Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The easYgen-1000 is Woodward's genset controller for single units and AMF duty. On RS-485 it is a Modbus RTU slave: the visualization telegram (protocol 4003) is block-read from Modicon 450001, and control word 1 at parameter 503 starts, stops and acknowledges the set. This map covers generator and mains voltages, currents and frequency, energy and hours counters, status and alarm words, a few J1939 engine values and the remote-control word.
This page lists 49 Modbus registers for the Woodward easYgen-1000 Series genset controller (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.
- Manufacturer
- Woodward
- Model
- easYgen-1000 Series genset controller (Modbus RTU)
- Equipment type
- Generator controller
- Registers
- 49 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 2.1xxx
- Also known as
- easYgen-1000, easYgen1000, easYgen-1000 Series
Integration notes: Woodward easYgen-1000 Series genset controller (Modbus RTU)
Block-read up to 128 holding registers from wire address 50000 (Modicon 450001) for measurements, status and alarms. To start or stop the set, write 0 and then the start (bit 0) or stop (bit 1) bit to parameter 503; acknowledge with two rising edges of bit 4.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 50000 | Protocol number | UINT16 | Protocol number (4003) to confirm the map | Read |
| HR 50001 | Generator voltage L1-L2 | UINT32 ABCD | Generator voltage L1-L2 | Read |
| HR 50003 | Generator frequency | UINT16 | Generator frequency | Read |
| HR 50037 | Generator current L1 | UINT32 ABCD | Generator current L1 | Read |
| HR 50033 | System state (operating mode) | BITMAP16 | Operating mode STOP/MANUAL/AUTO | Read |
| HR 50057 | System state | BITMAP16 | System state | Read |
| HR 50036 | Alarm class | BITMAP16 | Active alarm classes | Read |
| HR 503 | Control word 1 | BITMAP16 | Remote start / stop / acknowledge | Read/write |
Enable Modbus control & writes
Select the Modbus protocol on the serial interface and set the Modbus slave ID (0-255) and reply delay (0-1000 ms) in the controller. For remote start/stop the LogicsManager must use command variable 04.13; see application manual 37394. Parameter writes need the code level 2 password for that interface (parameter 10401 for serial interface 1).
Communication loss & watchdog
Interface watchdogs exist but are disabled by default; they are described in the device manual, not in this document.
Byte order & addressing
- Start, stop and acknowledge react only to a rising edge: write 0 first, then the bit.
- Acknowledge must be sent twice: the first edge silences the horn, the second clears faults that are gone.
- Some PLCs and tools offset addresses by one; the manual notes 450001 may become bus address 50000.
Network setup
- RS-485 half or full duplex is supported. Set the baud rate, parity and stop bits in the controller's serial interface menu to match the master.
Watch out for
- Writing control word 1 can start or stop the engine; make sure the site is safe first.
- Bits 2 and 3 of control word 1 must always be 0.
Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 503doc 503 (40504) | Control word 1 | Remote start / stop / acknowledge; act on a 0-to-1 transition. | BITMAP16 | Read/write | bit 0 = Remote start (rising edge); bit 1 = Remote stop (rising edge); bit 2 = Must be 0; bit 3 = Must be 0; bit 4 = Remote acknowledge (rising edge, send twice) | |||
| HR | 50000doc No. 1 (450001) | Protocol number | Reads 4003 for the easYgen-1000 series. | UINT16 | Read | ||||
| HR | 50001doc No. 2 (450002) | Generator voltage L1-L2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50003doc No. 4 (450004) | Generator frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 50004doc No. 5 (450005) | Generator voltage L1-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50006doc No. 7 (450007) | Mains frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 50007doc No. 8 (450008) | Generator voltage L2-L3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50010doc No. 11 (450011) | Generator voltage L2-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50013doc No. 14 (450014) | Generator voltage L3-L1 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50015doc No. 16 (450016) | Engine speed (pickup) | UINT16 | rpm | Read | ||||
| HR | 50016doc No. 17 (450017) | Generator voltage L3-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50018doc No. 19 (450019) | Battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 50019doc No. 20 (450020) | Mains voltage L1-L2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50022doc No. 23 (450023) | Mains voltage L1-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50025doc No. 26 (450026) | Mains voltage L2-L3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50027doc No. 28 (450028) | Discrete input state | Physical input state; NO/NC setting is ignored. | BITMAP16 | Read | bit 8 = Discrete input D8; bit 9 = Discrete input D7; bit 10 = Discrete input D6; bit 11 = Discrete input D5; bit 12 = Discrete input D4; bit 13 = Discrete input D3; bit 14 = Discrete input D2; bit 15 = Discrete input D1 | |||
| HR | 50028doc No. 29 (450029) | Mains voltage L2-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50030doc No. 31 (450031) | Relay state | BITMAP16 | Read | bit 5 = Relay R11; bit 6 = Relay R10; bit 7 = Relay R9; bit 8 = Relay R8; bit 9 = Relay R7; bit 10 = Relay R6; bit 11 = Relay R5; bit 12 = Relay R4; bit 13 = Relay R3; bit 14 = Relay R2; bit 15 = Relay R1 | ||||
| HR | 50031doc No. 32 (450032) | Mains voltage L3-L1 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50033doc No. 34 (450034) | System state (operating mode) | BITMAP16 | Read | bit 6 = Operating mode AUTOMATIC; bit 7 = Operating mode MANUAL; bit 8 = Operating mode STOP | ||||
| HR | 50034doc No. 35 (450035) | Mains voltage L3-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50036doc No. 37 (450037) | Alarm class | BITMAP16 | Read | bit 0 = Alarm class A; bit 1 = Alarm class B; bit 2 = Alarm class C; bit 3 = Alarm class D; bit 4 = Alarm class E; bit 5 = Alarm class F | ||||
| HR | 50037doc No. 38 (450038) | Generator current L1 | UINT32 | ABCD | mA | Read | |||
| HR | 50039doc No. 40 (450040) | Discrete inputs with alarm class | Bit set when the input is configured as an alarm input and active. | BITMAP16 | Read | bit 8 = Discrete input D8; bit 9 = Discrete input D7; bit 10 = Discrete input D6; bit 11 = Discrete input D5; bit 12 = Discrete input D4; bit 13 = Discrete input D3; bit 14 = Discrete input D2; bit 15 = Discrete input D1 | |||
| HR | 50040doc No. 41 (450041) | Generator current L2 | UINT32 | ABCD | mA | Read | |||
| HR | 50042doc No. 43 (450043) | Alarms 1 | BITMAP16 | Read | bit 1 = Maintenance hours expired; bit 2 = Maintenance days expired; bit 3 = Start failure; bit 5 = MCB open failure; bit 6 = MCB close failure; bit 7 = GCB open failure; bit 8 = GCB close failure; bit 9 = Stop failure; bit 10 = Speed detection alarm; bit 11 = Unintended stop; bit 12 = Underspeed limit 2; bit 13 = Underspeed limit 1; bit 14 = Overspeed limit 2; bit 15 = Overspeed limit 1 | ||||
| HR | 50043doc No. 44 (450044) | Generator current L3 | UINT32 | ABCD | mA | Read | |||
| HR | 50045doc No. 46 (450046) | Generator alarms 1 | BITMAP16 | Read | bit 1 = Overload limit 2; bit 2 = Overload limit 1; bit 3 = Reverse/reduced power limit 2; bit 4 = Reverse/reduced power limit 1; bit 5 = Overcurrent limit 3; bit 6 = Overcurrent limit 2; bit 7 = Overcurrent limit 1; bit 8 = Undervoltage limit 2; bit 9 = Undervoltage limit 1; bit 10 = Overvoltage limit 2; bit 11 = Overvoltage limit 1; bit 12 = Underfrequency limit 2; bit 13 = Underfrequency limit 1; bit 14 = Overfrequency limit 2; bit 15 = Overfrequency limit 1 | ||||
| HR | 50046doc No. 47 (450047) | Mains current L1 | UINT32 | ABCD | mA | Read | |||
| HR | 50048doc No. 49 (450049) | Mains alarms | BITMAP16 | Read | bit 0 = Mains load limit 2 (LogicsManager); bit 1 = Mains load limit 1 (LogicsManager); bit 2 = Mains phase rotation wrong; bit 3 = Mains undervoltage (emergency power); bit 4 = Mains overvoltage (emergency power); bit 5 = Mains underfrequency (emergency power); bit 6 = Mains overfrequency (emergency power) | ||||
| HR | 50051doc No. 52 (450052) | Analog input wire break | BITMAP16 | Read | bit 1 = Wire break analog input T1; bit 2 = Wire break analog input T2 | ||||
| HR | 50054doc No. 55 (450055) | Analog inputs and battery monitoring | BITMAP16 | Read | bit 0 = Battery undervoltage limit 1; bit 1 = Battery overvoltage limit 1; bit 2 = Battery undervoltage limit 2; bit 3 = Battery overvoltage limit 2; bit 4 = Analog input T1 limit 1; bit 5 = Analog input T1 limit 2; bit 6 = Analog input T2 limit 1; bit 7 = Analog input T2 limit 2 | ||||
| HR | 50057doc No. 58 (450058) | System state | BITMAP16 | Read | bit 0 = Critical mode (sprinkler) operation; bit 1 = Emergency power operation (AMF); bit 2 = Pre-run auxiliary services; bit 3 = Mains settling; bit 4 = Post-run auxiliary services; bit 5 = Emergency power (AMF) / critical mode; bit 6 = Crank protection; bit 7 = Preglow (diesel); bit 8 = Engine will be stopped; bit 9 = Engine post-run; bit 10 = Start pause; bit 11 = Starter / fuel solenoid (diesel) or gas valve (gas); bit 12 = Dead bus start MCB; bit 13 = Dead bus start GCB; bit 14 = Ignition on (gas engine); bit 15 = Turning (gas engine) | ||||
| HR | 50066doc No. 67 (450067) | Generator alarms 2 | BITMAP16 | Read | bit 7 = Inverse-time overcurrent; bit 8 = Generator load limit 2; bit 9 = Generator load limit 1; bit 10 = Generator phase rotation wrong; bit 11 = Ground fault limit 2; bit 12 = Ground fault limit 1; bit 13 = Voltage asymmetry; bit 14 = Load imbalance limit 2; bit 15 = Load imbalance limit 1 | ||||
| HR | 50067doc No. 68 (450068) | Real energy | UINT32 | ABCD | × 0.01 | MWh | Read | ||
| HR | 50069doc No. 70 (450070) | LogicsManager flags | BITMAP16 | Read | bit 8 = Flag 8 true; bit 9 = Flag 7 true; bit 10 = Flag 6 true; bit 11 = Flag 5 true; bit 12 = Flag 4 true; bit 13 = Flag 3 true; bit 14 = Flag 2 true; bit 15 = Flag 1 true | ||||
| HR | 50070doc No. 71 (450071) | Reactive energy | UINT32 | ABCD | × 0.01 | Mvarh | Read | ||
| HR | 50073doc No. 74 (450074) | Generator ground current | UINT32 | ABCD | mA | Read | |||
| HR | 50075doc No. 76 (450076) | External discrete inputs with alarm class | BITMAP16 | Read | bit 0 = External input DEx01; bit 1 = External input DEx02; bit 2 = External input DEx03; bit 3 = External input DEx04; bit 4 = External input DEx05; bit 5 = External input DEx06; bit 6 = External input DEx07; bit 7 = External input DEx08; bit 8 = External input DEx09; bit 9 = External input DEx10; bit 10 = External input DEx11; bit 11 = External input DEx12; bit 12 = External input DEx13; bit 13 = External input DEx14; bit 14 = External input DEx15; bit 15 = External input DEx16 | ||||
| HR | 50078doc No. 79 (450079) | External relay outputs | BITMAP16 | Read | bit 0 = External relay REx01; bit 1 = External relay REx02; bit 2 = External relay REx03; bit 3 = External relay REx04; bit 4 = External relay REx05; bit 5 = External relay REx06; bit 6 = External relay REx07; bit 7 = External relay REx08; bit 8 = External relay REx09; bit 9 = External relay REx10; bit 10 = External relay REx11; bit 11 = External relay REx12; bit 12 = External relay REx13; bit 13 = External relay REx14; bit 14 = External relay REx15; bit 15 = External relay REx16 | ||||
| HR | 50079doc No. 80 (450080) | External discrete inputs | BITMAP16 | Read | bit 0 = External input DEx01; bit 1 = External input DEx02; bit 2 = External input DEx03; bit 3 = External input DEx04; bit 4 = External input DEx05; bit 5 = External input DEx06; bit 6 = External input DEx07; bit 7 = External input DEx08; bit 8 = External input DEx09; bit 9 = External input DEx10; bit 10 = External input DEx11; bit 11 = External input DEx12; bit 12 = External input DEx13; bit 13 = External input DEx14; bit 14 = External input DEx15; bit 15 = External input DEx16 | ||||
| HR | 50111doc No. 112 (450112) | J1939 engine speed (SPN 190) | From the engine ECU over J1939. | UINT32 | ABCD | × 0.1 | rpm | Read | |
| HR | 50114doc No. 115 (450115) | J1939 total engine hours (SPN 247) | From the engine ECU over J1939. | UINT32 | ABCD | h | Read | ||
| HR | 50119doc No. 120 (450120) | J1939 engine oil pressure (SPN 100) | From the engine ECU over J1939. | UINT16 | kPa | Read | |||
| HR | 50169doc No. 170 (450170) | Hours of operation | UINT32 | ABCD | h | Read | |||
| HR | 50172doc No. 173 (450173) | ECU lamp alarms (Alarm 2) | BITMAP16 | Read | bit 0 = Amber warning lamp from ECU (J1939); bit 1 = Red stop lamp from ECU (J1939) | ||||
| HR | 50173doc No. 174 (450174) | Number of starts | UINT16 | Read | |||||
| HR | 50177doc No. 178 (450178) | Hours of operation (1/100 h) | UINT32 | ABCD | × 0.01 | h | Read | ||
| HR | 50180doc No. 181 (450181) | Free adjustable hours counter | UINT32 | ABCD | × 0.01 | h | Read |
Notes on this map
- 32-bit values are listed as a High word row followed by a Low word row, so the high word sits at the lower address (ABCD).
- The telegram prints units and resolution but no signed/unsigned type. Voltages, currents, frequency, energy and hours cannot be negative, so the unsigned type here reads them correctly either way.
- Left out: generator and mains real power, reactive power and power factor (words 10, 13, 50, 53, 56, 59, 61-65), because the telegram does not say whether they are signed and they can go negative; analog inputs T1/T2 (no scaling given); hours/days until maintenance; the system state bits 0-5 of word 34, whose labels sit between two bit rows; diagnostic (DM1/DM2) SPN/FMT words and most J1939 engine values.
- Words 112-168 come from an engine ECU over J1939 and only hold data when one is connected and configured.
- Parameters (configuration range 40001-450000) are read or written one at a time with a length that matches the parameter data type; the full parameter list is in configuration manual 37391, not this document.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Woodward easYgen-1000 Series genset controller (Modbus RTU)
What Modbus registers does the Woodward easYgen-1000 Series genset controller (Modbus RTU) have?
This map lists 49 registers: 49 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses Modicon numbers. Telegram word No. n is Modicon 450000 + n; the manual says 450001 may become bus address 50000, so word n is wire address 49999 + n. Parameters use Modicon 40000 + (parameter ID + 1), so control word 1 (parameter 503) is 40504 = wire address 503.
What byte order does the Woodward easYgen-1000 Series genset controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Woodward easYgen-1000 Series genset controller (Modbus RTU)?
Start with HR 50000 Protocol number (Protocol number (4003) to confirm the map); HR 50001 Generator voltage L1-L2 (Generator voltage L1-L2); HR 50003 Generator frequency (Generator frequency); HR 50037 Generator current L1 (Generator current L1); HR 50033 System state (operating mode) (Operating mode STOP/MANUAL/AUTO); HR 50057 System state (System state); HR 50036 Alarm class (Active alarm classes); HR 503 Control word 1 (Remote start / stop / acknowledge).
How do I enable Modbus control of the Woodward easYgen-1000 Series genset controller (Modbus RTU)?
Select the Modbus protocol on the serial interface and set the Modbus slave ID (0-255) and reply delay (0-1000 ms) in the controller. For remote start/stop the LogicsManager must use command variable 04.13; see application manual 37394. Parameter writes need the code level 2 password for that interface (parameter 10401 for serial interface 1).
What happens when the Woodward easYgen-1000 Series genset controller (Modbus RTU) loses Modbus communication?
Interface watchdogs exist but are disabled by default; they are described in the device manual, not in this document.
Where is the official Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus documentation?
The source is easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx (37393B), revision 2008-07-02, published free by Woodward at https://www.woodward.com/products/publication-asset/37393.
More Woodward Modbus register maps
- Generator controller (synchronizer and load sharing control)
Woodward DSLC-2 Digital Synchronizer and Load Control
DSLC-2, data protocol 5200, per manual 37443J.
Also known as: DSLC2, DSLC-2 synchronizer - Generator controller
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
easYgen-2200/2300/2500, data protocol 5100 (basic visualization), per manual 37535D.
Also known as: easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series - Generator controller
Woodward easYgen-3000XT Series
easYgen-3100XT-P1 / 3200XT-P1 / 3200XT-P1-LT, release 2.17-0, default Modbus data protocol 5010 (Basic Visualization).
Also known as: easYgen-3100XT-P1, easYgen-3200XT-P1, easYgen-3200XT-P1-LT, easYgen-3100XT, easYgen-3200XT - Generator controller (utility-tie master synchronizer)
Woodward MSLC-2 Master Synchronizer and Load Control
MSLC-2, data protocol 5200, per manual 37444G.
Also known as: MSLC2, MSLC-2 master synchronizer
Other generator controllers register maps
- Generator controller
ComAp InteliGen4 200
InteliGen4 200 with firmware 2.2.0: the fixed (reserved) registers only; measurement registers depend on the configuration.
Also known as: InteliGen 4 200, IG4 200 - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Transfer switch
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
ATL800 and ATL900 ATS controllers (document I463 GB I 11 21); LINE3, BRK3 and TB2 items are ATL900 only.
Also known as: ATL800, ATL900, ATL 800, ATL 900 - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Transfer switch controller
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.
Also known as: M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82
All generator controllers Modbus register maps →
Source: easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx · 37393B · rev. 2008-07-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.