Generator controller (paralleling master control) · Modbus register map
Cummins MCM3320 master control module (Modbus RTU) Modbus register map
Updated 19 November 2026
The MCM3320 is a Cummins master control for paralleled gensets and utility transfer pairs. Over Modbus RTU it reports genset-bus and utility metering, system and transfer state, breaker positions, load add/shed and load-demand status, and exposes system settings such as topology, transition type and kW/kVAR setpoints. This map covers the 42xxx master-control registers.
This page lists 224 Modbus registers for the Cummins MCM3320 master control module (Modbus RTU) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cummins’s own free documentation (linked below) and checked against it.
- Manufacturer
- Cummins
- Model
- MCM3320 master control module (Modbus RTU)
- Equipment type
- Generator controller (paralleling master control)
- Registers
- 224 (41 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MCM3320, MCM 3320, PowerCommand MCM3320
Integration notes: Cummins MCM3320 master control module (Modbus RTU)
Poll 42210 (system state), 42224 (PTC state), 42218/42219 (genset and utility breaker positions), 42033 and 42133 (genset and utility kW) and 42012 (active fault). Settings in 42300-42334 are read/write; write 42004 = 1 to keep changes after power loss.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2209 | System State | UINT16 | System state | Read |
| HR 2223 | PTC State | UINT16 | PTC state | Read |
| HR 2217 | Gen CB Position Status | UINT16 | Genset breaker position | Read |
| HR 2218 | Util CB Position Status | UINT16 | Utility breaker position | Read |
| HR 2032 | Genset Total kW | INT16 | Genset total kW | Read |
| HR 2132 | Utility Total kW | INT16 | Utility total kW | Read |
| HR 2011 | Current Fault Status | UINT16 | Active fault | Read |
Enable Modbus control & writes
Modbus RTU is on the RS-485 port; defaults are node 1, 19200 baud, 8 data bits, even parity, 1 stop bit, changeable through MON and PCCnet logicals.
Byte order & addressing
- 32-bit values are high word first and must be written with function 16.
- Only functions 03, 06, 08 and 16 are supported.
Network setup
- Default node address 1, 19200 8E1.
Watch out for
- The response rules say a block read that includes an undefined register returns 0xFF for that slot, but the holding-register section says the whole read fails; read only listed registers.
Cummins MCM3320 master control module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2003doc 42004 | Save Adjustments | Write 1 to save adjustments to non-volatile memory. | UINT16 | Read/write | 0 = Do Nothing; 1 = Save Trims | |||
| HR | 2008doc 42009 | Device Type | Fixed device type id 52 (0x0034). | UINT16 | Read | ||||
| HR | 2009doc 42010 | Software Version | UINT16 | × 0.0001 | Read | ||||
| HR | 2010doc 42011 | Genset Run Sequence State | UINT16 | Read | 0 = Time Delay Start; 1 = Time Delay Stop; 2 = Stop; 3 = Run | ||||
| HR | 2011doc 42012 | Current Fault Status | Most recent fault that is still active. | UINT16 | Read | ||||
| HR | 2016doc 42017 | Genset Bus Status | UINT16 | Read | 0 = Unavailable; 1 = Dead; 2 = Live | ||||
| HR | 2017doc 42018 | Genset L1N Voltage | UINT16 | V | Read | ||||
| HR | 2018doc 42019 | Genset L2N Voltage | UINT16 | V | Read | ||||
| HR | 2019doc 42020 | Genset L3N Voltage | UINT16 | V | Read | ||||
| HR | 2020doc 42021 | Genset LN Average Voltage | UINT16 | V | Read | ||||
| HR | 2021doc 42022 | Genset L1L2 Voltage | UINT16 | V | Read | ||||
| HR | 2022doc 42023 | Genset L2L3 Voltage | UINT16 | V | Read | ||||
| HR | 2023doc 42024 | Genset L3L1 Voltage | UINT16 | V | Read | ||||
| HR | 2024doc 42025 | Genset LL Average Voltage | UINT16 | V | Read | ||||
| HR | 2025doc 42026 | Genset L1 Current | UINT16 | A | Read | ||||
| HR | 2026doc 42027 | Genset L2 Current | UINT16 | A | Read | ||||
| HR | 2027doc 42028 | Genset L3 Current | UINT16 | A | Read | ||||
| HR | 2028doc 42029 | Genset Average Current | UINT16 | A | Read | ||||
| HR | 2029doc 42030 | Genset L1 kW | INT16 | kW | Read | ||||
| HR | 2030doc 42031 | Genset L2 kW | INT16 | kW | Read | ||||
| HR | 2031doc 42032 | Genset L3 kW | INT16 | kW | Read | ||||
| HR | 2032doc 42033 | Genset Total kW | INT16 | kW | Read | ||||
| HR | 2033doc 42034 | Genset L1 kVAR | INT16 | kVAR | Read | ||||
| HR | 2034doc 42035 | Genset L2 kVAR | INT16 | kVAR | Read | ||||
| HR | 2035doc 42036 | Genset L3 kVAR | INT16 | kVAR | Read | ||||
| HR | 2036doc 42037 | Genset Total kVAR | INT16 | kVAR | Read | ||||
| HR | 2038doc 42039 | Genset L1 kVA | UINT16 | kVA | Read | ||||
| HR | 2039doc 42040 | Genset L2 kVA | UINT16 | kVA | Read | ||||
| HR | 2040doc 42041 | Genset L3 kVA | UINT16 | kVA | Read | ||||
| HR | 2041doc 42042 | Genset Total kVA | UINT16 | kVA | Read | ||||
| HR | 2042doc 42043 | MB Genset Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 2043doc 42044 | Genset Total Negative kWh | UINT32 | ABCD | kWh | Read | |||
| HR | 2045doc 42046 | Genset Total Positive kWh | UINT32 | ABCD | kWh | Read | |||
| HR | 2047doc 42048 | Genset Total Net kWh | INT32 | ABCD | kWh | Read | |||
| HR | 2049doc 42050 | Genset Total Negative kVARh | UINT32 | ABCD | kVARh | Read | |||
| HR | 2053doc 42054 | Genset Total Net kVARh | INT32 | ABCD | kVARh | Read | |||
| HR | 2057doc 42058 | Genset Available Current | UINT16 | A | Read | ||||
| HR | 2058doc 42059 | Genset L1 Current Percent | INT16 | × 0.1 | % | Read | |||
| HR | 2059doc 42060 | Genset L2 Current Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2060doc 42061 | Genset L3 Current Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2061doc 42062 | Genset Total kW Percent | INT16 | × 0.1 | % | Read | |||
| HR | 2062doc 42063 | Genset Frequency Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2063doc 42064 | Genset L1L2 Voltage% | UINT16 | × 0.1 | % | Read | |||
| HR | 2064doc 42065 | Genset L2L3 Voltage% | UINT16 | × 0.1 | % | Read | |||
| HR | 2065doc 42066 | Genset L3L1 Voltage% | UINT16 | × 0.1 | % | Read | |||
| HR | 2069doc 42070 | Genset Total kW_32bit | INT32 | ABCD | kW | Read | |||
| HR | 2071doc 42072 | Genset Total kVAR_32bit | INT32 | ABCD | kVAR | Read | |||
| HR | 2073doc 42074 | Genset Total kVA_32bit | UINT32 | ABCD | kVA | Read | |||
| HR | 2116doc 42117 | Utility Bus Status | UINT16 | Read | 0 = Unavailable; 1 = Dead; 2 = Live | ||||
| HR | 2117doc 42118 | Utility L1N Voltage | UINT16 | V | Read | ||||
| HR | 2118doc 42119 | Utility L2N Voltage | UINT16 | V | Read | ||||
| HR | 2119doc 42120 | Utility L3N Voltage | UINT16 | V | Read | ||||
| HR | 2120doc 42121 | Utility LN Average Voltage | UINT16 | V | Read | ||||
| HR | 2121doc 42122 | Utility L1L2 Voltage | UINT16 | V | Read | ||||
| HR | 2122doc 42123 | Utility L2L3 Voltage | UINT16 | V | Read | ||||
| HR | 2123doc 42124 | Utility L3L1 Voltage | UINT16 | V | Read | ||||
| HR | 2124doc 42125 | Utility LL Average Voltage | UINT16 | V | Read | ||||
| HR | 2125doc 42126 | Utility L1 Current | UINT16 | A | Read | ||||
| HR | 2126doc 42127 | Utility L2 Current | UINT16 | A | Read | ||||
| HR | 2127doc 42128 | Utility L3 Current | UINT16 | A | Read | ||||
| HR | 2128doc 42129 | Utility Average Current | UINT16 | A | Read | ||||
| HR | 2129doc 42130 | Utility L1 kW | INT16 | kW | Read | ||||
| HR | 2130doc 42131 | Utility L2 kW | INT16 | kW | Read | ||||
| HR | 2131doc 42132 | Utility L3 kW | INT16 | kW | Read | ||||
| HR | 2132doc 42133 | Utility Total kW | INT16 | kW | Read | ||||
| HR | 2133doc 42134 | Utility L1 kVAR | INT16 | kVAR | Read | ||||
| HR | 2134doc 42135 | Utility L2 kVAR | INT16 | kVAR | Read | ||||
| HR | 2135doc 42136 | Utility L3 kVAR | INT16 | kVAR | Read | ||||
| HR | 2136doc 42137 | Utility Total kVAR | INT16 | kVAR | Read | ||||
| HR | 2138doc 42139 | Utility L1 kVA | UINT16 | kVA | Read | ||||
| HR | 2139doc 42140 | Utility L2 kVA | UINT16 | kVA | Read | ||||
| HR | 2140doc 42141 | Utility L3 kVA | UINT16 | kVA | Read | ||||
| HR | 2141doc 42142 | Utility Total kVA | UINT16 | kVA | Read | ||||
| HR | 2142doc 42143 | MB Utility Frequency | UINT16 | Hz | Read | ||||
| HR | 2143doc 42144 | Utility Total Negative kWh | UINT32 | ABCD | kWh | Read | |||
| HR | 2145doc 42146 | Utility Total Positive kWh | UINT32 | ABCD | kWh | Read | |||
| HR | 2147doc 42148 | Utility Total Net kWh | INT32 | ABCD | kWh | Read | |||
| HR | 2149doc 42150 | Utility Total Negative | UINT32 | ABCD | kVARh | Read | |||
| HR | 2151doc 42152 | Utility Total Positive kVARh | UINT32 | ABCD | kVARh | Read | |||
| HR | 2153doc 42154 | Utility Total Net kVARh | INT32 | ABCD | kVARh | Read | |||
| HR | 2155doc 42156 | Utility Total kVAh | UINT32 | ABCD | kVAh | Read | |||
| HR | 2157doc 42158 | System Total kW | INT16 | kW | Read | ||||
| HR | 2158doc 42159 | System Total kVAR | INT16 | kVAR | Read | ||||
| HR | 2159doc 42160 | System Total Power Factor | INT16 | × 0.01 | Read | ||||
| HR | 2160doc 42161 | System Total kVA | UINT16 | kVA | Read | ||||
| HR | 2161doc 42162 | Utility L1 Current Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2162doc 42163 | Utility L2 Current Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2163doc 42164 | Utility L3 Current Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2164doc 42165 | Utility Total kW Percent | INT16 | × 0.1 | % | Read | |||
| HR | 2165doc 42166 | Utility Frequency Percent | UINT16 | × 0.1 | % | Read | |||
| HR | 2166doc 42167 | Utility L1L2 Voltage % | UINT16 | × 0.1 | % | Read | |||
| HR | 2167doc 42168 | Utility L2L3 Voltage % | UINT16 | × 0.1 | % | Read | |||
| HR | 2168doc 42169 | Utility L3L1 Voltage % | UINT16 | × 0.1 | % | Read | |||
| HR | 2169doc 42170 | Utility Total kW _32 bit | INT32 | ABCD | kW | Read | |||
| HR | 2171doc 42172 | Utility total kVAR_32 bit | INT32 | ABCD | kVAR | Read | |||
| HR | 2173doc 42174 | Utility total kVA_32 bit | UINT32 | ABCD | kVA | Read | |||
| HR | 2175doc 42176 | System Total kW_32 bit | INT32 | ABCD | kW | Read | |||
| HR | 2177doc 42178 | System Total kVAR_32 bit | INT32 | ABCD | kVAR | Read | |||
| HR | 2179doc 42180 | System Total kVA_32 bit | UINT32 | ABCD | kVA | Read | |||
| HR | 2199doc 42200 | Total Number of Gensets | UINT16 | Read | |||||
| HR | 2200doc 42201 | Total System Capacity | UINT16 | kW | Read | ||||
| HR | 2201doc 42202 | Total Online Capacity | INT16 | kW | Read | ||||
| HR | 2202doc 42203 | Programmed Transition Timer | UINT16 | × 0.1 | s | Read | |||
| HR | 2203doc 42204 | Transfer Timer | UINT16 | × 0.1 | s | Read | |||
| HR | 2204doc 42205 | Retransfer Timer | UINT16 | × 0.1 | s | Read | |||
| HR | 2205doc 42206 | Maximum Parallel Timer | UINT16 | × 0.1 | s | Read | |||
| HR | 2206doc 42207 | kW Reference | INT16 | kW | Read | ||||
| HR | 2207doc 42208 | Utility Unloaded Status | UINT16 | Read | 0 = Not Available; 1 = Not Unloaded; 2 = Unloaded | ||||
| HR | 2208doc 42209 | Genset Unloaded Status | UINT16 | Read | 0 = Not Available; 1 = Not Unloaded; 2 = Unloaded | ||||
| HR | 2209doc 42210 | System State | UINT16 | Read | 0 = Not Available; 1 = TD Start; 2 = TD Stop; 3 = TD Programmed Transition; 4 = TD Transfer; 5 = TD Retransfer; 6 = Synchronizing; 7 = Sync Check OK; 8 = Inhibit; 9 = Unassigned; 10 = Ramp Unload (printed "Ramp Upload"); 11 = Ramp Load; 12 = Manual; 13 = Utility Failure; 14 = Test; 15 = Standby; 16 = Factory Test; 17 = Extended Parallel | ||||
| HR | 2210doc 42211 | PTC Operating Mode | UINT16 | Read | 0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel | ||||
| HR | 2211doc 42212 | Active Transition Timer | UINT16 | × 0.1 | s | Read | |||
| HR | 2212doc 42213 | Hardware Version | UINT16 | Read | |||||
| HR | 2213doc 42214 | Controller On Time | UINT32 | ABCD | s | Read | |||
| HR | 2215doc 42216 | Genset Availability Status | UINT16 | Read | 0 = Not Available; 1 = Available; 2 = Unknown | ||||
| HR | 2216doc 42217 | Utility Availability Status | UINT16 | Read | 0 = Not Available; 1 = Available; 2 = Unknown | ||||
| HR | 2217doc 42218 | Gen CB Position Status | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2218doc 42219 | Util CB Position Status | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2219doc 42220 | kVAR Load Reference | INT16 | kVAR | Read | ||||
| HR | 2220doc 42221 | kVAR Load Setpoint Engr Units Display Value | UINT16 | × 0.01 | % | Read | |||
| HR | 2221doc 42222 | kW Load Setpoint Engr Units Display Value | INT16 | × 0.01 | % | Read | |||
| HR | 2222doc 42223 | Power Factor Setpoint | INT16 | × 0.01 | Read | ||||
| HR | 2223doc 42224 | PTC State | UINT16 | Read | 0 = Not Enabled; 1 = No Source Connected; 2 = Utility Connected; 3 = Genset Connected; 4 = Paralleled | ||||
| HR | 2224doc 42225 | Sync Check Close Allowed | UINT16 | Read | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 2225doc 42226 | Sync Phase Difference | INT16 | × 0.01 | ° | Read | |||
| HR | 2226doc 42227 | Synchronizer Status | UINT16 | Read | 0 = Synchronizer Off; 1 = Synchronizer On | ||||
| HR | 2227doc 42228 | System Lockout Status | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 2228doc 42229 | Breaker 1 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2229doc 42230 | Breaker 2 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2230doc 42231 | Breaker 3 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2231doc 42232 | Breaker 4 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2232doc 42233 | Breaker 5 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2233doc 42234 | Breaker 6 Position | UINT16 | Read | 0 = Open; 1 = Closed; 2 = Not Available | ||||
| HR | 2234doc 42235 | Breaker 1 Trip Status | UINT16 | Read | 0 = Not Available; 1 = Normal; 2 = Tripped | ||||
| HR | 2235doc 42236 | Breaker 2 Trip Status | UINT16 | Read | 0 = Not Available; 1 = Normal; 2 = Tripped | ||||
| HR | 2245doc 42246 | Position | UINT16 | Read | 0 = Not Available; 1 = No Source Connected; 2 = Source 1 Connected; 3 = Source 2 Connected; 4 = Paralleled | ||||
| HR | 2246doc 42247 | SID1 Status | UINT16 | Read | 0 = Missing; 1 = Good; 2 = Connecting; 3 = No EXP Board; 4 = Not Applicable | ||||
| HR | 2247doc 42248 | SID0 Status | UINT16 | Read | 0 = Missing; 1 = Good; 2 = Connecting; 3 = No EXP Board; 4 = Not Applicable | ||||
| HR | 2248doc 42249 | Expansion Board Communications | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| HR | 2249doc 42250 | Current Add Level | UINT16 | Read | |||||
| HR | 2250doc 42251 | Current Shed Level | UINT16 | Read | |||||
| HR | 2251doc 42252 | Add Level 1 Command | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | ||||
| HR | 2252doc 42253 | Add Level 2 Command | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | ||||
| HR | 2253doc 42254 | Add Level 3 Command | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | ||||
| HR | 2254doc 42255 | Add Level 4 Command | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | ||||
| HR | 2255doc 42256 | Add Level 5 Command | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | ||||
| HR | 2286doc 42287 | Shed Load 3 Command | Values printed as Do Nothing / Add Level in the manual. | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | |||
| HR | 2287doc 42288 | Shed Load 4 Command | Values printed as Do Nothing / Add Level in the manual. | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | |||
| HR | 2288doc 42289 | Shed Load 5 Command | Values printed as Do Nothing / Add Level in the manual. | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | |||
| HR | 2289doc 42290 | Shed Load 6 Command | Values printed as Do Nothing / Add Level in the manual. | UINT16 | Read | 0 = Do Nothing; 1 = Add Level | |||
| HR | 2290doc 42291 | Battery Voltage Engr Units Display Value | UINT16 | × 0.01 | V | Read | |||
| HR | 2291doc 42292 | kVAR Master Load Control Output Predictor Value | INT16 | × 0.01 | V | Read | |||
| HR | 2292doc 42293 | kW Master Load Control Output Predictor Value | INT16 | × 0.01 | V | Read | |||
| HR | 2293doc 42294 | Master Frequency Bias Output Predictor Value | INT16 | × 0.01 | V | Read | |||
| HR | 2294doc 42295 | Master Voltage Bias Output Predictor Value | INT16 | × 0.01 | V | Read | |||
| HR | 2295doc 42296 | PTC Genset Operating Mode | UINT16 | Read | 0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel | ||||
| HR | 2296doc 42297 | PTC Transfer Pair Operating Mode | UINT16 | Read | 0 = Manual; 1 = Normal; 2 = Normal Override; 3 = Test; 4 = Utility Fail; 5 = Extended Parallel | ||||
| HR | 2297doc 42298 | PTC Operating Transition Type | UINT16 | Read | 0 = Open Transition; 1 = Hard Closed Transition; 2 = Soft Closed Transition | ||||
| HR | 2298doc 42299 | Expansion Board Communications 1 | UINT16 | Read | 0 = Disabled; 1 = Enabled | ||||
| HR | 2299doc 42300 | System Topology | UINT16 | Read/write | 0 = Master Synchronize Only; 1 = Isolated Bus w/ out GM; 2 = Isolated Bus w/GM; 3 = Common Bus; 4 = Transfer Pair; 5 = Component Mode | ||||
| HR | 2300doc 42301 | Transition Type | UINT16 | Read/write | 0 = Open Transition; 1 = Hard Closed Transition; 2 = Soft Closed Transition | ||||
| HR | 2301doc 42302 | Extended Parallel Enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 2302doc 42303 | Load Demand Type | UINT16 | Read/write | 0 = None; 1 = Fixed Sequence; 2 = Run Hours | ||||
| HR | 2303doc 42304 | Priority Control Method | UINT16 | Read/write | 0 = Manual; 1 = Automatic | ||||
| HR | 2304doc 42305 | Genset 01 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2305doc 42306 | Genset 02 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2306doc 42307 | Genset 03 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2307doc 42308 | Genset 04 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2308doc 42309 | Genset 05 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2309doc 42310 | Genset 06 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2310doc 42311 | Genset 07 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2311doc 42312 | Genset 08 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2312doc 42313 | Genset 09 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2313doc 42314 | Genset 10 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2314doc 42315 | Genset 11 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2315doc 42316 | Genset 12 kW Rating | INT16 | kW | Read/write | ||||
| HR | 2316doc 42317 | Programmed Transition Delay (TDPT) | UINT16 | × 0.1 | s | Read/write | |||
| HR | 2317doc 42318 | Transfer Delay (TDNE) | UINT16 | × 0.1 | s | Read/write | |||
| HR | 2318doc 42319 | Retransfer Delay (TDEN) | UINT16 | × 0.1 | s | Read/write | |||
| HR | 2319doc 42320 | Maximum Parallel Time (TDMP) | UINT16 | × 0.1 | s | Read/write | |||
| HR | 2320doc 42321 | Genset Bus %kW Setpoint | INT16 | × 0.01 | % | Read/write | |||
| HR | 2321doc 42322 | Genset Nominal Voltage | UINT16 | V | Read/write | ||||
| HR | 2322doc 42323 | Utility Nominal Voltage | UINT16 | V | Read/write | ||||
| HR | 2323doc 42324 | Genset Center Frequency | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 2324doc 42325 | Utility Center Frequency | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 2325doc 42326 | test With Load Enable | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 2326doc 42327 | System Frequency | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 2327doc 42328 | Genset Bus kW Setpoint Source | UINT16 | Read/write | 0 = Internal; 1 = Analog Input | ||||
| HR | 2328doc 42329 | Genset Bus kVAR Setpoint Source | UINT16 | Read/write | 0 = Internal; 1 = Analog Input | ||||
| HR | 2329doc 42330 | Genset Bus kW Setpoint | INT16 | kW | Read/write | ||||
| HR | 2330doc 42331 | Genset Bus kVAR Setpoint | INT16 | kVAR | Read/write | ||||
| HR | 2331doc 42332 | Genset Bus % kVAR Setpoint | INT16 | × 0.01 | % | Read/write | |||
| HR | 2332doc 42333 | Genset Bus Power Factor Setpoint | INT16 | × 0.01 | Read/write | ||||
| HR | 2333doc 42334 | Genset Unloaded Level | INT16 | kW | Read/write | ||||
| HR | 2599doc 42600 | Extended Parallel Start Vol | UINT16 | Read/write | 0 = Stop; 1 = Start | ||||
| HR | 2600doc 42601 | Synchronizer Enable Vol | UINT16 | Read/write | 0 = Inactive; 1 = Active | ||||
| HR | 2601doc 42602 | Utility Source Fail Vol | UINT16 | Read/write | 0 = Inactive; 1 = Active | ||||
| HR | 2602doc 42603 | Transfer Inhibit Vol | UINT16 | Read/write | 0 = No Inhibit; 1 = Inhibit | ||||
| HR | 2603doc 42604 | Retransfer Inhibit Vol | UINT16 | Read/write | 0 = No Inhibit; 1 = Inhibit | ||||
| HR | 2697doc 42698 | Load Add Shed Enable Status | UINT16 | Read | 0 = Disabled; 1 = Enabled; 2 = Paused | ||||
| HR | 2698doc 42699 | PCCNet Status | UINT16 | Read | 0 = No Connection; 1 = Connected; 2 = Connecting | ||||
| HR | 2699doc 42700 | Gen1 Availability State | UINT16 | Read | 0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed | ||||
| HR | 2700doc 42701 | Gen2 Availability State | UINT16 | Read | 0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed | ||||
| HR | 2701doc 42702 | Gen3 Availability State | UINT16 | Read | 0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed | ||||
| HR | 2702doc 42703 | Gen4 Availability State | UINT16 | Read | 0 = Gen Does Not Exist; 1 = Offline; 2 = Waiting For Gen; 3 = Online; 4 = Failed | ||||
| HR | 2703doc 42704 | Gen1 Online Time | UINT32 | ABCD | × 0.0002777778 | h | Read | ||
| HR | 2711doc 42712 | GenA | UINT16 | Read | 0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16 | ||||
| HR | 2715doc 42716 | Load Demand State | UINT16 | Read | 0 = Off; 1 = Initial Delay Timing; 2 = Load Monitor | ||||
| HR | 2716doc 42717 | Total Number of Gensets Online | UINT16 | Read | |||||
| HR | 2717doc 42718 | Total Spare Online Capacity | INT16 | kW | Read | ||||
| HR | 2718doc 42719 | Next Gen Shutdown Threshold | INT16 | kW | Read | ||||
| HR | 2719doc 42720 | Next Gen Shutdown Threshold | INT16 | kW | Read | ||||
| HR | 2720doc 42721 | Next Gen Restart | UINT16 | Read | 0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16 | ||||
| HR | 2721doc 42722 | Next Gen Shutdown | UINT16 | Read | 0 = Gen1; 1 = Gen2; 2 = Gen3; 3 = Gen4; 4 = Gen5; 5 = Gen6; 6 = Gen7; 7 = Gen8; 8 = Gen9; 9 = Gen10; 10 = Gen11; 11 = Gen12; 12 = Gen13; 13 = Gen14; 14 = Gen15; 15 = Gen16 | ||||
| HR | 2722doc 42723 | Load Demand Gen1 Driver Status | UINT16 | Read | 0 = Run; 1 = Load Demand Stop | ||||
| HR | 2723doc 42724 | Load Demand Gen2 Driver Status | UINT16 | Read | 0 = Run; 1 = Load Demand Stop | ||||
| HR | 2724doc 42725 | Load Demand Gen3 Driver Status | UINT16 | Read | 0 = Run; 1 = Load Demand Stop | ||||
| HR | 2725doc 42726 | Load Demand Gen4 Driver Status | UINT16 | Read | 0 = Run; 1 = Load Demand Stop | ||||
| HR | 2726doc 42727 | Genset Bus kW Overload Status | INT16 | kW | Read | ||||
| HR | 2727doc 42728 | Genset Bus kW Overload Status | UINT16 | Read | 0 = No Overload; 1 = Overload | ||||
| HR | 2728doc 42729 | Genset Bus Underfrequency Overload Status | UINT16 | Read | 0 = No Overload; 1 = Overload | ||||
| HR | 2729doc 42730 | Active Schedule | UINT16 | Read | 0 = None; 1 = Program 1; 2 = Program 2; 3 = Program 3; 4 = Program 4; 5 = Program 5; 6 = Program 6; 7 = Program 7; 8 = Program 8; 9 = Program 9; 10 = Program 10; 11 = Program 11; 12 = Program 12; 13 = Exception 1; 14 = Exception 2; 15 = Exception 3; 16 = Exception 4; 17 = Exception 5; 18 = Exception 6 | ||||
| HR | 2730doc 42731 | Scheduler Run Command | UINT16 | Read | 0 = Off; 1 = No Load; 2 = With Load; 3 = Extended Parallel | ||||
| HR | 2731doc 42732 | Modbus Bus Message Count | UINT16 | Read |
Notes on this map
- Cummins does not host this document publicly; the link is a copy on an integrator's site (Control Concepts). A dealer site lists a newer Issue 26 (2020) that could not be downloaded here.
- Section 10 states that a 32-bit value at register X holds the upper 16 bits and X+1 the lower 16 bits, so 32-bit values are ABCD. A 32-bit value must be written with function 16; function 06 returns illegal address.
- Types, multipliers and units follow the table's Multiplier/Size/Sign/Unit columns, including inconsistencies such as utility frequency 42143 printed with multiplier 1 while genset frequency 42043 uses 0.1.
- Left out: 42001/42002 (logical-access helpers), 40052 (printed inside the 420xx block, apparently a misprint for 42052), power factors 42038/42138 (multiplier 1, no unit), 42056 (named kVAh but unit kVARh), the 32-bit fault/event bitmaps 42500-42507, the gen 2-4 online times (sign not given) and the remaining setting blocks above 42334.
- Registers in a multi-register read that are not defined return 0xFF; a single read of an undefined register returns exception 02.
- Up to 40 contiguous registers per read or write. The module answers within 100 ms and is ready about 10 s after power-up.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Cummins MCM3320 master control module (Modbus RTU)
What Modbus registers does the Cummins MCM3320 master control module (Modbus RTU) have?
This map lists 224 registers: 224 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Cummins MCM3320 master control module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as Modicon 4xxxx holding-register numbers; 42018 is wire address 2017.
What byte order does the Cummins MCM3320 master control module (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Cummins MCM3320 master control module (Modbus RTU)?
Start with HR 2209 System State (System state); HR 2223 PTC State (PTC state); HR 2217 Gen CB Position Status (Genset breaker position); HR 2218 Util CB Position Status (Utility breaker position); HR 2032 Genset Total kW (Genset total kW); HR 2132 Utility Total kW (Utility total kW); HR 2011 Current Fault Status (Active fault).
How do I enable Modbus control of the Cummins MCM3320 master control module (Modbus RTU)?
Modbus RTU is on the RS-485 port; defaults are node 1, 19200 baud, 8 data bits, even parity, 1 stop bit, changeable through MON and PCCnet logicals.
Where is the official Cummins MCM3320 master control module (Modbus RTU) Modbus documentation?
The source is Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) (A029X159 Issue 7), revision 2012-04. Cummins doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/modbus2300.pdf. It may be an older revision, so check it against the live unit.
More Cummins Modbus register maps
- Generator controller
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Cummins PCC 1301 and PowerCommand 1.1/1.2 generator set controls on their RS-485 Modbus RTU port, per section 1 of A029X159 Issue 7.
Also known as: PCC 1301, PCC1301, PowerCommand 1.1, PowerCommand 1.2, PC1.1, PC1.2 - Generator controller
Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)
Cummins PowerCommand 2.x and 3.x generator set controls (PC 2.2, 2.3, 3.3), per section 2 of A029X159 Issue 7; registers marked PC 3.x only are absent on PC 2.x.
Also known as: PowerCommand 2.2, PowerCommand 2.3, PowerCommand 3.3, PC2.2, PC2.3, PC3.3
Other generator controllers register maps
- Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Woodward easYgen-1000 Series genset controller (Modbus RTU)
easYgen-1000 series software version 2.1xxx, transmission telegram protocol 4003, per interface manual 37393B.
Also known as: easYgen-1000, easYgen1000, easYgen-1000 Series - Generator controller
ComAp InteliGen4 200
InteliGen4 200 with firmware 2.2.0: the fixed (reserved) registers only; measurement registers depend on the configuration.
Also known as: InteliGen 4 200, IG4 200