Generator controller · Modbus register map

Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The easYgen-1000 is Woodward's genset controller for single units and AMF duty. On RS-485 it is a Modbus RTU slave: the visualization telegram (protocol 4003) is block-read from Modicon 450001, and control word 1 at parameter 503 starts, stops and acknowledges the set. This map covers generator and mains voltages, currents and frequency, energy and hours counters, status and alarm words, a few J1939 engine values and the remote-control word.

This page lists 49 Modbus registers for the Woodward easYgen-1000 Series genset controller (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.

Manufacturer
Woodward
Model
easYgen-1000 Series genset controller (Modbus RTU)
Equipment type
Generator controller
Registers
49 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
2.1xxx
Also known as
easYgen-1000, easYgen1000, easYgen-1000 Series
Source document
easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx · 37393B · rev. 2008-07-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Woodward easYgen-1000 Series genset controller (Modbus RTU)

Integration in brief

Block-read up to 128 holding registers from wire address 50000 (Modicon 450001) for measurements, status and alarms. To start or stop the set, write 0 and then the start (bit 0) or stop (bit 1) bit to parameter 503; acknowledge with two rising edges of bit 4.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 50000Protocol numberUINT16Protocol number (4003) to confirm the mapRead
HR 50001Generator voltage L1-L2UINT32 ABCDGenerator voltage L1-L2Read
HR 50003Generator frequencyUINT16Generator frequencyRead
HR 50037Generator current L1UINT32 ABCDGenerator current L1Read
HR 50033System state (operating mode)BITMAP16Operating mode STOP/MANUAL/AUTORead
HR 50057System stateBITMAP16System stateRead
HR 50036Alarm classBITMAP16Active alarm classesRead
HR 503Control word 1BITMAP16Remote start / stop / acknowledgeRead/write

Enable Modbus control & writes

Select the Modbus protocol on the serial interface and set the Modbus slave ID (0-255) and reply delay (0-1000 ms) in the controller. For remote start/stop the LogicsManager must use command variable 04.13; see application manual 37394. Parameter writes need the code level 2 password for that interface (parameter 10401 for serial interface 1).

Communication loss & watchdog

Interface watchdogs exist but are disabled by default; they are described in the device manual, not in this document.

Byte order & addressing

Network setup

Watch out for

Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR503doc 503 (40504)Control word 1Remote start / stop / acknowledge; act on a 0-to-1 transition.BITMAP16Read/writebit 0 = Remote start (rising edge); bit 1 = Remote stop (rising edge); bit 2 = Must be 0; bit 3 = Must be 0; bit 4 = Remote acknowledge (rising edge, send twice)
HR50000doc No. 1 (450001)Protocol numberReads 4003 for the easYgen-1000 series.UINT16Read
HR50001doc No. 2 (450002)Generator voltage L1-L2UINT32ABCD× 0.1VRead
HR50003doc No. 4 (450004)Generator frequencyUINT16× 0.01HzRead
HR50004doc No. 5 (450005)Generator voltage L1-NUINT32ABCD× 0.1VRead
HR50006doc No. 7 (450007)Mains frequencyUINT16× 0.01HzRead
HR50007doc No. 8 (450008)Generator voltage L2-L3UINT32ABCD× 0.1VRead
HR50010doc No. 11 (450011)Generator voltage L2-NUINT32ABCD× 0.1VRead
HR50013doc No. 14 (450014)Generator voltage L3-L1UINT32ABCD× 0.1VRead
HR50015doc No. 16 (450016)Engine speed (pickup)UINT16rpmRead
HR50016doc No. 17 (450017)Generator voltage L3-NUINT32ABCD× 0.1VRead
HR50018doc No. 19 (450019)Battery voltageUINT16× 0.1VRead
HR50019doc No. 20 (450020)Mains voltage L1-L2UINT32ABCD× 0.1VRead
HR50022doc No. 23 (450023)Mains voltage L1-NUINT32ABCD× 0.1VRead
HR50025doc No. 26 (450026)Mains voltage L2-L3UINT32ABCD× 0.1VRead
HR50027doc No. 28 (450028)Discrete input statePhysical input state; NO/NC setting is ignored.BITMAP16Readbit 8 = Discrete input D8; bit 9 = Discrete input D7; bit 10 = Discrete input D6; bit 11 = Discrete input D5; bit 12 = Discrete input D4; bit 13 = Discrete input D3; bit 14 = Discrete input D2; bit 15 = Discrete input D1
HR50028doc No. 29 (450029)Mains voltage L2-NUINT32ABCD× 0.1VRead
HR50030doc No. 31 (450031)Relay stateBITMAP16Readbit 5 = Relay R11; bit 6 = Relay R10; bit 7 = Relay R9; bit 8 = Relay R8; bit 9 = Relay R7; bit 10 = Relay R6; bit 11 = Relay R5; bit 12 = Relay R4; bit 13 = Relay R3; bit 14 = Relay R2; bit 15 = Relay R1
HR50031doc No. 32 (450032)Mains voltage L3-L1UINT32ABCD× 0.1VRead
HR50033doc No. 34 (450034)System state (operating mode)BITMAP16Readbit 6 = Operating mode AUTOMATIC; bit 7 = Operating mode MANUAL; bit 8 = Operating mode STOP
HR50034doc No. 35 (450035)Mains voltage L3-NUINT32ABCD× 0.1VRead
HR50036doc No. 37 (450037)Alarm classBITMAP16Readbit 0 = Alarm class A; bit 1 = Alarm class B; bit 2 = Alarm class C; bit 3 = Alarm class D; bit 4 = Alarm class E; bit 5 = Alarm class F
HR50037doc No. 38 (450038)Generator current L1UINT32ABCDmARead
HR50039doc No. 40 (450040)Discrete inputs with alarm classBit set when the input is configured as an alarm input and active.BITMAP16Readbit 8 = Discrete input D8; bit 9 = Discrete input D7; bit 10 = Discrete input D6; bit 11 = Discrete input D5; bit 12 = Discrete input D4; bit 13 = Discrete input D3; bit 14 = Discrete input D2; bit 15 = Discrete input D1
HR50040doc No. 41 (450041)Generator current L2UINT32ABCDmARead
HR50042doc No. 43 (450043)Alarms 1BITMAP16Readbit 1 = Maintenance hours expired; bit 2 = Maintenance days expired; bit 3 = Start failure; bit 5 = MCB open failure; bit 6 = MCB close failure; bit 7 = GCB open failure; bit 8 = GCB close failure; bit 9 = Stop failure; bit 10 = Speed detection alarm; bit 11 = Unintended stop; bit 12 = Underspeed limit 2; bit 13 = Underspeed limit 1; bit 14 = Overspeed limit 2; bit 15 = Overspeed limit 1
HR50043doc No. 44 (450044)Generator current L3UINT32ABCDmARead
HR50045doc No. 46 (450046)Generator alarms 1BITMAP16Readbit 1 = Overload limit 2; bit 2 = Overload limit 1; bit 3 = Reverse/reduced power limit 2; bit 4 = Reverse/reduced power limit 1; bit 5 = Overcurrent limit 3; bit 6 = Overcurrent limit 2; bit 7 = Overcurrent limit 1; bit 8 = Undervoltage limit 2; bit 9 = Undervoltage limit 1; bit 10 = Overvoltage limit 2; bit 11 = Overvoltage limit 1; bit 12 = Underfrequency limit 2; bit 13 = Underfrequency limit 1; bit 14 = Overfrequency limit 2; bit 15 = Overfrequency limit 1
HR50046doc No. 47 (450047)Mains current L1UINT32ABCDmARead
HR50048doc No. 49 (450049)Mains alarmsBITMAP16Readbit 0 = Mains load limit 2 (LogicsManager); bit 1 = Mains load limit 1 (LogicsManager); bit 2 = Mains phase rotation wrong; bit 3 = Mains undervoltage (emergency power); bit 4 = Mains overvoltage (emergency power); bit 5 = Mains underfrequency (emergency power); bit 6 = Mains overfrequency (emergency power)
HR50051doc No. 52 (450052)Analog input wire breakBITMAP16Readbit 1 = Wire break analog input T1; bit 2 = Wire break analog input T2
HR50054doc No. 55 (450055)Analog inputs and battery monitoringBITMAP16Readbit 0 = Battery undervoltage limit 1; bit 1 = Battery overvoltage limit 1; bit 2 = Battery undervoltage limit 2; bit 3 = Battery overvoltage limit 2; bit 4 = Analog input T1 limit 1; bit 5 = Analog input T1 limit 2; bit 6 = Analog input T2 limit 1; bit 7 = Analog input T2 limit 2
HR50057doc No. 58 (450058)System stateBITMAP16Readbit 0 = Critical mode (sprinkler) operation; bit 1 = Emergency power operation (AMF); bit 2 = Pre-run auxiliary services; bit 3 = Mains settling; bit 4 = Post-run auxiliary services; bit 5 = Emergency power (AMF) / critical mode; bit 6 = Crank protection; bit 7 = Preglow (diesel); bit 8 = Engine will be stopped; bit 9 = Engine post-run; bit 10 = Start pause; bit 11 = Starter / fuel solenoid (diesel) or gas valve (gas); bit 12 = Dead bus start MCB; bit 13 = Dead bus start GCB; bit 14 = Ignition on (gas engine); bit 15 = Turning (gas engine)
HR50066doc No. 67 (450067)Generator alarms 2BITMAP16Readbit 7 = Inverse-time overcurrent; bit 8 = Generator load limit 2; bit 9 = Generator load limit 1; bit 10 = Generator phase rotation wrong; bit 11 = Ground fault limit 2; bit 12 = Ground fault limit 1; bit 13 = Voltage asymmetry; bit 14 = Load imbalance limit 2; bit 15 = Load imbalance limit 1
HR50067doc No. 68 (450068)Real energyUINT32ABCD× 0.01MWhRead
HR50069doc No. 70 (450070)LogicsManager flagsBITMAP16Readbit 8 = Flag 8 true; bit 9 = Flag 7 true; bit 10 = Flag 6 true; bit 11 = Flag 5 true; bit 12 = Flag 4 true; bit 13 = Flag 3 true; bit 14 = Flag 2 true; bit 15 = Flag 1 true
HR50070doc No. 71 (450071)Reactive energyUINT32ABCD× 0.01MvarhRead
HR50073doc No. 74 (450074)Generator ground currentUINT32ABCDmARead
HR50075doc No. 76 (450076)External discrete inputs with alarm classBITMAP16Readbit 0 = External input DEx01; bit 1 = External input DEx02; bit 2 = External input DEx03; bit 3 = External input DEx04; bit 4 = External input DEx05; bit 5 = External input DEx06; bit 6 = External input DEx07; bit 7 = External input DEx08; bit 8 = External input DEx09; bit 9 = External input DEx10; bit 10 = External input DEx11; bit 11 = External input DEx12; bit 12 = External input DEx13; bit 13 = External input DEx14; bit 14 = External input DEx15; bit 15 = External input DEx16
HR50078doc No. 79 (450079)External relay outputsBITMAP16Readbit 0 = External relay REx01; bit 1 = External relay REx02; bit 2 = External relay REx03; bit 3 = External relay REx04; bit 4 = External relay REx05; bit 5 = External relay REx06; bit 6 = External relay REx07; bit 7 = External relay REx08; bit 8 = External relay REx09; bit 9 = External relay REx10; bit 10 = External relay REx11; bit 11 = External relay REx12; bit 12 = External relay REx13; bit 13 = External relay REx14; bit 14 = External relay REx15; bit 15 = External relay REx16
HR50079doc No. 80 (450080)External discrete inputsBITMAP16Readbit 0 = External input DEx01; bit 1 = External input DEx02; bit 2 = External input DEx03; bit 3 = External input DEx04; bit 4 = External input DEx05; bit 5 = External input DEx06; bit 6 = External input DEx07; bit 7 = External input DEx08; bit 8 = External input DEx09; bit 9 = External input DEx10; bit 10 = External input DEx11; bit 11 = External input DEx12; bit 12 = External input DEx13; bit 13 = External input DEx14; bit 14 = External input DEx15; bit 15 = External input DEx16
HR50111doc No. 112 (450112)J1939 engine speed (SPN 190)From the engine ECU over J1939.UINT32ABCD× 0.1rpmRead
HR50114doc No. 115 (450115)J1939 total engine hours (SPN 247)From the engine ECU over J1939.UINT32ABCDhRead
HR50119doc No. 120 (450120)J1939 engine oil pressure (SPN 100)From the engine ECU over J1939.UINT16kPaRead
HR50169doc No. 170 (450170)Hours of operationUINT32ABCDhRead
HR50172doc No. 173 (450173)ECU lamp alarms (Alarm 2)BITMAP16Readbit 0 = Amber warning lamp from ECU (J1939); bit 1 = Red stop lamp from ECU (J1939)
HR50173doc No. 174 (450174)Number of startsUINT16Read
HR50177doc No. 178 (450178)Hours of operation (1/100 h)UINT32ABCD× 0.01hRead
HR50180doc No. 181 (450181)Free adjustable hours counterUINT32ABCD× 0.01hRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Woodward easYgen-1000 Series genset controller (Modbus RTU)

What Modbus registers does the Woodward easYgen-1000 Series genset controller (Modbus RTU) have?

This map lists 49 registers: 49 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses Modicon numbers. Telegram word No. n is Modicon 450000 + n; the manual says 450001 may become bus address 50000, so word n is wire address 49999 + n. Parameters use Modicon 40000 + (parameter ID + 1), so control word 1 (parameter 503) is 40504 = wire address 503.

What byte order does the Woodward easYgen-1000 Series genset controller (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Woodward easYgen-1000 Series genset controller (Modbus RTU)?

Start with HR 50000 Protocol number (Protocol number (4003) to confirm the map); HR 50001 Generator voltage L1-L2 (Generator voltage L1-L2); HR 50003 Generator frequency (Generator frequency); HR 50037 Generator current L1 (Generator current L1); HR 50033 System state (operating mode) (Operating mode STOP/MANUAL/AUTO); HR 50057 System state (System state); HR 50036 Alarm class (Active alarm classes); HR 503 Control word 1 (Remote start / stop / acknowledge).

How do I enable Modbus control of the Woodward easYgen-1000 Series genset controller (Modbus RTU)?

Select the Modbus protocol on the serial interface and set the Modbus slave ID (0-255) and reply delay (0-1000 ms) in the controller. For remote start/stop the LogicsManager must use command variable 04.13; see application manual 37394. Parameter writes need the code level 2 password for that interface (parameter 10401 for serial interface 1).

What happens when the Woodward easYgen-1000 Series genset controller (Modbus RTU) loses Modbus communication?

Interface watchdogs exist but are disabled by default; they are described in the device manual, not in this document.

Where is the official Woodward easYgen-1000 Series genset controller (Modbus RTU) Modbus documentation?

The source is easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx (37393B), revision 2008-07-02, published free by Woodward at https://www.woodward.com/products/publication-asset/37393.

More Woodward Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx · 37393B · rev. 2008-07-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.