  4. Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)

Energy meter · Modbus register map

Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) Modbus register map

Updated 17 November 2026

Short answer

When a Fronius Smart Meter is connected to a GEN24 or Tauro inverter over Modbus RTU, the inverter republishes its readings over Modbus TCP as a SunSpec device at a configurable unit ID (meter address 1 = 200 by default, up to 204). With the int+SF data type the meter appears as SunSpec model 201, 202 or 203 after the common block. This map covers the common block, the 16-bit current, voltage, frequency, power and power-factor values with their scale factors, and the end block.

This page lists 48 Modbus registers for the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fronius’s own free documentation (linked below) and checked against it.

Manufacturer
Fronius
Model
Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
Equipment type
Energy meter
Registers
48 (0 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
200
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
Register map archive 1.2.7-2 (Smart_Meter_Register_Map_Int&SF.xlsx); manual 42,0410,2649 rev. 034-28092026.
Also known as
Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203
Source document
Fronius GEN24 Modbus TCP & RTU (operating instructions) + Smart_Meter_Register_Map_Int&SF.xlsx · 42,0410,2649 (034-28092026) · rev. 2026-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)

Integration in brief

Enable the Modbus TCP server in the inverter web UI with SunSpec Model Type int+SF, then poll the meter at its unit ID (default 200). Read 40072-40107 (wire 40071-40106) in one request and apply each _SF register as a power of ten.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40069ID (meter model)UINT16Model ID (203 = three-phase) confirms the int+SF layoutRead
HR 40087WINT16Total active powerRead
HR 40091W_SFINT16Power scale factorRead
HR 40071AINT16Total currentRead
HR 40075A_SFINT16Current scale factorRead
HR 40077PhVphAINT16Phase A voltageRead
HR 40084V_SFINT16Voltage scale factorRead
HR 40085HzINT16FrequencyRead

Enable Modbus control & writes

Inverter web interface > Communication > Modbus: enable the TCP server and choose SunSpec Model Type int+SF. The meter unit ID is set with Meter address offset (factory 200).

Byte order & addressing

Network setup

Watch out for

Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR40002doc 40003ID (common)Common block ID, reads 1.UINT16Read
HR40003doc 40004L (common)Common block length, reads 65.UINT16Read
HR40004doc 40005MnManufacturer name (Fronius).STRING[32]Read
HR40020doc 40021MdMeter model name.STRING[32]Read
HR40036doc 40037OptMeter name, e.g. <primary>.STRING[16]Read
HR40044doc 40045VrMeter software version.STRING[16]Read
HR40052doc 40053SNMeter serial number.STRING[32]Read
HR40068doc 40069DAModbus device address of the meter.UINT16Read
HR40069doc 40070ID (meter model)201 single-phase, 202 split-phase, 203 wye three-phase, 204 delta three-phase.UINT16Read201 = Single phase; 202 = Split phase; 203 = Three phase; 204 = Delta three phase
HR40070doc 40071L (meter model)Length of the meter model block, reads 105.UINT16Read
HR40071doc 40072ATotal AC currentINT16× 10^SF (HR 40075)ARead
HR40072doc 40073AphAPhase A currentINT16× 10^SF (HR 40075)ARead
HR40073doc 40074AphBPhase B currentINT16× 10^SF (HR 40075)ARead
HR40074doc 40075AphCPhase C currentINT16× 10^SF (HR 40075)ARead
HR40075doc 40076A_SFScale factor for current registers.INT16Read
HR40076doc 40077PhVAverage phase-to-neutral voltageINT16× 10^SF (HR 40084)VRead
HR40077doc 40078PhVphAPhase A to neutral voltageINT16× 10^SF (HR 40084)VRead
HR40078doc 40079PhVphBPhase B to neutral voltageINT16× 10^SF (HR 40084)VRead
HR40079doc 40080PhVphCPhase C to neutral voltageINT16× 10^SF (HR 40084)VRead
HR40080doc 40081PPVAverage phase-to-phase voltageINT16× 10^SF (HR 40084)VRead
HR40081doc 40082PhVphABVoltage A-BINT16× 10^SF (HR 40084)VRead
HR40082doc 40083PhVphBCVoltage B-CINT16× 10^SF (HR 40084)VRead
HR40083doc 40084PhVphCAVoltage C-AINT16× 10^SF (HR 40084)VRead
HR40084doc 40085V_SFScale factor for voltage registers.INT16Read
HR40085doc 40086HzGrid frequency.INT16× 10^SF (HR 40086)HzRead
HR40086doc 40087Hz_SFScale factor for frequency.INT16Read
HR40087doc 40088WTotal active power (sign depends on meter location)INT16× 10^SF (HR 40091)WRead
HR40088doc 40089WphAPhase A active powerINT16× 10^SF (HR 40091)WRead
HR40089doc 40090WphBPhase B active powerINT16× 10^SF (HR 40091)WRead
HR40090doc 40091WphCPhase C active powerINT16× 10^SF (HR 40091)WRead
HR40091doc 40092W_SFScale factor for active power.INT16Read
HR40092doc 40093VATotal apparent powerINT16× 10^SF (HR 40096)VARead
HR40093doc 40094VAphAPhase A apparent powerINT16× 10^SF (HR 40096)VARead
HR40094doc 40095VAphBPhase B apparent powerINT16× 10^SF (HR 40096)VARead
HR40095doc 40096VAphCPhase C apparent powerINT16× 10^SF (HR 40096)VARead
HR40096doc 40097VA_SFScale factor for apparent power.INT16Read
HR40097doc 40098VARTotal reactive powerINT16× 10^SF (HR 40101)VArRead
HR40098doc 40099VARphAPhase A reactive powerINT16× 10^SF (HR 40101)VArRead
HR40099doc 40100VARphBPhase B reactive powerINT16× 10^SF (HR 40101)VArRead
HR40100doc 40101VARphCPhase C reactive powerINT16× 10^SF (HR 40101)VArRead
HR40101doc 40102VAR_SFScale factor for reactive power.INT16Read
HR40102doc 40103PFTotal power factorINT16× 10^SF (HR 40106)%Read
HR40103doc 40104PFphAPhase A power factorINT16× 10^SF (HR 40106)%Read
HR40104doc 40105PFphBPhase B power factorINT16× 10^SF (HR 40106)%Read
HR40105doc 40106PFphCPhase C power factorINT16× 10^SF (HR 40106)%Read
HR40106doc 40107PF_SFScale factor for power factor.INT16Read
HR40176doc 40177ID (end block)End block marker, reads 0xFFFF.UINT16Read
HR40177doc 40178L (end block)End block length, reads 0.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)

What Modbus registers does the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) have?

This map lists 48 registers: 48 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Fronius numbers registers from 1 (SunSpec base register 40001) and tells you to request the register number minus one, so register 40072 is read at wire address 40071. The manual's RTU example reads register 40005 with address bytes 9C 44 (40004).

What are the minimum Modbus registers to integrate the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)?

Start with HR 40069 ID (meter model) (Model ID (203 = three-phase) confirms the int+SF layout); HR 40087 W (Total active power); HR 40091 W_SF (Power scale factor); HR 40071 A (Total current); HR 40075 A_SF (Current scale factor); HR 40077 PhVphA (Phase A voltage); HR 40084 V_SF (Voltage scale factor); HR 40085 Hz (Frequency).

How do I enable Modbus control of the Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)?

Inverter web interface > Communication > Modbus: enable the TCP server and choose SunSpec Model Type int+SF. The meter unit ID is set with Meter address offset (factory 200).

Where is the official Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF) Modbus documentation?

The source is Fronius GEN24 Modbus TCP & RTU (operating instructions) + Smart_Meter_Register_Map_Int&SF.xlsx (42,0410,2649 (034-28092026)), revision 2026-09, published free by Fronius at https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2649.pdf.

More Fronius Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →