BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The F3N200 is a BTicino PM multifunction meter with an RS-485 Modbus RTU port. Its main readings are 32-bit scaled integers starting at 50512 (hex C550), but the document never states their word order, so this map lists the 16-bit copies at 51280 instead: voltages, currents, frequency, power, power factor, energy, temperature and THD, plus setup registers and the reset/save commands.

This page lists 60 Modbus registers for the BTicino PM multifunction meter F3N200 (Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from BTicino’s own free documentation (linked below) and checked against it.

Manufacturer
BTicino
Model
PM multifunction meter F3N200 (Modbus RTU)
Equipment type
Power meter
Registers
60 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
F3N200, BTicino PM F3N200
Source document
PM Multifunction meter Cat No. F3N200 - ModbusTable BT EN v1.01 · IDP000024 v1.01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: BTicino PM multifunction meter F3N200 (Modbus RTU)

Integration in brief

Read holding registers with function 03 from 51280: the 16-bit block gives voltages, currents, frequency, power, power factor and energy without any word-order question. The 32-bit block at 50512 is more precise but its word order is not documented, so test it on a live meter before using it.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 51284Voltage V1 (16-bit)UINT16Phase 1 voltageRead
HR 51288Current I1 (16-bit)UINT16Phase 1 currentRead
HR 51292Total active power P (16-bit)INT16Total active powerRead
HR 51295Total power factor (16-bit)INT16Total power factorRead
HR 51287Frequency (16-bit)UINT16FrequencyRead
HR 51311Total positive active energy Ea+ (not resettable)UINT16Imported active energyRead

Enable Modbus control & writes

Modbus address (1-247), baud rate, parity and stop bits are programmable; the table does not say where. To change setup over Modbus, write the registers, write 0xA1 to 57856 (E200) to store, then 0xB2 to reboot.

Byte order & addressing

Network setup

Watch out for

BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

60 of 60 shown
BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1024ResetWrite-only (function 06); codes can be added together.UINT16Write1 = Max currents; 2 = Max P+, Q+, S; 128 = kWh+; 256 = kvarh+; 4096 = All parameters
HR36176Alarm cause, lower thresholdWhich measurement tripped the low-threshold alarm.UINT16Read0 = No alarm; 1 = I1; 2 = I2; 3 = I3; 4 = IN; 5 = U12; 6 = U23; 7 = U31; 8 = Total P+; 9 = Total Q+; 10 = Total S; 11 = F; 12 = Total PF lagging; 15 = THD I1; 16 = THD I2; 17 = THD I3; 18 = THD U12; 19 = THD U23; 20 = THD U31; 21 = Hour; 22 = V1; 23 = V2; 24 = V3; 26 = THD V1; 27 = THD V2; 28 = THD V3; 31 = Total PF leading; 32 = Temperature 1
HR36178Alarm cause, upper thresholdWhich measurement tripped the high-threshold alarm.UINT16Read0 = No alarm; 1 = I1; 2 = I2; 3 = I3; 4 = IN; 5 = U12; 6 = U23; 7 = U31; 8 = Total P+; 9 = Total Q+; 10 = Total S; 11 = F; 12 = Total PF lagging; 15 = THD I1; 16 = THD I2; 17 = THD I3; 18 = THD U12; 19 = THD U23; 20 = THD U31; 21 = Hour; 22 = V1; 23 = V2; 24 = V3; 26 = THD V1; 27 = THD V2; 28 = THD V3; 31 = Total PF leading; 32 = Temperature 1
HR36352Network type (setup table)UINT16Read/write0 = 1BL; 1 = 2BL; 2 = 3BL; 3 = 3NBL; 4 = 4BL; 5 = 4NBL
HR36353CT secondary (setup table)UINT16ARead/write1 = 1 A; 5 = 5 A
HR36354CT primary (setup table)UINT16ARead/write
HR36357P/Q/S average/max integration periodUINT16Read/write10 = 10 s; 300 = 5 min; 480 = 8 min; 600 = 10 min; 900 = 15 min; 1200 = 20 min; 1800 = 30 min; 3600 = 60 min
HR36358OUT1 allocationUINT16Read/write0 = kWh+ pulses; 1 = kvarh+ pulses; 2 = Alarm; 3 = Command
HR36359OUT1 pulse weightUINT16Read/write0 = 0.1 kWh/kvarh; 1 = 1 kWh/kvarh; 2 = 10 kWh/kvarh; 3 = 100 kWh/kvarh; 4 = 1000 kWh/kvarh; 5 = 10000 kWh/kvarh
HR36360OUT1 pulse durationUINT16Read/write1 = 100 ms; 2 = 200 ms; 3 = 300 ms; 4 = 400 ms; 5 = 500 ms; 6 = 600 ms; 7 = 700 ms; 8 = 800 ms; 9 = 900 ms
HR36361Hour meter allocationUINT16Read/write1 = Auxiliary supply; 2 = Currents; 3 = Phase-to-phase voltage
HR36368Relay stateUINT16Read/write0 = Open; 1 = Closed
HR50848Number of tariffs0-8; 0 if not available.UINT16Read
HR50849Tariff in progress1-8; 0 if not available.UINT16Read
HR51280Hour meter (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16hRead
HR51281Voltage U12 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51282Voltage U23 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51283Voltage U31 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51284Voltage V1 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51285Voltage V2 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51286Voltage V3 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01VRead
HR51287Frequency (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01HzRead
HR51288Current I1 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16mARead
HR51289Current I2 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16mARead
HR51290Current I3 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16mARead
HR51291Neutral current In (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16mARead
HR51292Total active power P (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kWRead
HR51293Total reactive power Q (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kvarRead
HR51294Total apparent power S (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01kVARead
HR51295Total power factor (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.001Read
HR51296Active power P1 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kWRead
HR51297Active power P2 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kWRead
HR51298Active power P3 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kWRead
HR51299Reactive power Q1 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kvarRead
HR51300Reactive power Q2 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kvarRead
HR51301Reactive power Q3 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.01kvarRead
HR51302Apparent power S1 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01kVARead
HR51303Apparent power S2 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01kVARead
HR51304Apparent power S3 (16-bit)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16× 0.01kVARead
HR51305Power factor PF1 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.001Read
HR51306Power factor PF2 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.001Read
HR51307Power factor PF3 (16-bit)Not affected by CT/VT ratios; 0x7FFF if not available.INT16× 0.001Read
HR51311Total positive active energy Ea+ (not resettable)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16MWhRead
HR51313Total negative active energy Ea- (not resettable)Not affected by CT/VT ratios; 0xFFFF if not available.UINT16MWhRead
HR51456Internal temperature sensor presentUINT16Read0 = No; 1 = Yes
HR51457Module temperatureUINT16°CRead
HR51536THD U120xFFFF if not available.UINT16× 0.1%Read
HR51537THD U230xFFFF if not available.UINT16× 0.1%Read
HR51538THD U310xFFFF if not available.UINT16× 0.1%Read
HR51539THD V10xFFFF if not available.UINT16× 0.1%Read
HR51540THD V20xFFFF if not available.UINT16× 0.1%Read
HR51541THD V30xFFFF if not available.UINT16× 0.1%Read
HR51542THD I10xFFFF if not available.UINT16× 0.1%Read
HR51543THD I20xFFFF if not available.UINT16× 0.1%Read
HR51544THD I30xFFFF if not available.UINT16× 0.1%Read
HR51545THD In0xFFFF if not available.UINT16× 0.1%Read
HR57344Network type0xFFFF if not available.UINT16Read/write0 = 1BL; 1 = 2BL; 2 = 3BL; 3 = 3NBL; 4 = 4BL; 5 = 4NBL
HR57345CT secondary0xFFFF if not available.UINT16ARead/write1 = 1 A; 5 = 5 A
HR57346CT primary0xFFFF if not available.UINT16ARead/write
HR57856ActionWrite 0xA1 to save new settings, then 0xB2 to reboot.UINT16Write161 = 0xA1: store configuration; 178 = 0xB2: reboot

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the BTicino PM multifunction meter F3N200 (Modbus RTU)

What Modbus registers does the BTicino PM multifunction meter F3N200 (Modbus RTU) have?

This map lists 60 registers: 60 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints three columns: a 'Register Number' (address + 1) and the 'Register Address' in decimal and hex. The register address is the wire address: the worked example reads V1 with request 05 03 C558 0002, so 50520 (C558) goes on the wire unchanged.

What are the minimum Modbus registers to integrate the BTicino PM multifunction meter F3N200 (Modbus RTU)?

Start with HR 51284 Voltage V1 (16-bit) (Phase 1 voltage); HR 51288 Current I1 (16-bit) (Phase 1 current); HR 51292 Total active power P (16-bit) (Total active power); HR 51295 Total power factor (16-bit) (Total power factor); HR 51287 Frequency (16-bit) (Frequency); HR 51311 Total positive active energy Ea+ (not resettable) (Imported active energy).

How do I enable Modbus control of the BTicino PM multifunction meter F3N200 (Modbus RTU)?

Modbus address (1-247), baud rate, parity and stop bits are programmable; the table does not say where. To change setup over Modbus, write the registers, write 0xA1 to 57856 (E200) to store, then 0xB2 to reboot.

Where is the official BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus documentation?

The source is PM Multifunction meter Cat No. F3N200 - ModbusTable BT EN v1.01 (IDP000024 v1.01), published free by BTicino at https://dar.bticino.it/asset/Documents/IDP000024_EN_v1.01.pdf.