- PM multifunction meter F3N200 (Modbus RTU)
Power meter · Modbus register map
BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus register map
Updated 17 November 2026
The F3N200 is a BTicino PM multifunction meter with an RS-485 Modbus RTU port. Its main readings are 32-bit scaled integers starting at 50512 (hex C550), but the document never states their word order, so this map lists the 16-bit copies at 51280 instead: voltages, currents, frequency, power, power factor, energy, temperature and THD, plus setup registers and the reset/save commands.
This page lists 60 Modbus registers for the BTicino PM multifunction meter F3N200 (Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from BTicino’s own free documentation (linked below) and checked against it.
- Manufacturer
- BTicino
- Model
- PM multifunction meter F3N200 (Modbus RTU)
- Equipment type
- Power meter
- Registers
- 60 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- F3N200, BTicino PM F3N200
Integration notes: BTicino PM multifunction meter F3N200 (Modbus RTU)
Read holding registers with function 03 from 51280: the 16-bit block gives voltages, currents, frequency, power, power factor and energy without any word-order question. The 32-bit block at 50512 is more precise but its word order is not documented, so test it on a live meter before using it.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 51284 | Voltage V1 (16-bit) | UINT16 | Phase 1 voltage | Read |
| HR 51288 | Current I1 (16-bit) | UINT16 | Phase 1 current | Read |
| HR 51292 | Total active power P (16-bit) | INT16 | Total active power | Read |
| HR 51295 | Total power factor (16-bit) | INT16 | Total power factor | Read |
| HR 51287 | Frequency (16-bit) | UINT16 | Frequency | Read |
| HR 51311 | Total positive active energy Ea+ (not resettable) | UINT16 | Imported active energy | Read |
Enable Modbus control & writes
Modbus address (1-247), baud rate, parity and stop bits are programmable; the table does not say where. To change setup over Modbus, write the registers, write 0xA1 to 57856 (E200) to store, then 0xB2 to reboot.
Byte order & addressing
- Values are read with function 03 even though the table calls them input registers.
Network setup
- RS-485 two-wire, RTU mode, 8 data bits; baud 2400-38400, parity none/odd/even and 1 or 2 stop bits are programmable.
- The table does not state factory defaults for address, baud or parity.
Watch out for
- Setup changes are not applied until 0xA1 (store) and 0xB2 (reboot) are written to 57856.
- Reset codes at 1024 can be OR-ed together; 0x1000 resets all parameters.
BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1024 | Reset | Write-only (function 06); codes can be added together. | UINT16 | Write | 1 = Max currents; 2 = Max P+, Q+, S; 128 = kWh+; 256 = kvarh+; 4096 = All parameters | |||
| HR | 36176 | Alarm cause, lower threshold | Which measurement tripped the low-threshold alarm. | UINT16 | Read | 0 = No alarm; 1 = I1; 2 = I2; 3 = I3; 4 = IN; 5 = U12; 6 = U23; 7 = U31; 8 = Total P+; 9 = Total Q+; 10 = Total S; 11 = F; 12 = Total PF lagging; 15 = THD I1; 16 = THD I2; 17 = THD I3; 18 = THD U12; 19 = THD U23; 20 = THD U31; 21 = Hour; 22 = V1; 23 = V2; 24 = V3; 26 = THD V1; 27 = THD V2; 28 = THD V3; 31 = Total PF leading; 32 = Temperature 1 | |||
| HR | 36178 | Alarm cause, upper threshold | Which measurement tripped the high-threshold alarm. | UINT16 | Read | 0 = No alarm; 1 = I1; 2 = I2; 3 = I3; 4 = IN; 5 = U12; 6 = U23; 7 = U31; 8 = Total P+; 9 = Total Q+; 10 = Total S; 11 = F; 12 = Total PF lagging; 15 = THD I1; 16 = THD I2; 17 = THD I3; 18 = THD U12; 19 = THD U23; 20 = THD U31; 21 = Hour; 22 = V1; 23 = V2; 24 = V3; 26 = THD V1; 27 = THD V2; 28 = THD V3; 31 = Total PF leading; 32 = Temperature 1 | |||
| HR | 36352 | Network type (setup table) | UINT16 | Read/write | 0 = 1BL; 1 = 2BL; 2 = 3BL; 3 = 3NBL; 4 = 4BL; 5 = 4NBL | ||||
| HR | 36353 | CT secondary (setup table) | UINT16 | A | Read/write | 1 = 1 A; 5 = 5 A | |||
| HR | 36354 | CT primary (setup table) | UINT16 | A | Read/write | ||||
| HR | 36357 | P/Q/S average/max integration period | UINT16 | Read/write | 10 = 10 s; 300 = 5 min; 480 = 8 min; 600 = 10 min; 900 = 15 min; 1200 = 20 min; 1800 = 30 min; 3600 = 60 min | ||||
| HR | 36358 | OUT1 allocation | UINT16 | Read/write | 0 = kWh+ pulses; 1 = kvarh+ pulses; 2 = Alarm; 3 = Command | ||||
| HR | 36359 | OUT1 pulse weight | UINT16 | Read/write | 0 = 0.1 kWh/kvarh; 1 = 1 kWh/kvarh; 2 = 10 kWh/kvarh; 3 = 100 kWh/kvarh; 4 = 1000 kWh/kvarh; 5 = 10000 kWh/kvarh | ||||
| HR | 36360 | OUT1 pulse duration | UINT16 | Read/write | 1 = 100 ms; 2 = 200 ms; 3 = 300 ms; 4 = 400 ms; 5 = 500 ms; 6 = 600 ms; 7 = 700 ms; 8 = 800 ms; 9 = 900 ms | ||||
| HR | 36361 | Hour meter allocation | UINT16 | Read/write | 1 = Auxiliary supply; 2 = Currents; 3 = Phase-to-phase voltage | ||||
| HR | 36368 | Relay state | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 50848 | Number of tariffs | 0-8; 0 if not available. | UINT16 | Read | ||||
| HR | 50849 | Tariff in progress | 1-8; 0 if not available. | UINT16 | Read | ||||
| HR | 51280 | Hour meter (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | h | Read | |||
| HR | 51281 | Voltage U12 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51282 | Voltage U23 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51283 | Voltage U31 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51284 | Voltage V1 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51285 | Voltage V2 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51286 | Voltage V3 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | V | Read | ||
| HR | 51287 | Frequency (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 51288 | Current I1 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | mA | Read | |||
| HR | 51289 | Current I2 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | mA | Read | |||
| HR | 51290 | Current I3 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | mA | Read | |||
| HR | 51291 | Neutral current In (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | mA | Read | |||
| HR | 51292 | Total active power P (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kW | Read | ||
| HR | 51293 | Total reactive power Q (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kvar | Read | ||
| HR | 51294 | Total apparent power S (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | kVA | Read | ||
| HR | 51295 | Total power factor (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.001 | Read | |||
| HR | 51296 | Active power P1 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kW | Read | ||
| HR | 51297 | Active power P2 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kW | Read | ||
| HR | 51298 | Active power P3 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kW | Read | ||
| HR | 51299 | Reactive power Q1 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kvar | Read | ||
| HR | 51300 | Reactive power Q2 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kvar | Read | ||
| HR | 51301 | Reactive power Q3 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.01 | kvar | Read | ||
| HR | 51302 | Apparent power S1 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | kVA | Read | ||
| HR | 51303 | Apparent power S2 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | kVA | Read | ||
| HR | 51304 | Apparent power S3 (16-bit) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | × 0.01 | kVA | Read | ||
| HR | 51305 | Power factor PF1 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.001 | Read | |||
| HR | 51306 | Power factor PF2 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.001 | Read | |||
| HR | 51307 | Power factor PF3 (16-bit) | Not affected by CT/VT ratios; 0x7FFF if not available. | INT16 | × 0.001 | Read | |||
| HR | 51311 | Total positive active energy Ea+ (not resettable) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | MWh | Read | |||
| HR | 51313 | Total negative active energy Ea- (not resettable) | Not affected by CT/VT ratios; 0xFFFF if not available. | UINT16 | MWh | Read | |||
| HR | 51456 | Internal temperature sensor present | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 51457 | Module temperature | UINT16 | °C | Read | ||||
| HR | 51536 | THD U12 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51537 | THD U23 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51538 | THD U31 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51539 | THD V1 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51540 | THD V2 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51541 | THD V3 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51542 | THD I1 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51543 | THD I2 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51544 | THD I3 | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 51545 | THD In | 0xFFFF if not available. | UINT16 | × 0.1 | % | Read | ||
| HR | 57344 | Network type | 0xFFFF if not available. | UINT16 | Read/write | 0 = 1BL; 1 = 2BL; 2 = 3BL; 3 = 3NBL; 4 = 4BL; 5 = 4NBL | |||
| HR | 57345 | CT secondary | 0xFFFF if not available. | UINT16 | A | Read/write | 1 = 1 A; 5 = 5 A | ||
| HR | 57346 | CT primary | 0xFFFF if not available. | UINT16 | A | Read/write | |||
| HR | 57856 | Action | Write 0xA1 to save new settings, then 0xB2 to reboot. | UINT16 | Write | 161 = 0xA1: store configuration; 178 = 0xB2: reboot |
Notes on this map
- The document states only the byte order ('Big Endian, most significant byte first') and never which word of a 2-register value comes first, so every 32-bit register is left out. The 16-bit copies of the live values (51280 block) are listed instead.
- The table groups these values under 'INPUT REGISTERS' but gives function code 3 for reading them, and the worked example uses function 03, so they are listed as holding registers.
- The worked example requests 2 registers for V1 but shows a 2-byte reply (08FC = 2300 x 0.01 = 230 V); it confirms the address and scale, not the word order.
- Unavailable values read 0xFFFFFFFF (unsigned) or 0x7FFFFFFF (signed); 16-bit copies use 0xFFFF / 0x7FFF.
- The 51280 block holds 16-bit values that the table says are not affected by the CT/VT ratios; the 50512 block includes them.
- Left out: the customisation and TC-correction block at 4096, whose data types are not given; alarm min/max values and alarm duration (no data type); alarm type, thresholds and hysteresis (36363-36367), because the alarm-type code list repeats codes 5-9 and thresholds have no units; and setup registers 36355/36356, whose rows run together so the 'Reserved' register and the current-averaging period can't be told apart; and the hour-meter trigger threshold (36362), whose unit is printed as A/V.
- The setup and network registers have no data type column; they are single-word values listed here as UINT16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the BTicino PM multifunction meter F3N200 (Modbus RTU)
What Modbus registers does the BTicino PM multifunction meter F3N200 (Modbus RTU) have?
This map lists 60 registers: 60 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints three columns: a 'Register Number' (address + 1) and the 'Register Address' in decimal and hex. The register address is the wire address: the worked example reads V1 with request 05 03 C558 0002, so 50520 (C558) goes on the wire unchanged.
What are the minimum Modbus registers to integrate the BTicino PM multifunction meter F3N200 (Modbus RTU)?
Start with HR 51284 Voltage V1 (16-bit) (Phase 1 voltage); HR 51288 Current I1 (16-bit) (Phase 1 current); HR 51292 Total active power P (16-bit) (Total active power); HR 51295 Total power factor (16-bit) (Total power factor); HR 51287 Frequency (16-bit) (Frequency); HR 51311 Total positive active energy Ea+ (not resettable) (Imported active energy).
How do I enable Modbus control of the BTicino PM multifunction meter F3N200 (Modbus RTU)?
Modbus address (1-247), baud rate, parity and stop bits are programmable; the table does not say where. To change setup over Modbus, write the registers, write 0xA1 to 57856 (E200) to store, then 0xB2 to reboot.
Where is the official BTicino PM multifunction meter F3N200 (Modbus RTU) Modbus documentation?
The source is PM Multifunction meter Cat No. F3N200 - ModbusTable BT EN v1.01 (IDP000024 v1.01), published free by BTicino at https://dar.bticino.it/asset/Documents/IDP000024_EN_v1.01.pdf.
More BTicino Modbus register maps
Other power & energy meters register maps
- Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Energy meter (heat / cooling meter)
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Modbus RTU plug-in communication module (Sylop M/N 11024, firmware 1.0) in a Diehl SHARKY 775 compact heat meter or SCYLAR INT 8 calculator.
Also known as: SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485
All power & energy meters Modbus register maps →
Source: PM Multifunction meter Cat No. F3N200 - ModbusTable BT EN v1.01 · IDP000024 v1.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.