Short answer

The Datamanager publishes each Fronius Sensor Card as its own Modbus device (unit ID 245 for Solar Net address 0, up to 247). After the common block it carries SunSpec irradiance model 302, back-of-module temperature model 303 and base meteorological model 307. This map covers the identification block, irradiance, both temperature inputs and wind speed.

This page lists 20 Modbus registers for the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fronius’s own free documentation (linked below) and checked against it.

Manufacturer
Fronius
Model
Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
Equipment type
Sensor
Registers
20 (0 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
245
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
Register map archive version 1.1.7-0 (IG_Sensor_Card_Register_Map_Float_and_Int&SF_v1.0.xlsx); manual 42,0410,2049 rev. 033-24022026.
Also known as
Fronius Sensor Card, IG Sensor Card
Source document
Fronius Datamanager Modbus TCP & RTU (operating instructions) + IG_Sensor_Card_Register_Map_Float_and_Int&SF_v1.0.xlsx · 42,0410,2049 (033-24022026) · rev. 2026-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)

Integration in brief

Enable Modbus on the Datamanager and poll the sensor card at unit ID 245 + its Solar Net address. Read 40072 for irradiance and 40079-40086 for temperatures and wind speed.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40069Irradiance IDUINT16Model ID 302 confirms the layoutRead
HR 40071GHIUINT16Global horizontal irradianceRead
HR 40078TmpBOMINT16Module temperature (sensor 1)Read
HR 40082TmpAmbINT16Ambient temperature (sensor 2)Read
HR 40085WndSpdINT16Wind speedRead

Enable Modbus control & writes

In the Datamanager web interface open Settings > Modbus and set data output to tcp (or rtu). The sensor card must be connected to the Datamanager via Solar Net.

Byte order & addressing

Network setup

Watch out for

Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

20 of 20 shown
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR40002doc 40003Common IDCommon block ID, reads 1.UINT16Read
HR40003doc 40004Common LCommon block length, reads 65.UINT16Read
HR40004doc 40005MnManufacturer name (Fronius).STRING[32]Read
HR40020doc 40021MdDevice model name.STRING[32]Read
HR40036doc 40037OptOptions string.STRING[16]Read
HR40044doc 40045VrSoftware version.STRING[16]Read
HR40052doc 40053SNSerial number.STRING[32]Read
HR40068doc 40069DAModbus device address.UINT16Read
HR40069doc 40070Irradiance IDSunSpec irradiance model, reads 302.UINT16Read
HR40070doc 40071Irradiance LModel length, reads 5.UINT16Read
HR40071doc 40072GHIGlobal horizontal irradiance.UINT16W/m2Read
HR40076doc 40077BOM temperature IDSunSpec back-of-module temperature model, reads 303.UINT16Read
HR40077doc 40078BOM temperature LModel length, reads 2.UINT16Read
HR40078doc 40079TmpBOMBack-of-module temperature from temperature sensor 1.INT16× 0.1°CRead
HR40080doc 40081Meteorological IDSunSpec base meteorological model, reads 307.UINT16Read
HR40081doc 40082Meteorological LModel length, reads 11.UINT16Read
HR40082doc 40083TmpAmbAmbient temperature from temperature sensor 2.INT16× 0.1°CRead
HR40085doc 40086WndSpdWind speed.INT16m/sRead
HR40093doc 40094End IDEnd block marker, reads 0xFFFF.UINT16Read
HR40094doc 40095End LEnd block length, reads 0.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)

What Modbus registers does the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) have?

This map lists 20 registers: 20 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Fronius numbers registers from 1 (SunSpec base register 40001) and tells you to request the register number minus one, so register 40072 is read at wire address 40071. The manual's RTU example reads register 40005 with address bytes 9C 44 (40004).

What are the minimum Modbus registers to integrate the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)?

Start with HR 40069 Irradiance ID (Model ID 302 confirms the layout); HR 40071 GHI (Global horizontal irradiance); HR 40078 TmpBOM (Module temperature (sensor 1)); HR 40082 TmpAmb (Ambient temperature (sensor 2)); HR 40085 WndSpd (Wind speed).

How do I enable Modbus control of the Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)?

In the Datamanager web interface open Settings > Modbus and set data output to tcp (or rtu). The sensor card must be connected to the Datamanager via Solar Net.

Where is the official Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307) Modbus documentation?

The source is Fronius Datamanager Modbus TCP & RTU (operating instructions) + IG_Sensor_Card_Register_Map_Float_and_Int&SF_v1.0.xlsx (42,0410,2049 (033-24022026)), revision 2026-02, published free by Fronius at https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2049.pdf.

More Fronius Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Fronius Datamanager Modbus TCP & RTU (operating instructions) + IG_Sensor_Card_Register_Map_Float_and_Int&SF_v1.0.xlsx · 42,0410,2049 (033-24022026) · rev. 2026-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.