Sensor (electromagnetic flowmeter) · Modbus register map

Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus register map

Updated 17 November 2026

Short answer

The Promag 400 is Endress+Hauser's electromagnetic flowmeter family (D, L and W sensors). Its Modbus RS485 interface exposes every operating-menu parameter at a fixed register. This map lists the values an integrator needs: volume and mass flow, conductivity, three totalizers with their controls, units, diagnostics and the Modbus settings.

This page lists 53 Modbus registers for the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.

Manufacturer
Endress+Hauser
Model
Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Equipment type
Sensor (electromagnetic flowmeter)
Registers
53 (33 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
247
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Valid from device firmware 02.01.zz
Also known as
Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485
Source document
Description of Device Parameters Proline Promag 400 Modbus RS485 · GP01045D/06/EN/02.21 · rev. 2022-02-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)

Integration in brief

Set bus address, baud rate and parity on the device, then read volume flow (register 3874, wire 3873) and totalizer 1 (register 2610, wire 2609) with function 03 or 04 as CDAB floats. Reset totalizers by writing to the totalizer control registers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3873Volume flowFLOAT32 CDABVolume flowRead
HR 3875Mass flowFLOAT32 CDABMass flowRead
HR 2609Totalizer 1 valueFLOAT32 CDABTotalizer 1 valueRead
HR 2102Volume flow unitUINT16Volume flow unit codeRead/write
HR 2731Actual diagnosticsUINT16Active diagnosticRead
HR 2607Control totalizer 1UINT16Totalizer 1 control (reset/hold)Read/write

Enable Modbus control & writes

Modbus settings are under Expert > Communication > Modbus configuration. Writing over the bus can be limited with the Fieldbus writing access parameter (Read + write or Read only).

Byte order & addressing

Network setup

Watch out for

Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

53 of 53 shown
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2012doc 2013 to 2014ConductivityMeasured conductivity of the fluid (if the option is active).FLOAT32CDABRead
HR2100doc 2101Mass flow unitUINT16Read/write0 = g/s; 1 = g/min; 2 = g/h; 3 = g/d; 4 = kg/s; 5 = kg/min; 6 = kg/h; 7 = kg/d; 8 = t/s; 9 = t/min; 10 = t/h; 11 = t/d; 12 = oz/s; 13 = oz/min; 14 = oz/h; 15 = oz/d; 16 = lb/s; 17 = lb/min; 18 = lb/h; 19 = lb/d; 20 = STon/s; 21 = STon/min; 22 = STon/h; 23 = STon/d
HR2101doc 2102Mass unitUINT16Read/write50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon
HR2102doc 2103Volume flow unitUINT16Read/write0 = cm³/s; 1 = cm³/min; 2 = cm³/h; 3 = cm³/d; 4 = dm³/s; 5 = dm³/min; 6 = dm³/h; 7 = dm³/d; 8 = m³/s; 9 = m³/min; 10 = m³/h; 11 = m³/d; 12 = ml/s; 13 = ml/min; 14 = ml/h; 15 = ml/d; 16 = l/s; 17 = l/min; 18 = l/h; 19 = l/d; 20 = hl/s; 21 = hl/min; 22 = hl/h; 23 = hl/d; 24 = Ml/s; 25 = Ml/min; 26 = Ml/h; 27 = Ml/d; 32 = af/s; 33 = af/min; 34 = af/h; 35 = af/d; 36 = ft³/s; 37 = ft³/min; 38 = ft³/h; 39 = ft³/d; 40 = fl oz/s (us); 41 = fl oz/min (us); 42 = fl oz/h (us); 43 = fl oz/d (us); 44 = gal/s (us); 45 = gal/min (us); 46 = gal/h (us); 47 = gal/d (us); 48 = Mgal/s (us); 49 = Mgal/min (us); 50 = Mgal/h (us); 51 = Mgal/d (us); 52 = bbl/s (us;liq.); 53 = bbl/min (us;liq.); 54 = bbl/h (us;liq.); 55 = bbl/d (us;liq.); 56 = bbl/s (us;beer); 57 = bbl/min (us;beer); 58 = bbl/h (us;beer); 59 = bbl/d (us;beer); 60 = bbl/s (us;oil); 61 = bbl/min (us;oil); 62 = bbl/h (us;oil); 63 = bbl/d (us;oil); 64 = bbl/s (us;tank); 65 = bbl/min (us;tank); 66 = bbl/h (us;tank); 67 = bbl/d (us;tank); 68 = gal/s (imp); 69 = gal/min (imp); 70 = gal/h (imp); 71 = gal/d (imp); 72 = Mgal/s (imp); 73 = Mgal/min (imp); 74 = Mgal/h (imp); 75 = Mgal/d (imp); 76 = bbl/s (imp;beer); 77 = bbl/min (imp;beer); 78 = bbl/h (imp;beer); 79 = bbl/d (imp;beer); 80 = bbl/s (imp;oil); 81 = bbl/min (imp;oil); 82 = bbl/h (imp;oil); 83 = bbl/d (imp;oil); 88 = kgal/s (us); 89 = kgal/min (us); 90 = kgal/h (us); 91 = kgal/d (us); 92 = MMft³/s; 93 = MMft³/min; 94 = MMft³/h; 96 = Mft³/d
HR2103doc 2104Volume unitUINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³
HR2108doc 2109Temperature unitUINT16Read/write0 = °C; 1 = K; 2 = °F; 3 = °R
HR2120doc 2121Conductivity unitUINT16Read/write1 = MS/m; 2 = kS/m; 3 = S/m; 4 = S/cm; 5 = mS/m; 6 = mS/cm; 7 = µS/m; 8 = µS/cm; 9 = µS/mm; 10 = nS/cm
HR2312doc 2313 to 2314Calibration factorSensor calibration factor.FLOAT32CDABRead
HR2546doc 2547Device IDFour-digit hex device type code.UINT16Read
HR2589doc 2590 to 2591Preset value 1Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2591doc 2592 to 2593Preset value 2Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2593doc 2594 to 2595Preset value 3Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2600doc 2601Totalizer 1 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow
HR2604doc 2605Totalizer 1 operation modeUINT16Read/write0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total
HR2605doc 2606Totalizer 1 failure modeBehaviour of the totalizer during a device alarm.UINT16Read/write0 = Stop; 1 = Actual value; 2 = Last valid value
HR2607doc 2608Control totalizer 1Write to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR2608doc 2609Reset all totalizersWrite 1 to reset all totalizers and keep counting.UINT16Read/write0 = Cancel; 1 = Reset + totalize
HR2609doc 2610 to 2611Totalizer 1 valueCurrent totalizer count in the totalizer's unit.FLOAT32CDABRead
HR2611doc 2612 to 2613Totalizer 1 overflowNumber of overflows of the totalizer.FLOAT32CDABRead
HR2731doc 2732Actual diagnosticsCurrently active diagnostic event as an integer code.UINT16Read
HR2733doc 2734Previous diagnosticsLast diagnostic event before the current one.UINT16Read
HR2735doc 2736Diagnostics 1Entry 1 of the diagnostic list.UINT16Read
HR2737doc 2738Diagnostics 2Entry 2 of the diagnostic list.UINT16Read
HR2739doc 2740Diagnostics 3Entry 3 of the diagnostic list.UINT16Read
HR2741doc 2742Diagnostics 4Entry 4 of the diagnostic list.UINT16Read
HR2743doc 2744Diagnostics 5Entry 5 of the diagnostic list.UINT16Read
HR2800doc 2801Totalizer 2 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow
HR2804doc 2805Totalizer 2 operation modeUINT16Read/write0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total
HR2805doc 2806Totalizer 2 failure modeBehaviour of the totalizer during a device alarm.UINT16Read/write0 = Stop; 1 = Actual value; 2 = Last valid value
HR2807doc 2808Control totalizer 2Write to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR2809doc 2810 to 2811Totalizer 2 valueCurrent totalizer count in the totalizer's unit.FLOAT32CDABRead
HR2811doc 2812 to 2813Totalizer 2 overflowNumber of overflows of the totalizer.FLOAT32CDABRead
HR2869doc 2870 to 2871Zero pointSensor zero point.FLOAT32CDABRead
HR3000doc 3001Totalizer 3 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Volume flow; 2 = Mass flow; 3 = Corrected volume flow
HR3004doc 3005Totalizer 3 operation modeUINT16Read/write0 = Net flow total; 1 = Forward flow total; 2 = Reverse flow total
HR3005doc 3006Totalizer 3 failure modeBehaviour of the totalizer during a device alarm.UINT16Read/write0 = Stop; 1 = Actual value; 2 = Last valid value
HR3007doc 3008Control totalizer 3Write to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR3009doc 3010 to 3011Totalizer 3 valueCurrent totalizer count in the totalizer's unit.FLOAT32CDABRead
HR3011doc 3012 to 3013Totalizer 3 overflowNumber of overflows of the totalizer.FLOAT32CDABRead
HR3873doc 3874 to 3875Volume flowMeasured volume flow in the configured volume flow unit.FLOAT32CDABRead
HR3875doc 3876 to 3877Mass flowCalculated mass flow (volume x density) in the mass flow unit.FLOAT32CDABRead
HR4480doc 4481Device revisionFour-digit hex device revision.UINT16Read
HR4603doc 4604Unit totalizer 1Engineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None
HR4604doc 4605Unit totalizer 2Engineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None
HR4605doc 4606Unit totalizer 3Engineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 100 = Nl; 101 = Nm³; 102 = Sm³; 103 = Sft³; 104 = Sl; 105 = Sgal (us); 106 = Sbbl (us;liq.); 107 = Sgal (imp); 108 = Sbbl (us;oil); 109 = MMSft³; 110 = Nhl; 251 = None
HR4909doc 4910Bus addressModbus slave address, 1-247.UINT16Read/write
HR4911doc 4912BaudrateUINT16baudRead/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200
HR4912doc 4913Data transfer modeUINT16Read/write0 = RTU; 1 = ASCII
HR4913doc 4914Parity0 = Even, 1 = Odd; codes 2/3 (no parity) conflict in the manual.UINT16Read/write
HR4914doc 4915Byte orderByte sequence for floats and strings (factory 1-0-3-2).UINT16Read/write0 = 0-1-2-3; 1 = 3-2-1-0; 2 = 2-3-0-1; 3 = 1-0-3-2
HR4915doc 4916 to 4917Telegram delayReply delay after a request, 0-100 ms.FLOAT32CDABmsRead/write
HR4919doc 4920Failure modeValue sent for measured values while a diagnostic is active.UINT16Read/write1 = Last valid value; 255 = NaN value
HR6816doc 6817Device resetRestart the device or return it to delivery settings.UINT16Read/write0 = Cancel; 1 = Restart device; 2 = To delivery settings; 25 = Restore S-DAT backup

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)

What Modbus registers does the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) have?

This map lists 53 registers: 53 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed in the Modbus Application Protocol form, which the manual equates with Modicon 3XXXX/4XXXX numbers (mass flow 2007 = 32007), and the scan-list parameter says register addresses are 1-based. So subtract 1 for the wire address: volume flow 3874 is requested at 3873.

What byte order does the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)?

Start with HR 3873 Volume flow (Volume flow); HR 3875 Mass flow (Mass flow); HR 2609 Totalizer 1 value (Totalizer 1 value); HR 2102 Volume flow unit (Volume flow unit code); HR 2731 Actual diagnostics (Active diagnostic); HR 2607 Control totalizer 1 (Totalizer 1 control (reset/hold)).

How do I enable Modbus control of the Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)?

Modbus settings are under Expert > Communication > Modbus configuration. Writing over the bus can be limited with the Fieldbus writing access parameter (Read + write or Read only).

Where is the official Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485) Modbus documentation?

The source is Description of Device Parameters Proline Promag 400 Modbus RS485 (GP01045D/06/EN/02.21), revision 2022-02-01, published free by Endress+Hauser at https://bdih-download.endress.com/files/DLA/005056A500261EEC9FD771039688391B/GP01045DEN_0221-00.pdf.

More Endress+Hauser Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Description of Device Parameters Proline Promag 400 Modbus RS485 · GP01045D/06/EN/02.21 · rev. 2022-02-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.