Transfer switch controller · Modbus register map

BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus register map

Updated 17 November 2026

Short answer

The M7000CBNCU03 is BTicino's automatic transfer (changeover) controller for two supply lines. With the RS485 expansion module, or the front optical USB/WiFi interface, it speaks Modbus RTU or ASCII. This map covers both lines' voltages and frequencies, battery voltage, run-time and switching counters, the alarm word, keypad, input, line, breaker and output-function status words and the global status double word.

This page lists 43 Modbus registers for the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from BTicino’s own free documentation (linked below) and checked against it.

Manufacturer
BTicino
Model
M7000CBNCU03 automatic transfer switch controller (Modbus)
Equipment type
Transfer switch controller
Registers
43 (0 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
5
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82
Source document
M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus · LE09509AA-01/17-01 · rev. 2017-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)

Integration in brief

Read input registers (function 04) at table address minus 1: 0x0001 for line 1 L1-N voltage, 0x003F for the alarm double word and 0x220F for the global status flags.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 1Line 1 voltage L1-NUINT32 ABCDLine 1 voltage L1-NRead
IR 13Line 2 voltage L1-NUINT32 ABCDLine 2 voltage L1-NRead
IR 25Line 1 frequencyUINT32 ABCDLine 1 frequencyRead
IR 63AlarmsUINT32 ABCDAlarm flagsRead
IR 8719Global device statusUINT32 ABCDGlobal status (mode, which line feeds the load)Read
IR 8315Controller general statusBITMAP16Controller mode and errorRead

Enable Modbus control & writes

Fit the M7000CBNRS485 module, then in the Settings menu open M08 Communication for COM1 or COM2 and set node address, baud, data format, stop bits and protocol. The front IR-USB/IR-WiFi interfaces need no setup.

Byte order & addressing

Network setup

Watch out for

BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 02 hexLine 1 voltage L1-NUINT32ABCDVRead
IR3doc 04 hexLine 1 voltage L2-NUINT32ABCDVRead
IR5doc 06 hexLine 1 voltage L3-NUINT32ABCDVRead
IR7doc 08 hexLine 1 voltage L1-L2UINT32ABCDVRead
IR9doc 0A hexLine 1 voltage L2-L3UINT32ABCDVRead
IR11doc 0C hexLine 1 voltage L3-L1UINT32ABCDVRead
IR13doc 0E hexLine 2 voltage L1-NUINT32ABCDVRead
IR15doc 10 hexLine 2 voltage L2-NUINT32ABCDVRead
IR17doc 12 hexLine 2 voltage L3-NUINT32ABCDVRead
IR19doc 14 hexLine 2 voltage L1-L2UINT32ABCDVRead
IR21doc 16 hexLine 2 voltage L2-L3UINT32ABCDVRead
IR23doc 18 hexLine 2 voltage L3-L1UINT32ABCDVRead
IR25doc 1A hexLine 1 frequencyUINT32ABCD× 0.1HzRead
IR27doc 1C hexLine 2 frequencyUINT32ABCD× 0.1HzRead
IR29doc 1E hexBattery (DC supply) voltageUINT32ABCD× 0.1VRead
IR31doc 20 hexTotal operating timeUINT32ABCDsRead
IR33doc 22 hexTotal time line 1 OKUINT32ABCDsRead
IR35doc 24 hexTotal time line 2 OKUINT32ABCDsRead
IR37doc 26 hexTotal time line 1 not OKUINT32ABCDsRead
IR39doc 28 hexTotal time line 2 not OKUINT32ABCDsRead
IR41doc 2A hexTotal time breaker line 1 closedUINT32ABCDsRead
IR43doc 2C hexTotal time breaker line 2 closedUINT32ABCDsRead
IR45doc 2E hexTotal time both breakers openUINT32ABCDsRead
IR49doc 32 hexBreaker 1 operations in AUTCount.UINT32ABCDRead
IR51doc 34 hexBreaker 2 operations in AUTCount.UINT32ABCDRead
IR53doc 36 hexBreaker 1 operations in MANCount.UINT32ABCDRead
IR55doc 38 hexBreaker 2 operations in MANCount.UINT32ABCDRead
IR57doc 3A hexBreaker 1 switching alarmsCount. The manual's example reads 7 here.UINT32ABCDRead
IR59doc 3C hexBreaker 2 switching alarmsCount.UINT32ABCDRead
IR63doc 40 hexAlarms32-bit alarm flags; bit set = alarm active.UINT32ABCDReadbit 0 = A01 Battery voltage too low; bit 1 = A02 Battery voltage too high; bit 2 = A03 Line 1 breaker timeout; bit 3 = A04 Line 2 breaker timeout; bit 4 = A05 Line 1 wrong phase sequence; bit 5 = A06 Line 2 wrong phase sequence; bit 6 = A07 Load not supplied timeout; bit 7 = A08 External charger fault; bit 8 = A09 Emergency; bit 9 = A10 Line 1 breaker protection trip; bit 10 = A11 Line 2 breaker protection trip; bit 11 = A12 Line 1 generator not available; bit 12 = A13 Line 2 generator not available; bit 13 = A14 Hour maintenance 1; bit 14 = A15 Hour maintenance 2; bit 15 = A16 Operation maintenance 1; bit 16 = A17 Operation maintenance 2; bit 17 = A18 Auxiliary voltage alarm; bit 18 = UA1 User alarm; bit 19 = UA2 User alarm; bit 20 = UA3 User alarm; bit 21 = UA4 User alarm
IR79doc 50 hexBattery voltage minimumUINT32ABCDVRead
IR81doc 52 hexBattery voltage maximumUINT32ABCDVRead
IR83doc 54 hexHour maintenance line 1UINT32ABCDRead
IR85doc 56 hexHour maintenance line 2UINT32ABCDRead
IR87doc 58 hexOperations left to maintenance, line 1INT32ABCDRead
IR89doc 5A hexOperations left to maintenance, line 2INT32ABCDRead
IR8303doc 2070 hexFront keypad statusBITMAP16Readbit 0 = Up arrow; bit 1 = OFF/RESET; bit 2 = MAN; bit 3 = Down arrow; bit 4 = AUT/ENTER
IR8307doc 2074 hexLine 1 voltage statusBITMAP16Readbit 0 = Line within limits; bit 1 = Line within limits + delay; bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry out of threshold; bit 9 = Voltage below phase-loss threshold; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8308doc 2075 hexLine 1 breaker statusBITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = closed); bit 4 = Close command output; bit 5 = Open command output
IR8313doc 207A hexOutput functions statusBITMAP16Readbit 0 = Open line 1; bit 1 = Open line 2; bit 2 = Close line 1; bit 3 = Close line 2; bit 4 = Global alarm; bit 5 = Start generator 1; bit 6 = Start generator 2; bit 7 = ATS ready; bit 8 = Load shed; bit 11 = Open all; bit 12 = Undervoltage coil 1; bit 13 = Undervoltage coil 2; bit 14 = Line 1 OK; bit 15 = Line 2 OK
IR8315doc 207C hexController general statusBITMAP16Readbit 0 = Mode OFF/Reset; bit 1 = Mode MAN; bit 2 = Mode AUT; bit 3 = Mode TEST; bit 4 = In error; bit 5 = AC supply present; bit 6 = DC supply present; bit 7 = Global alarm active
IR8447doc 2100 hexDigital inputs statusBITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14
IR8719doc 2210 hexGlobal device status32-bit status flags (bit 0-31).UINT32ABCDReadbit 0 = Device in OFF; bit 1 = Device in MAN; bit 2 = Device in AUT; bit 3 = Device in TEST; bit 4 = Line 1 voltage OK; bit 5 = Line 2 voltage OK; bit 6 = Line 1 LED on; bit 7 = Line 2 LED on; bit 10 = Mains contactor closed; bit 11 = Generator contactor closed; bit 12 = Global alarm; bit 13 = AC supply; bit 14 = Start generator 1; bit 15 = Start generator 2; bit 16 = Line 1 max volt; bit 17 = Line 1 min volt; bit 18 = Line 1 max Hz; bit 19 = Line 1 min Hz; bit 20 = Line 1 phase loss; bit 21 = Line 1 asymmetry; bit 22 = Line 2 max volt; bit 23 = Line 2 min volt; bit 24 = Line 2 max Hz; bit 25 = Line 2 min Hz; bit 26 = Line 2 phase loss; bit 27 = Line 2 asymmetry

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)

What Modbus registers does the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) have?

This map lists 43 registers: 43 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table addresses are hex and one higher than the wire address. The manual says the request address is the table address minus 1, and its example reads breaker-1 switching alarms (table 3A hex) with the frame 01 04 00 39 00 02.

What byte order does the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)?

Start with IR 1 Line 1 voltage L1-N (Line 1 voltage L1-N); IR 13 Line 2 voltage L1-N (Line 2 voltage L1-N); IR 25 Line 1 frequency (Line 1 frequency); IR 63 Alarms (Alarm flags); IR 8719 Global device status (Global status (mode, which line feeds the load)); IR 8315 Controller general status (Controller mode and error).

How do I enable Modbus control of the BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)?

Fit the M7000CBNRS485 module, then in the Settings menu open M08 Communication for COM1 or COM2 and set node address, baud, data format, stop bits and protocol. The front IR-USB/IR-WiFi interfaces need no setup.

Where is the official BTicino M7000CBNCU03 automatic transfer switch controller (Modbus) Modbus documentation?

The source is M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus (LE09509AA-01/17-01), revision 2017-01, published free by BTicino at https://assets.legrand.com/pim/NP-FT-GT/LE09509AA.pdf.

More BTicino Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus · LE09509AA-01/17-01 · rev. 2017-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.