- Home
- Modbus register maps
- BTicino
Manufacturer
BTicino Modbus register maps
Updated 17 November 2026
2 BTicino models, 103 registers in all, each re-typed from BTicino’s own free documentation and checked against it.
- Transfer switch controller
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.
Also known as: M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82 - Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200
BTicino: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| M7000CBNCU03 automatic transfer switch controller (Modbus) | RTU/ASCII | 5 | 19200 baud, 8E1 | ABCD | 1-based | 43 |
| PM multifunction meter F3N200 (Modbus RTU) | RTU | Not stated | - | 16-bit only | 0-based | 60 |