Energy meter (heat / cooling meter) · Modbus register map

Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus register map

Updated 19 November 2026

Short answer

The SHARKY 775 ultrasonic heat meter and the SCYLAR INT 8 calculator take an extension card that polls the meter over its internal M-Bus link and serves the values as a Modbus RTU slave on RS-485. Every measurement is mirrored in both the input and holding register tables, in ten-register groups holding an integer, a unit factor, the unit as text, a unit code and an IEEE-754 float. This map lists the input-register copies of the float, unit and temperature values plus the module's own settings.

This page lists 76 Modbus registers for the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Diehl Metering’s own free documentation (linked below) and checked against it.

Manufacturer
Diehl Metering
Model
SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Equipment type
Energy meter (heat / cooling meter)
Registers
76 (7 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
Module firmware 1.0 (the only version in the change list)
Also known as
SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module
Source document
Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8 - User Manual · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module

Integration in brief

Wire RS-485 to terminals 90(+)/91(-), power the module with 12-24 V AC/DC on 60/61, then read input registers with function 04 at 9600 8N1. The float block of each group (energy 30009, volume 30019, power 30029, flow 30039) is ready to use; read the unit ID just before it once to know the unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 7Energy unit IDUINT16Energy unit codeRead
IR 8Energy (float)FLOAT32 ABCDEnergy (float)Read
IR 18Volume (float)FLOAT32 ABCDVolume (float)Read
IR 28Power (float)FLOAT32 ABCDPower (float)Read
IR 38Flow rate (float)FLOAT32 ABCDFlow rate (float)Read
IR 46Forward temperature (float)FLOAT32 ABCDForward temperature (float)Read
IR 54Return temperature (float)FLOAT32 ABCDReturn temperature (float)Read
IR 164Error codeUINT16Error / data-freshness codeRead

Enable Modbus control & writes

No setting is needed in the meter: fit the card in extension slot 1 or 2, connect it with the ribbon cable and power it. Communication settings are holding registers 41001-41008 written with function 06 or 16.

Byte order & addressing

Network setup

Watch out for

Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

76 of 76 shown
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR3doc 30004Energy unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR7doc 30008Energy unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR8doc 30009Energy (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR13doc 30014Volume unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR17doc 30018Volume unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR18doc 30019Volume (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR23doc 30024Power unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR27doc 30028Power unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR28doc 30029Power (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR33doc 30034Flow rate unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR37doc 30038Flow rate unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR38doc 30039Flow rate (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR40doc 30041Forward temperatureOne decimal; unit given by the unit ID register.INT16× 0.1Read
IR41doc 30042Forward temperature unit nameSTRING[8]Read
IR45doc 30046Forward temperature unit IDUINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR46doc 30047Forward temperature (float)FLOAT32ABCDRead
IR48doc 30049Return temperatureOne decimal; unit given by the unit ID register.INT16× 0.1Read
IR49doc 30050Return temperature unit nameSTRING[8]Read
IR53doc 30054Return temperature unit IDUINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR54doc 30055Return temperature (float)FLOAT32ABCDRead
IR56doc 30057Temperature differenceOne decimal; unit given by the unit ID register.INT16× 0.1Read
IR57doc 30058Temperature difference unit nameSTRING[8]Read
IR61doc 30062Temperature difference unit IDUINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR62doc 30063Temperature difference (float)FLOAT32ABCDRead
IR67doc 30068Tariff energy 1 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR71doc 30072Tariff energy 1 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR72doc 30073Tariff energy 1 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR77doc 30078Tariff volume 1 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR81doc 30082Tariff volume 1 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR82doc 30083Tariff volume 1 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR87doc 30088Tariff energy 2 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR91doc 30092Tariff energy 2 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR92doc 30093Tariff energy 2 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR97doc 30098Tariff volume 2 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR101doc 30102Tariff volume 2 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR102doc 30103Tariff volume 2 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR107doc 30108Tariff energy 3 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR111doc 30112Tariff energy 3 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR112doc 30113Tariff energy 3 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR117doc 30118Tariff volume 3 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR121doc 30122Tariff volume 3 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR122doc 30123Tariff volume 3 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR127doc 30128Tariff energy 4 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR131doc 30132Tariff energy 4 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR132doc 30133Tariff energy 4 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR137doc 30138Tariff volume 4 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR141doc 30142Tariff volume 4 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR142doc 30143Tariff volume 4 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR147doc 30148Pulse input volume 1 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR151doc 30152Pulse input volume 1 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR152doc 30153Pulse input volume 1 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR157doc 30158Pulse input volume 2 unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR161doc 30162Pulse input volume 2 unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR162doc 30163Pulse input volume 2 (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR164doc 30165Error codeHighest-priority active error only; 0x0100 means no fresh data from the meter.UINT16Read0 = No error; 4 = E-8 defective primary voltage, running on backup battery (0x0004); 8 = C-1 basic parameter error in flash or RAM (0x0008); 16 = E-5 communication not possible, update rate too frequent (0x0010); 40 = E-4 ultrasonic measurement hardware error (0x0028); 80 = E-1 temperature out of range -9.9 to 190 °C (0x0050); 112 = E-7 no meaningful ultrasonic signal, air in path (0x0070); 132 = E-9 battery almost flat (0x0084); 176 = E-3 forward and return sensors reversed (0x00B0); 208 = E-6 wrong flow direction (0x00D0); 240 = Leak error (0x00F0); 256 = No data update from heat meter (0x0100)
IR165doc 30166Heat meter serial numberUINT32ABCDRead
IR167doc 30168Heat meter serial number (ASCII)STRING[8]Read
IR171doc 30172Periodical log 0 date: dayValid only when 41008 = 1.UINT16Read
IR172doc 30173Periodical log 0 date: monthUINT16Read
IR173doc 30174Periodical log 0 date: yearUINT16Read
IR177doc 30178Periodical log 0 energy unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR181doc 30182Periodical log 0 energy unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR182doc 30183Periodical log 0 energy (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR187doc 30188Periodical log 0 volume unit nameUnit as 8 ASCII characters, e.g. MJ.STRING[8]Read
IR191doc 30192Periodical log 0 volume unit IDUnit code from the unit ID table.UINT16Read0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F
IR192doc 30193Periodical log 0 volume (float)Unit given by the unit ID register just before it.FLOAT32ABCDRead
IR2000doc 32001Module serial numberUINT32ABCDRead
IR2002doc 32003Module model numberUINT32ABCDRead
IR2004doc 32005Module firmware versionHigh byte major, low byte minor.UINT16Read
HR1000doc 41001Modbus slave IDLow byte = ID 1-247; high byte 1 = auto from meter serial, 0 = static.UINT16Read/write
HR1001doc 41002Update rateHow often the module reads the meter. Default 150 (15.0 s); 0 stops reading.UINT16× 0.1sRead/write
HR1002doc 41003Baud rate1200 to 115200; default 9600.UINT32ABCDbit/sRead/write
HR1004doc 41005Data bitsDefault 8.UINT16Read/write
HR1005doc 41006ParityASCII character code; default 'N'.UINT16Read/write69 = Even ('E'); 78 = None ('N'); 79 = Odd ('O'); 101 = Even ('e'); 110 = None ('n'); 111 = Odd ('o')
HR1006doc 41007Stop bits1 or 2; default 1.UINT16Read/write
HR1007doc 41008Enable periodical log 0 dataUINT16Read/write0 = Disabled (default); 1 = Enabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module

What Modbus registers does the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module have?

This map lists 76 registers: 69 input registers, 7 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print both the Modbus register (30001/40001 style) and the Modbus address; the address is the register minus 30001 or 40001 (e.g. 40011 -> 10). The worked example reads energy with function 04 starting at address 0x0000. Input register 30001+n and holding register 40001+n hold the same measurement value.

What byte order does the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module?

Start with IR 7 Energy unit ID (Energy unit code); IR 8 Energy (float) (Energy (float)); IR 18 Volume (float) (Volume (float)); IR 28 Power (float) (Power (float)); IR 38 Flow rate (float) (Flow rate (float)); IR 46 Forward temperature (float) (Forward temperature (float)); IR 54 Return temperature (float) (Return temperature (float)); IR 164 Error code (Error / data-freshness code).

How do I enable Modbus control of the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module?

No setting is needed in the meter: fit the card in extension slot 1 or 2, connect it with the ribbon cable and power it. Communication settings are holding registers 41001-41008 written with function 06 or 16.

Where is the official Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus documentation?

The source is Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8 - User Manual. Diehl Metering doesn't publish it on its own website, so this map was re-typed from a free copy at https://armatec.com/4a2b67/globalassets/armatec-se/inriver/documents/3535-1607/7500f_man_3.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8 - User Manual · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.