- SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Energy meter (heat / cooling meter) · Modbus register map
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus register map
Updated 19 November 2026
The SHARKY 775 ultrasonic heat meter and the SCYLAR INT 8 calculator take an extension card that polls the meter over its internal M-Bus link and serves the values as a Modbus RTU slave on RS-485. Every measurement is mirrored in both the input and holding register tables, in ten-register groups holding an integer, a unit factor, the unit as text, a unit code and an IEEE-754 float. This map lists the input-register copies of the float, unit and temperature values plus the module's own settings.
This page lists 76 Modbus registers for the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Diehl Metering’s own free documentation (linked below) and checked against it.
- Manufacturer
- Diehl Metering
- Model
- SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
- Equipment type
- Energy meter (heat / cooling meter)
- Registers
- 76 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Module firmware 1.0 (the only version in the change list)
- Also known as
- SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module
Integration notes: Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Wire RS-485 to terminals 90(+)/91(-), power the module with 12-24 V AC/DC on 60/61, then read input registers with function 04 at 9600 8N1. The float block of each group (energy 30009, volume 30019, power 30029, flow 30039) is ready to use; read the unit ID just before it once to know the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 7 | Energy unit ID | UINT16 | Energy unit code | Read |
| IR 8 | Energy (float) | FLOAT32 ABCD | Energy (float) | Read |
| IR 18 | Volume (float) | FLOAT32 ABCD | Volume (float) | Read |
| IR 28 | Power (float) | FLOAT32 ABCD | Power (float) | Read |
| IR 38 | Flow rate (float) | FLOAT32 ABCD | Flow rate (float) | Read |
| IR 46 | Forward temperature (float) | FLOAT32 ABCD | Forward temperature (float) | Read |
| IR 54 | Return temperature (float) | FLOAT32 ABCD | Return temperature (float) | Read |
| IR 164 | Error code | UINT16 | Error / data-freshness code | Read |
Enable Modbus control & writes
No setting is needed in the meter: fit the card in extension slot 1 or 2, connect it with the ribbon cable and power it. Communication settings are holding registers 41001-41008 written with function 06 or 16.
Byte order & addressing
- Floats and 32-bit integers are high word first (ABCD).
- The slave ID follows the meter serial number by default (last three digits, with fall-backs for values over 247); write 41001 with high byte 0 to make it static.
- The float values are computed by the module and can differ slightly from the meter display; the integer copies are exact.
Network setup
- Defaults: automatic slave ID, 9600 baud, 8 data bits, no parity, 1 stop bit.
- Hold the status button for at least 15 s to restore defaults; the LED blinks to confirm.
- Terminate both bus ends; the module is a 1/8 unit-load transceiver.
Watch out for
- On battery-powered meters keep the update rate above 3 minutes, otherwise the meter shows E-5 and the module reports error 0x0010.
- Update rate 0 stops the module reading the meter, so values freeze.
- Periodical log 0 registers (30172-30193) are only valid after writing 1 to 41008, and enabling it changes the M-Bus readout the module uses.
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 3doc 30004 | Energy unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 7doc 30008 | Energy unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 8doc 30009 | Energy (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 13doc 30014 | Volume unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 17doc 30018 | Volume unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 18doc 30019 | Volume (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 23doc 30024 | Power unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 27doc 30028 | Power unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 28doc 30029 | Power (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 33doc 30034 | Flow rate unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 37doc 30038 | Flow rate unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 38doc 30039 | Flow rate (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Forward temperature | One decimal; unit given by the unit ID register. | INT16 | × 0.1 | Read | |||
| IR | 41doc 30042 | Forward temperature unit name | STRING[8] | Read | |||||
| IR | 45doc 30046 | Forward temperature unit ID | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | ||||
| IR | 46doc 30047 | Forward temperature (float) | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Return temperature | One decimal; unit given by the unit ID register. | INT16 | × 0.1 | Read | |||
| IR | 49doc 30050 | Return temperature unit name | STRING[8] | Read | |||||
| IR | 53doc 30054 | Return temperature unit ID | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | ||||
| IR | 54doc 30055 | Return temperature (float) | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | Temperature difference | One decimal; unit given by the unit ID register. | INT16 | × 0.1 | Read | |||
| IR | 57doc 30058 | Temperature difference unit name | STRING[8] | Read | |||||
| IR | 61doc 30062 | Temperature difference unit ID | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | ||||
| IR | 62doc 30063 | Temperature difference (float) | FLOAT32 | ABCD | Read | ||||
| IR | 67doc 30068 | Tariff energy 1 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 71doc 30072 | Tariff energy 1 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 72doc 30073 | Tariff energy 1 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 77doc 30078 | Tariff volume 1 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 81doc 30082 | Tariff volume 1 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 82doc 30083 | Tariff volume 1 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 87doc 30088 | Tariff energy 2 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 91doc 30092 | Tariff energy 2 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 92doc 30093 | Tariff energy 2 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 97doc 30098 | Tariff volume 2 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 101doc 30102 | Tariff volume 2 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 102doc 30103 | Tariff volume 2 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 107doc 30108 | Tariff energy 3 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 111doc 30112 | Tariff energy 3 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 112doc 30113 | Tariff energy 3 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 117doc 30118 | Tariff volume 3 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 121doc 30122 | Tariff volume 3 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 122doc 30123 | Tariff volume 3 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 127doc 30128 | Tariff energy 4 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 131doc 30132 | Tariff energy 4 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 132doc 30133 | Tariff energy 4 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 137doc 30138 | Tariff volume 4 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 141doc 30142 | Tariff volume 4 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 142doc 30143 | Tariff volume 4 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 147doc 30148 | Pulse input volume 1 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 151doc 30152 | Pulse input volume 1 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 152doc 30153 | Pulse input volume 1 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 157doc 30158 | Pulse input volume 2 unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 161doc 30162 | Pulse input volume 2 unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 162doc 30163 | Pulse input volume 2 (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Error code | Highest-priority active error only; 0x0100 means no fresh data from the meter. | UINT16 | Read | 0 = No error; 4 = E-8 defective primary voltage, running on backup battery (0x0004); 8 = C-1 basic parameter error in flash or RAM (0x0008); 16 = E-5 communication not possible, update rate too frequent (0x0010); 40 = E-4 ultrasonic measurement hardware error (0x0028); 80 = E-1 temperature out of range -9.9 to 190 °C (0x0050); 112 = E-7 no meaningful ultrasonic signal, air in path (0x0070); 132 = E-9 battery almost flat (0x0084); 176 = E-3 forward and return sensors reversed (0x00B0); 208 = E-6 wrong flow direction (0x00D0); 240 = Leak error (0x00F0); 256 = No data update from heat meter (0x0100) | |||
| IR | 165doc 30166 | Heat meter serial number | UINT32 | ABCD | Read | ||||
| IR | 167doc 30168 | Heat meter serial number (ASCII) | STRING[8] | Read | |||||
| IR | 171doc 30172 | Periodical log 0 date: day | Valid only when 41008 = 1. | UINT16 | Read | ||||
| IR | 172doc 30173 | Periodical log 0 date: month | UINT16 | Read | |||||
| IR | 173doc 30174 | Periodical log 0 date: year | UINT16 | Read | |||||
| IR | 177doc 30178 | Periodical log 0 energy unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 181doc 30182 | Periodical log 0 energy unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 182doc 30183 | Periodical log 0 energy (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 187doc 30188 | Periodical log 0 volume unit name | Unit as 8 ASCII characters, e.g. MJ. | STRING[8] | Read | ||||
| IR | 191doc 30192 | Periodical log 0 volume unit ID | Unit code from the unit ID table. | UINT16 | Read | 0 = None; 1 = mWh; 2 = Wh; 3 = kWh; 4 = MWh; 5 = GWh; 6 = J; 7 = kJ; 8 = MJ; 9 = GJ; 10 = cal; 11 = kcal; 12 = Mcal; 13 = Gcal; 14 = Btu; 15 = kBtu; 16 = MBtu; 17 = GBtu; 18 = ml; 19 = l; 20 = m3; 21 = mGal; 22 = Gal; 23 = kGal; 24 = MGal; 25 = ml/h; 26 = l/h; 27 = m3/h; 28 = mGal/min; 29 = Gal/min; 30 = kGal/min; 31 = MGal/min; 32 = mW; 33 = W; 34 = kW; 35 = MW; 36 = GW; 37 = Btu/h; 38 = kBtu/h; 39 = MBtu/h; 40 = GBtu/h; 41 = °C; 42 = °F | |||
| IR | 192doc 30193 | Periodical log 0 volume (float) | Unit given by the unit ID register just before it. | FLOAT32 | ABCD | Read | |||
| IR | 2000doc 32001 | Module serial number | UINT32 | ABCD | Read | ||||
| IR | 2002doc 32003 | Module model number | UINT32 | ABCD | Read | ||||
| IR | 2004doc 32005 | Module firmware version | High byte major, low byte minor. | UINT16 | Read | ||||
| HR | 1000doc 41001 | Modbus slave ID | Low byte = ID 1-247; high byte 1 = auto from meter serial, 0 = static. | UINT16 | Read/write | ||||
| HR | 1001doc 41002 | Update rate | How often the module reads the meter. Default 150 (15.0 s); 0 stops reading. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1002doc 41003 | Baud rate | 1200 to 115200; default 9600. | UINT32 | ABCD | bit/s | Read/write | ||
| HR | 1004doc 41005 | Data bits | Default 8. | UINT16 | Read/write | ||||
| HR | 1005doc 41006 | Parity | ASCII character code; default 'N'. | UINT16 | Read/write | 69 = Even ('E'); 78 = None ('N'); 79 = Odd ('O'); 101 = Even ('e'); 110 = None ('n'); 111 = Odd ('o') | |||
| HR | 1006doc 41007 | Stop bits | 1 or 2; default 1. | UINT16 | Read/write | ||||
| HR | 1007doc 41008 | Enable periodical log 0 data | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled |
Notes on this map
- The module is made by Sylop for Diehl Metering meters. Diehl's own download of this guide (diehl.com/cms/files/..._Userguide_ModbusRTU_EN.pdf) answers 401 without a login, so the link is to the unaltered copy published by the Swedish distributor Armatec.
- Word order: the manual says the module sends the most significant register first and most significant byte first, with no byte or word swap. The worked example confirms it: energy Int32 reads 0x0000 0x3039 = 12345 and the float reads 0x4640 0xE400 = 12345.0.
- Left out: the Int32 fixed-point copies and their UInt16 unit-factor registers (offsets 0 and 2 of each ten-register group, e.g. 30001 and 30003). The engineering value is the integer times a unit factor read at run time, so it has no fixed scale. The manual recommends these integers for exact billing values; read them together with the factor register if you need full precision.
- Only the input-register copies are listed. Each value can also be read with function 03 at the same offset in the 4xxxx table (e.g. energy float 30009 = 40009).
- Units of each float follow the unit ID register directly before it (8 = MJ, 9 = GJ, 3 = kWh, 4 = MWh, 20 = m3, 27 = m3/h, 34 = kW, 41 = °C, etc.).
- Temperature integers carry one decimal (multiply by 0.1). Error code is printed as hex values and is shown here as decimal enum keys.
- Defaults from the configuration table: slave ID 0x0101 (automatic from the last three digits of the meter serial number), update rate 15 s, 9600 baud, 8 data bits, parity 'N', 1 stop bit, log 0 disabled.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
What Modbus registers does the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module have?
This map lists 76 registers: 69 input registers, 7 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print both the Modbus register (30001/40001 style) and the Modbus address; the address is the register minus 30001 or 40001 (e.g. 40011 -> 10). The worked example reads energy with function 04 starting at address 0x0000. Input register 30001+n and holding register 40001+n hold the same measurement value.
What byte order does the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module?
Start with IR 7 Energy unit ID (Energy unit code); IR 8 Energy (float) (Energy (float)); IR 18 Volume (float) (Volume (float)); IR 28 Power (float) (Power (float)); IR 38 Flow rate (float) (Flow rate (float)); IR 46 Forward temperature (float) (Forward temperature (float)); IR 54 Return temperature (float) (Return temperature (float)); IR 164 Error code (Error / data-freshness code).
How do I enable Modbus control of the Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module?
No setting is needed in the meter: fit the card in extension slot 1 or 2, connect it with the ribbon cable and power it. Communication settings are holding registers 41001-41008 written with function 06 or 16.
Where is the official Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus documentation?
The source is Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8 - User Manual. Diehl Metering doesn't publish it on its own website, so this map was re-typed from a free copy at https://armatec.com/4a2b67/globalassets/armatec-se/inriver/documents/3535-1607/7500f_man_3.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485 - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509
All power & energy meters Modbus register maps →
Source: Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8 - User Manual · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.