Sensor (electromagnetic flowmeter) · Modbus register map
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus register map
Updated 17 November 2026
The Promag 400 is Endress+Hauser's electromagnetic flowmeter family (D, L and W sensors). Its Modbus RS485 interface exposes every operating-menu parameter at a fixed register. This map lists the values an integrator needs: volume and mass flow, conductivity, three totalizers with their controls, units, diagnostics and the Modbus settings.
This page lists 53 Modbus registers for the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.
- Manufacturer
- Endress+Hauser
- Model
- Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
- Equipment type
- Sensor (electromagnetic flowmeter)
- Registers
- 53 (33 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 247
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Valid from device firmware 02.01.zz
- Also known as
- Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485
Integration notes: Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Set bus address, baud rate and parity on the device, then read volume flow (register 3874, wire 3873) and totalizer 1 (register 2610, wire 2609) with function 03 or 04 as CDAB floats. Reset totalizers by writing to the totalizer control registers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3873 | Volume flow | FLOAT32 CDAB | Volume flow | Read |
| HR 3875 | Mass flow | FLOAT32 CDAB | Mass flow | Read |
| HR 2609 | Totalizer 1 value | FLOAT32 CDAB | Totalizer 1 value | Read |
| HR 2102 | Volume flow unit | UINT16 | Volume flow unit code | Read/write |
| HR 2731 | Actual diagnostics | UINT16 | Active diagnostic | Read |
| HR 2607 | Control totalizer 1 | UINT16 | Totalizer 1 control (reset/hold) | Read/write |
Enable Modbus control & writes
Modbus settings are under Expert > Communication > Modbus configuration. Writing over the bus can be limited with the Fieldbus writing access parameter (Read + write or Read only).
Byte order & addressing
- Floats default to CDAB because of the 1-0-3-2 byte order; the order is selectable on the device.
- Failure mode (register 4920) chooses whether measured values go to NaN or hold the last valid value during a fault.
Network setup
- Factory settings: address 247, 19200 baud, Even parity, RTU.
- Telegram delay (default 6 ms) can be raised for slow masters.
Watch out for
- Writing parameters cyclically wears out the EEPROM.
- Flow and totalizer values are sent in the units set in the unit registers, so changing a unit on the device changes what the numbers mean.
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2012doc 2013 to 2014 | Conductivity | Measured conductivity of the fluid (if the option is active). | FLOAT32 | CDAB | Read | |||
| HR | 2100doc 2101 | Mass flow unit | UINT16 | Read/write | 0 = g/s; 1 = g/min; 2 = g/h; 3 = g/d; 4 = kg/s; 5 = kg/min; 6 = kg/h; 7 = kg/d; 8 = t/s; 9 = t/min; 10 = t/h; 11 = t/d; 12 = oz/s; 13 = oz/min; 14 = oz/h; 15 = oz/d; 16 = lb/s; 17 = lb/min; 18 = lb/h; 19 = lb/d; 20 = STon/s; 21 = STon/min; 22 = STon/h; 23 = STon/d | ||||
| HR | 2101doc 2102 | Mass unit | UINT16 | Read/write | 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon | ||||
| HR | 2102doc 2103 | Volume flow unit | UINT16 | Read/write | 0 = cm³/s; 1 = cm³/min; 2 = cm³/h; 3 = cm³/d; 4 = dm³/s; 5 = dm³/min; 6 = dm³/h; 7 = dm³/d; 8 = m³/s; 9 = m³/min; 10 = m³/h; 11 = m³/d; 12 = ml/s; 13 = ml/min; 14 = ml/h; 15 = ml/d; 16 = l/s; 17 = l/min; 18 = l/h; 19 = l/d; 20 = hl/s; 21 = hl/min; 22 = hl/h; 23 = hl/d; 24 = Ml/s; 25 = Ml/min; 26 = Ml/h; 27 = Ml/d; 32 = af/s; 33 = af/min; 34 = af/h; 35 = af/d; 36 = ft³/s; 37 = ft³/min; 38 = ft³/h; 39 = ft³/d; 40 = fl oz/s (us); 41 = fl oz/min (us); 42 = fl oz/h (us); 43 = fl oz/d (us); 44 = gal/s (us); 45 = gal/min (us); 46 = gal/h (us); 47 = gal/d (us); 48 = Mgal/s (us); 49 = Mgal/min (us); 50 = Mgal/h (us); 51 = Mgal/d (us); 52 = bbl/s (us;liq.); 53 = bbl/min (us;liq.); 54 = bbl/h (us;liq.); 55 = bbl/d (us;liq.); 56 = bbl/s (us;beer); 57 = bbl/min (us;beer); 58 = bbl/h (us;beer); 59 = bbl/d (us;beer); 60 = bbl/s (us;oil); 61 = bbl/min (us;oil); 62 = bbl/h (us;oil); 63 = bbl/d (us;oil); 64 = bbl/s (us;tank); 65 = bbl/min (us;tank); 66 = bbl/h (us;tank); 67 = bbl/d (us;tank); 68 = gal/s (imp); 69 = gal/min (imp); 70 = gal/h (imp); 71 = gal/d (imp); 72 = Mgal/s (imp); 73 = Mgal/min (imp); 74 = Mgal/h (imp); 75 = Mgal/d (imp); 76 = bbl/s (imp;beer); 77 = bbl/min (imp;beer); 78 = bbl/h (imp;beer); 79 = bbl/d (imp;beer); 80 = bbl/s (imp;oil); 81 = bbl/min (imp;oil); 82 = bbl/h (imp;oil); 83 = bbl/d (imp;oil); 88 = kgal/s (us); 89 = kgal/min (us); 90 = kgal/h (us); 91 = kgal/d (us); 92 = MMft³/s; 93 = MMft³/min; 94 = MMft³/h; 96 = Mft³/d | ||||
| HR | 2103doc 2104 | Volume unit | UINT16 | Read/write | 0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³ | ||||
| HR | 2108doc 2109 | Temperature unit | UINT16 | Read/write | 0 = °C; 1 = K; 2 = °F; 3 = °R | ||||
| HR | 2120doc 2121 | Conductivity unit | UINT16 | Read/write | 1 = MS/m; 2 = kS/m; 3 = S/m; 4 = S/cm; 5 = mS/m; 6 = mS/cm; 7 = µS/m; 8 = µS/cm; 9 = µS/mm; 10 = nS/cm | ||||
| HR | 2312doc 2313 to 2314 | Calibration factor | Sensor calibration factor. | FLOAT32 | CDAB | Read | |||
| HR | 2546doc 2547 | Device ID | Four-digit hex device type code. | UINT16 | Read | ||||
| HR | 2589doc 2590 to 2591 | Preset value 1 | Start value used by the preset totalizer commands. | FLOAT32 | CDAB | Read/write | |||
| HR | 2591doc 2592 to 2593 | Preset value 2 | Start value used by the preset totalizer commands. | FLOAT32 | CDAB | Read/write | |||
| HR | 2593doc 2594 to 2595 | Preset value 3 | Start value used by the preset totalizer commands. | FLOAT32 | CDAB | Read/write | |||
| HR | 2600doc 2601 | Totalizer 1 assign process variable | Which flow the totalizer adds up. | UINT16 | Read/write | 0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow | |||
| HR | 2604doc 2605 | Totalizer 1 operation mode | UINT16 | Read/write | 0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total | ||||
| HR | 2605doc 2606 | Totalizer 1 failure mode | Behaviour of the totalizer during a device alarm. | UINT16 | Read/write | 0 = Stop; 1 = Actual value; 2 = Last valid value | |||
| HR | 2607doc 2608 | Control totalizer 1 | Write to reset, preset, hold or run the totalizer. | UINT16 | Read/write | 0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold | |||
| HR | 2608doc 2609 | Reset all totalizers | Write 1 to reset all totalizers and keep counting. | UINT16 | Read/write | 0 = Cancel; 1 = Reset + totalize | |||
| HR | 2609doc 2610 to 2611 | Totalizer 1 value | Current totalizer count in the totalizer's unit. | FLOAT32 | CDAB | Read | |||
| HR | 2611doc 2612 to 2613 | Totalizer 1 overflow | Number of overflows of the totalizer. | FLOAT32 | CDAB | Read | |||
| HR | 2731doc 2732 | Actual diagnostics | Currently active diagnostic event as an integer code. | UINT16 | Read | ||||
| HR | 2733doc 2734 | Previous diagnostics | Last diagnostic event before the current one. | UINT16 | Read | ||||
| HR | 2735doc 2736 | Diagnostics 1 | Entry 1 of the diagnostic list. | UINT16 | Read | ||||
| HR | 2737doc 2738 | Diagnostics 2 | Entry 2 of the diagnostic list. | UINT16 | Read | ||||
| HR | 2739doc 2740 | Diagnostics 3 | Entry 3 of the diagnostic list. | UINT16 | Read | ||||
| HR | 2741doc 2742 | Diagnostics 4 | Entry 4 of the diagnostic list. | UINT16 | Read | ||||
| HR | 2743doc 2744 | Diagnostics 5 | Entry 5 of the diagnostic list. | UINT16 | Read | ||||
| HR | 2800doc 2801 | Totalizer 2 assign process variable | Which flow the totalizer adds up. | UINT16 | Read/write | 0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow | |||
| HR | 2804doc 2805 | Totalizer 2 operation mode | UINT16 | Read/write | 0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total | ||||
| HR | 2805doc 2806 | Totalizer 2 failure mode | Behaviour of the totalizer during a device alarm. | UINT16 | Read/write | 0 = Stop; 1 = Actual value; 2 = Last valid value | |||
| HR | 2807doc 2808 | Control totalizer 2 | Write to reset, preset, hold or run the totalizer. | UINT16 | Read/write | 0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold | |||
| HR | 2809doc 2810 to 2811 | Totalizer 2 value | Current totalizer count in the totalizer's unit. | FLOAT32 | CDAB | Read | |||
| HR | 2811doc 2812 to 2813 | Totalizer 2 overflow | Number of overflows of the totalizer. | FLOAT32 | CDAB | Read | |||
| HR | 2869doc 2870 to 2871 | Zero point | Sensor zero point. | FLOAT32 | CDAB | Read | |||
| HR | 3000doc 3001 | Totalizer 3 assign process variable | Which flow the totalizer adds up. | UINT16 | Read/write | 0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow | |||
| HR | 3004doc 3005 | Totalizer 3 operation mode | UINT16 | Read/write | 0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total | ||||
| HR | 3005doc 3006 | Totalizer 3 failure mode | Behaviour of the totalizer during a device alarm. | UINT16 | Read/write | 0 = Stop; 1 = Actual value; 2 = Last valid value | |||
| HR | 3007doc 3008 | Control totalizer 3 | Write to reset, preset, hold or run the totalizer. | UINT16 | Read/write | 0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold | |||
| HR | 3009doc 3010 to 3011 | Totalizer 3 value | Current totalizer count in the totalizer's unit. | FLOAT32 | CDAB | Read | |||
| HR | 3011doc 3012 to 3013 | Totalizer 3 overflow | Number of overflows of the totalizer. | FLOAT32 | CDAB | Read | |||
| HR | 3873doc 3874 to 3875 | Volume flow | Measured volume flow in the configured volume flow unit. | FLOAT32 | CDAB | Read | |||
| HR | 3875doc 3876 to 3877 | Mass flow | Calculated mass flow (volume x density) in the mass flow unit. | FLOAT32 | CDAB | Read | |||
| HR | 4480doc 4481 | Device revision | Four-digit hex device revision. | UINT16 | Read | ||||
| HR | 4603doc 4604 | Unit totalizer 1 | Engineering unit of the totalizer. | UINT16 | Read/write | 0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None | |||
| HR | 4604doc 4605 | Unit totalizer 2 | Engineering unit of the totalizer. | UINT16 | Read/write | 0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None | |||
| HR | 4605doc 4606 | Unit totalizer 3 | Engineering unit of the totalizer. | UINT16 | Read/write | 0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None | |||
| HR | 4909doc 4910 | Bus address | Modbus slave address, 1-247. | UINT16 | Read/write | ||||
| HR | 4911doc 4912 | Baudrate | UINT16 | baud | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200 | |||
| HR | 4912doc 4913 | Data transfer mode | UINT16 | Read/write | 0 = RTU; 1 = ASCII | ||||
| HR | 4913doc 4914 | Parity | 0 = Even, 1 = Odd; codes 2/3 (no parity) conflict in the manual. | UINT16 | Read/write | ||||
| HR | 4914doc 4915 | Byte order | Byte sequence for floats and strings (factory 1-0-3-2). | UINT16 | Read/write | 0 = 0-1-2-3; 1 = 3-2-1-0; 2 = 2-3-0-1; 3 = 1-0-3-2 | |||
| HR | 4915doc 4916 to 4917 | Telegram delay | Reply delay after a request, 0-100 ms. | FLOAT32 | CDAB | ms | Read/write | ||
| HR | 4919doc 4920 | Failure mode | Value sent for measured values while a diagnostic is active. | UINT16 | Read/write | 1 = Last valid value; 255 = NaN value | |||
| HR | 6816doc 6817 | Device reset | Restart the device or return it to delivery settings. | UINT16 | Read/write | 0 = Cancel; 1 = Restart device; 2 = To delivery settings; 25 = Restore S-DAT backup |
Notes on this map
- This is an integrator subset of a parameter manual that gives a register for every menu item; display, sensor-adjustment, I/O and web-server parameters are left out.
- Float word order follows the Byte order parameter (register 4915). At the factory setting 1-0-3-2 the bytes go out as byte 1, byte 0, byte 3, byte 2, with byte 3 holding the sign and exponent, which is CDAB. If you change Byte order, the word order of every float changes with it.
- Integer parameters are 2 bytes; the manual does not say signed or unsigned, so they are listed as UINT16 (all values shown are positive codes).
- Every value can be read with function 03 or 04 and written with 06 or 16, so it is listed here as a holding register.
- The parity picklist codes for the no-parity options disagree between the parameter description (2 = None/1 stop bit) and the register table (2 = None/2 stop bits), so only 0 = Even and 1 = Odd are given.
- The diagnostic registers return an integer only; the manual does not list the coding, so read the meaning from the device display or operating manual.
- String parameters (device tag, serial number, firmware version, order code) and the scan list (5001-5016, data read back at 5051-5081) are left out because their packing depends on the byte-order setting.
- Writes to non-volatile parameters go to EEPROM, which the manual limits to about one million writes; do not write setpoints cyclically.
- The data-bit and stop-bit count for the Even/Odd parity settings is not stated in this manual, so those defaults are left blank.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
What Modbus registers does the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) have?
This map lists 53 registers: 53 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed in the Modbus Application Protocol form, which the manual equates with Modicon 3XXXX/4XXXX numbers (mass flow 2007 = 32007), and the scan-list parameter says register addresses are 1-based. So subtract 1 for the wire address: volume flow 3874 is requested at 3873.
What byte order does the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)?
Start with HR 3873 Volume flow (Volume flow); HR 3875 Mass flow (Mass flow); HR 2609 Totalizer 1 value (Totalizer 1 value); HR 2102 Volume flow unit (Volume flow unit code); HR 2731 Actual diagnostics (Active diagnostic); HR 2607 Control totalizer 1 (Totalizer 1 control (reset/hold)).
How do I enable Modbus control of the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)?
Modbus settings are under Expert > Communication > Modbus configuration. Writing over the bus can be limited with the Fieldbus writing access parameter (Read + write or Read only).
Where is the official Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus documentation?
The source is Description of Device Parameters Proline Promag 400 Modbus RS485 (GP01045D/06/EN/02.21), revision 2022-02-01, published free by Endress+Hauser at https://bdih-download.endress.com/files/DLA/005056A500261EEC9FD771039688391B/GP01045DEN_0221-00.pdf.
More Endress+Hauser Modbus register maps
- Sensor (water analysis transmitter)
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Liquiline CM44x with the Modbus RS485 or Modbus TCP option, software 1.11.00 and later (SD01189C/07/EN/07.22). The CSFxx sampler and CA80xx analyzer blocks of the same guide are not included.
Also known as: CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448 - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
Promag 300 with the Modbus RS485 communication option, parameter description GP01053D/06/EN/04.22.
Also known as: Promag 300, Promag P 300, Promag H 300, Promag W 300 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Sensor (clamp-on ultrasonic flowmeter)
Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)
Proline Prosonic Flow W 400 clamp-on flowmeter with the Modbus RS485 output, as described in GP01207D/06/EN/01.24.
Also known as: Prosonic Flow W 400
Other power & energy meters register maps
- Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Sensor (Coriolis mass flowmeter)
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).
Also known as: MFC300, KROHNE MFC 300
All power & energy meters Modbus register maps →
Source: Description of Device Parameters Proline Promag 400 Modbus RS485 · GP01045D/06/EN/02.21 · rev. 2022-02-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.