Transfer switch controller · Modbus register map
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus register map
Updated 17 November 2026
The M7000CBNCU03 is BTicino's automatic transfer (changeover) controller for two supply lines. With the RS485 expansion module, or the front optical USB/WiFi interface, it speaks Modbus RTU or ASCII. This map covers both lines' voltages and frequencies, battery voltage, run-time and switching counters, the alarm word, keypad, input, line, breaker and output-function status words and the global status double word.
This page lists 43 Modbus registers for the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from BTicino’s own free documentation (linked below) and checked against it.
- Manufacturer
- BTicino
- Model
- M7000CBNCU03 automatic transfer switch controller (Modbus)
- Equipment type
- Transfer switch controller
- Registers
- 43 (0 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 5
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82
Integration notes: BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
Read input registers (function 04) at table address minus 1: 0x0001 for line 1 L1-N voltage, 0x003F for the alarm double word and 0x220F for the global status flags.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1 | Line 1 voltage L1-N | UINT32 ABCD | Line 1 voltage L1-N | Read |
| IR 13 | Line 2 voltage L1-N | UINT32 ABCD | Line 2 voltage L1-N | Read |
| IR 25 | Line 1 frequency | UINT32 ABCD | Line 1 frequency | Read |
| IR 63 | Alarms | UINT32 ABCD | Alarm flags | Read |
| IR 8719 | Global device status | UINT32 ABCD | Global status (mode, which line feeds the load) | Read |
| IR 8315 | Controller general status | BITMAP16 | Controller mode and error | Read |
Enable Modbus control & writes
Fit the M7000CBNRS485 module, then in the Settings menu open M08 Communication for COM1 or COM2 and set node address, baud, data format, stop bits and protocol. The front IR-USB/IR-WiFi interfaces need no setup.
Byte order & addressing
- Table addresses minus 1 on the wire.
- Voltages are whole volts; frequency and battery voltage in tenths.
Network setup
- Address 1-247 (248-255 internal).
- Baud 1200-115200; 7-bit formats only for Modbus ASCII.
Watch out for
- Writes with function 06 are accepted only above 1000 hex.
- Up to 80 registers per request.
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1doc 02 hex | Line 1 voltage L1-N | UINT32 | ABCD | V | Read | |||
| IR | 3doc 04 hex | Line 1 voltage L2-N | UINT32 | ABCD | V | Read | |||
| IR | 5doc 06 hex | Line 1 voltage L3-N | UINT32 | ABCD | V | Read | |||
| IR | 7doc 08 hex | Line 1 voltage L1-L2 | UINT32 | ABCD | V | Read | |||
| IR | 9doc 0A hex | Line 1 voltage L2-L3 | UINT32 | ABCD | V | Read | |||
| IR | 11doc 0C hex | Line 1 voltage L3-L1 | UINT32 | ABCD | V | Read | |||
| IR | 13doc 0E hex | Line 2 voltage L1-N | UINT32 | ABCD | V | Read | |||
| IR | 15doc 10 hex | Line 2 voltage L2-N | UINT32 | ABCD | V | Read | |||
| IR | 17doc 12 hex | Line 2 voltage L3-N | UINT32 | ABCD | V | Read | |||
| IR | 19doc 14 hex | Line 2 voltage L1-L2 | UINT32 | ABCD | V | Read | |||
| IR | 21doc 16 hex | Line 2 voltage L2-L3 | UINT32 | ABCD | V | Read | |||
| IR | 23doc 18 hex | Line 2 voltage L3-L1 | UINT32 | ABCD | V | Read | |||
| IR | 25doc 1A hex | Line 1 frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| IR | 27doc 1C hex | Line 2 frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| IR | 29doc 1E hex | Battery (DC supply) voltage | UINT32 | ABCD | × 0.1 | V | Read | ||
| IR | 31doc 20 hex | Total operating time | UINT32 | ABCD | s | Read | |||
| IR | 33doc 22 hex | Total time line 1 OK | UINT32 | ABCD | s | Read | |||
| IR | 35doc 24 hex | Total time line 2 OK | UINT32 | ABCD | s | Read | |||
| IR | 37doc 26 hex | Total time line 1 not OK | UINT32 | ABCD | s | Read | |||
| IR | 39doc 28 hex | Total time line 2 not OK | UINT32 | ABCD | s | Read | |||
| IR | 41doc 2A hex | Total time breaker line 1 closed | UINT32 | ABCD | s | Read | |||
| IR | 43doc 2C hex | Total time breaker line 2 closed | UINT32 | ABCD | s | Read | |||
| IR | 45doc 2E hex | Total time both breakers open | UINT32 | ABCD | s | Read | |||
| IR | 49doc 32 hex | Breaker 1 operations in AUT | Count. | UINT32 | ABCD | Read | |||
| IR | 51doc 34 hex | Breaker 2 operations in AUT | Count. | UINT32 | ABCD | Read | |||
| IR | 53doc 36 hex | Breaker 1 operations in MAN | Count. | UINT32 | ABCD | Read | |||
| IR | 55doc 38 hex | Breaker 2 operations in MAN | Count. | UINT32 | ABCD | Read | |||
| IR | 57doc 3A hex | Breaker 1 switching alarms | Count. The manual's example reads 7 here. | UINT32 | ABCD | Read | |||
| IR | 59doc 3C hex | Breaker 2 switching alarms | Count. | UINT32 | ABCD | Read | |||
| IR | 63doc 40 hex | Alarms | 32-bit alarm flags; bit set = alarm active. | UINT32 | ABCD | Read | bit 0 = A01 Battery voltage too low; bit 1 = A02 Battery voltage too high; bit 2 = A03 Line 1 breaker timeout; bit 3 = A04 Line 2 breaker timeout; bit 4 = A05 Line 1 wrong phase sequence; bit 5 = A06 Line 2 wrong phase sequence; bit 6 = A07 Load not supplied timeout; bit 7 = A08 External charger fault; bit 8 = A09 Emergency; bit 9 = A10 Line 1 breaker protection trip; bit 10 = A11 Line 2 breaker protection trip; bit 11 = A12 Line 1 generator not available; bit 12 = A13 Line 2 generator not available; bit 13 = A14 Hour maintenance 1; bit 14 = A15 Hour maintenance 2; bit 15 = A16 Operation maintenance 1; bit 16 = A17 Operation maintenance 2; bit 17 = A18 Auxiliary voltage alarm; bit 18 = UA1 User alarm; bit 19 = UA2 User alarm; bit 20 = UA3 User alarm; bit 21 = UA4 User alarm | ||
| IR | 79doc 50 hex | Battery voltage minimum | UINT32 | ABCD | V | Read | |||
| IR | 81doc 52 hex | Battery voltage maximum | UINT32 | ABCD | V | Read | |||
| IR | 83doc 54 hex | Hour maintenance line 1 | UINT32 | ABCD | Read | ||||
| IR | 85doc 56 hex | Hour maintenance line 2 | UINT32 | ABCD | Read | ||||
| IR | 87doc 58 hex | Operations left to maintenance, line 1 | INT32 | ABCD | Read | ||||
| IR | 89doc 5A hex | Operations left to maintenance, line 2 | INT32 | ABCD | Read | ||||
| IR | 8303doc 2070 hex | Front keypad status | BITMAP16 | Read | bit 0 = Up arrow; bit 1 = OFF/RESET; bit 2 = MAN; bit 3 = Down arrow; bit 4 = AUT/ENTER | ||||
| IR | 8307doc 2074 hex | Line 1 voltage status | BITMAP16 | Read | bit 0 = Line within limits; bit 1 = Line within limits + delay; bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry out of threshold; bit 9 = Voltage below phase-loss threshold; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK | ||||
| IR | 8308doc 2075 hex | Line 1 breaker status | BITMAP16 | Read | bit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = closed); bit 4 = Close command output; bit 5 = Open command output | ||||
| IR | 8313doc 207A hex | Output functions status | BITMAP16 | Read | bit 0 = Open line 1; bit 1 = Open line 2; bit 2 = Close line 1; bit 3 = Close line 2; bit 4 = Global alarm; bit 5 = Start generator 1; bit 6 = Start generator 2; bit 7 = ATS ready; bit 8 = Load shed; bit 11 = Open all; bit 12 = Undervoltage coil 1; bit 13 = Undervoltage coil 2; bit 14 = Line 1 OK; bit 15 = Line 2 OK | ||||
| IR | 8315doc 207C hex | Controller general status | BITMAP16 | Read | bit 0 = Mode OFF/Reset; bit 1 = Mode MAN; bit 2 = Mode AUT; bit 3 = Mode TEST; bit 4 = In error; bit 5 = AC supply present; bit 6 = DC supply present; bit 7 = Global alarm active | ||||
| IR | 8447doc 2100 hex | Digital inputs status | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14 | ||||
| IR | 8719doc 2210 hex | Global device status | 32-bit status flags (bit 0-31). | UINT32 | ABCD | Read | bit 0 = Device in OFF; bit 1 = Device in MAN; bit 2 = Device in AUT; bit 3 = Device in TEST; bit 4 = Line 1 voltage OK; bit 5 = Line 2 voltage OK; bit 6 = Line 1 LED on; bit 7 = Line 2 LED on; bit 10 = Mains contactor closed; bit 11 = Generator contactor closed; bit 12 = Global alarm; bit 13 = AC supply; bit 14 = Start generator 1; bit 15 = Start generator 2; bit 16 = Line 1 max volt; bit 17 = Line 1 min volt; bit 18 = Line 1 max Hz; bit 19 = Line 1 min Hz; bit 20 = Line 1 phase loss; bit 21 = Line 1 asymmetry; bit 22 = Line 2 max volt; bit 23 = Line 2 min volt; bit 24 = Line 2 max Hz; bit 25 = Line 2 min Hz; bit 26 = Line 2 phase loss; bit 27 = Line 2 asymmetry |
Notes on this map
- The source is in Italian; names here are our English translations.
- Word order: the manual's example answers 00 00 00 07 for 7 alarms, so 2-word values are high word first (ABCD).
- Measurements are read with function 04 (input registers) or 03; the manual also lists 06, 07, 16 and 17. Function 06 works only on addresses above 1000 hex.
- Defaults of the COM parameters (P08.n.01-05) as printed: node address 05, 19200 baud, 8 bits even parity, 1 stop bit, Modbus RTU.
- Left out: line 2 voltage/breaker status, printed at 2176/2177 hex while the line 1 rows are 2074/2075 (probably 2076/2077, but not certain); the input-functions status at 2078 (listed as 2 words of 'unsigned integer'); display-message and LED status words; the generic counters CNT1-4 and limits LIM1-4; and all command registers (2F00-2FF0, 4F00), whose wiring into this map would need the full parameter manual.
- Left out: the digital-outputs status word. The status table puts it at 2140 hex, but the bit table below it reads the outputs at 2072 hex, so the address is uncertain.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
What Modbus registers does the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) have?
This map lists 43 registers: 43 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table addresses are hex and one higher than the wire address. The manual says the request address is the table address minus 1, and its example reads breaker-1 switching alarms (table 3A hex) with the frame 01 04 00 39 00 02.
What byte order does the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)?
Start with IR 1 Line 1 voltage L1-N (Line 1 voltage L1-N); IR 13 Line 2 voltage L1-N (Line 2 voltage L1-N); IR 25 Line 1 frequency (Line 1 frequency); IR 63 Alarms (Alarm flags); IR 8719 Global device status (Global status (mode, which line feeds the load)); IR 8315 Controller general status (Controller mode and error).
How do I enable Modbus control of the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)?
Fit the M7000CBNRS485 module, then in the Settings menu open M08 Communication for COM1 or COM2 and set node address, baud, data format, stop bits and protocol. The front IR-USB/IR-WiFi interfaces need no setup.
Where is the official BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus documentation?
The source is M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus (LE09509AA-01/17-01), revision 2017-01, published free by BTicino at https://assets.legrand.com/pim/NP-FT-GT/LE09509AA.pdf.
More BTicino Modbus register maps
Other generator controllers register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
SmartGen HGM9510N / HGM9520N / HGM9530N
HGM9510N, HGM9520N and HGM9530N paralleling genset controllers, protocol document v1.5.
Also known as: HGM9520N, HGM9530N - Power meter (transfer switch metering)
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
ASCO Power Manager Xp, firmware FS611842-006 (some registers AS629262-004); document 381339-221 revision I.
Also known as: ASCO Power Manager Xp, Power Manager Xp, 381339-221
All generator controllers Modbus register maps →
Source: M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus · LE09509AA-01/17-01 · rev. 2017-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.