0 = Internal; 1 = Analog Input
HR2329doc 42330Genset Bus kW SetpointINT16kWRead/write
HR2330doc 42331Genset Bus kVAR SetpointINT16kVARRead/write
HR2331doc 42332Genset Bus % kVAR SetpointINT16× 0.01%Read/write
HR2332doc 42333Genset Bus Power Factor SetpointINT16× 0.01Read/write
HR2333doc 42334Genset Unloaded LevelINT16kWRead/write
HR2599doc 42600Extended Parallel Start VolUINT16Read/write0 = Stop; 1 = Start
HR2600doc 42601Synchronizer Enable VolUINT16Read/write0 = Inactive; 1 = Active
HR2601doc 42602Utility Source Fail VolUINT16Read/write0 = Inactive; 1 = Active
HR2602doc 42603Transfer Inhibit VolUINT16Read/write0 = No Inhibit; 1 = Inhibit
HR2603doc 42604Retransfer Inhibit VolUINT16Read/write0 = No Inhibit; 1 = Inhibit
HR2697doc 42698Load Add Shed Enable StatusUINT16Read0 = Disabled; 1 = Enabled; 2 = Paused
HR2698doc 42699PCCNet StatusUINT16Read0 = No Connection; 1 = Connected; 2 = Connecting
HR2699doc 42700Gen1 Availability StateUINT16Read0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed
HR2700doc 42701Gen2 Availability StateUINT16Read0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed
HR2701doc 42702Gen3 Availability StateUINT16Read0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed
HR2702doc 42703Gen4 Availability StateUINT16Read0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed
HR2703doc 42704Gen1 Online TimeUINT32ABCD× 0.0002777778hRead
HR2711doc 42712GenAUINT16Read0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16
HR2715doc 42716Load Demand StateUINT16Read0 = Off; 1 = Initial Delay Timing; 2 = Load Monitor
HR2716doc 42717Total Number of Gensets OnlineUINT16Read
HR2717doc 42718Total Spare Online CapacityINT16kWRead
HR2718doc 42719Next Gen Shutdown ThresholdINT16kWRead
HR2719doc 42720Next Gen Shutdown ThresholdINT16kWRead
HR2720doc 42721Next Gen RestartUINT16Read0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16
HR2721doc 42722Next Gen ShutdownUINT16Read0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16
HR2722doc 42723Load Demand Gen1 Driver StatusUINT16Read0 = Run; 1 = Load Demand Stop
HR2723doc 42724Load Demand Gen2 Driver StatusUINT16Read0 = Run; 1 = Load Demand Stop
HR2724doc 42725Load Demand Gen3 Driver StatusUINT16Read0 = Run; 1 = Load Demand Stop
HR2725doc 42726Load Demand Gen4 Driver StatusUINT16Read0 = Run; 1 = Load Demand Stop
HR2726doc 42727Genset Bus kW Overload StatusINT16kWRead
HR2727doc 42728Genset Bus kW Overload StatusUINT16Read0 = No Overload; 1 = Overload
HR2728doc 42729Genset Bus Underfrequency Overload StatusUINT16Read0 = No Overload; 1 = Overload
HR2729doc 42730Active ScheduleUINT16Read0 = None; 1 = Program 1; 2 = Program 2; 3 = Program 3; 4 = Program 4; 5 = Program 5; 6 = Program 6; 7 = Program 7; 8 = Program 8; 9 = Program 9; 10 = Program 10; 11 = Program 11; 12 = Program 12; 13 = Exception 1; 14 = Exception 2; 15 = Exception 3; 16 = Exception 4; 17 = Exception 5; 18 = Exception 6
HR2730doc 42731Scheduler Run CommandUINT16Read0 = Off; 1 = No Load; 2 = With Load; 3 = Extended Parallel
HR2731doc 42732Modbus Bus Message CountUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Cummins MCM3320 master control module (Modbus RTU)

What Modbus registers does the Cummins MCM3320 master control module (Modbus RTU) have?

This map lists 224 registers: 224 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Cummins MCM3320 master control module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as Modicon 4xxxx holding-register numbers; 42018 is wire address 2017.

What byte order does the Cummins MCM3320 master control module (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Cummins MCM3320 master control module (Modbus RTU)?

Start with HR 2209 System State (System state); HR 2223 PTC State (PTC state); HR 2217 Gen CB Position Status (Genset breaker position); HR 2218 Util CB Position Status (Utility breaker position); HR 2032 Genset Total kW (Genset total kW); HR 2132 Utility Total kW (Utility total kW); HR 2011 Current Fault Status (Active fault).

How do I enable Modbus control of the Cummins MCM3320 master control module (Modbus RTU)?

Modbus RTU is on the RS-485 port; defaults are node 1, 19200 baud, 8 data bits, even parity, 1 stop bit, changeable through MON and PCCnet logicals.

Where is the official Cummins MCM3320 master control module (Modbus RTU) Modbus documentation?

The source is Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) (A029X159 Issue 7), revision 2012-04. Cummins doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/modbus2300.pdf. It may be an older revision, so check it against the live unit.

More Cummins Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.