- Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
Energy meter · Modbus register map
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) Modbus register map
Updated 17 November 2026
When a Fronius Smart Meter is connected to the Datamanager's RS485 port, the Datamanager republishes its readings as a SunSpec device at Modbus unit ID 240 (meter address 1) to 244. With the int+SF data type the meter appears as SunSpec model 201, 202 or 203 after the common block. This map covers the common block, the 16-bit current, voltage, frequency, power and power-factor values with their scale factors, and the end block.
This page lists 48 Modbus registers for the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fronius’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fronius
- Model
- Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
- Equipment type
- Energy meter
- Registers
- 48 (0 writable)
- Transport
- Modbus TCP
- Default unit ID
- 240
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- Register map archive version 1.1.7-0 (Meter_Register_Map_Int&SF_v1.0.xlsx); manual 42,0410,2049 rev. 033-24022026.
- Also known as
- Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203
Integration notes: Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
Enable Modbus TCP on the Datamanager with SunSpec Model Type int+SF, then poll unit ID 240 (Smart Meter address 1) on port 502. Read 40072-40107 (wire 40071-40106) in one request and apply each _SF register as a power of ten.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40069 | ID (meter model) | UINT16 | Model ID (203 = three-phase) confirms the int+SF layout | Read |
| HR 40087 | W | INT16 | Total active power | Read |
| HR 40091 | W_SF | INT16 | Power scale factor | Read |
| HR 40071 | A | INT16 | Total current | Read |
| HR 40075 | A_SF | INT16 | Current scale factor | Read |
| HR 40077 | PhVphA | INT16 | Phase A voltage | Read |
| HR 40084 | V_SF | INT16 | Voltage scale factor | Read |
| HR 40085 | Hz | INT16 | Frequency | Read |
Enable Modbus control & writes
In the Datamanager web interface open Settings > Modbus, set data output to tcp, and choose SunSpec Model Type int+SF. The meter must already be configured under Settings > Meter.
Byte order & addressing
- Scale factors are signed int16 exponents: value = raw x 10^SF.
- The meter is a separate Modbus device (unit ID 240-244) with its own common block starting again at 40001, not part of the inverter's unit ID.
- The model ID at 40070 tells you which layout is active: 201-203 = int+SF, 211-213 = float (different addresses).
Network setup
- Fronius Smart Meter address 1 maps to Modbus unit ID 240, address 5 to 244.
- If a Modbus meter is configured on the Datamanager, the rtu output setting cannot be used; read the meter over TCP.
Watch out for
- Power sign flips with the configured meter location (grid vs load); check the location before trusting import/export direction.
- Energy counters are 32-bit and not included here because Fronius does not document their word order.
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40002doc 40003 | ID (common) | Common block ID, reads 1. | UINT16 | Read | ||||
| HR | 40003doc 40004 | L (common) | Common block length, reads 65. | UINT16 | Read | ||||
| HR | 40004doc 40005 | Mn | Manufacturer name (Fronius). | STRING[32] | Read | ||||
| HR | 40020doc 40021 | Md | Meter model name. | STRING[32] | Read | ||||
| HR | 40036doc 40037 | Opt | Options string. | STRING[16] | Read | ||||
| HR | 40044doc 40045 | Vr | Meter software version. | STRING[16] | Read | ||||
| HR | 40052doc 40053 | SN | Meter serial number. | STRING[32] | Read | ||||
| HR | 40068doc 40069 | DA | Modbus device address of the meter. | UINT16 | Read | ||||
| HR | 40069doc 40070 | ID (meter model) | 201 single-phase, 202 split-phase, 203 three-phase. | UINT16 | Read | 201 = Single phase; 202 = Split phase; 203 = Three phase | |||
| HR | 40070doc 40071 | L (meter model) | Length of the meter model block, reads 105. | UINT16 | Read | ||||
| HR | 40071doc 40072 | A | Total AC current | INT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40072doc 40073 | AphA | Phase A current | INT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40073doc 40074 | AphB | Phase B current | INT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40074doc 40075 | AphC | Phase C current | INT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40075doc 40076 | A_SF | Scale factor for current registers. | INT16 | Read | ||||
| HR | 40076doc 40077 | PhV | Average phase-to-neutral voltage | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40077doc 40078 | PhVphA | Phase A to neutral voltage | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40078doc 40079 | PhVphB | Phase B to neutral voltage | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40079doc 40080 | PhVphC | Phase C to neutral voltage | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40080doc 40081 | PPV | Average phase-to-phase voltage | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40081doc 40082 | PPVphAB | Voltage A-B | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40082doc 40083 | PPVphBC | Voltage B-C | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40083doc 40084 | PPVphCA | Voltage C-A | INT16 | × 10^SF (HR 40084) | V | Read | ||
| HR | 40084doc 40085 | V_SF | Scale factor for voltage registers. | INT16 | Read | ||||
| HR | 40085doc 40086 | Hz | Grid frequency. | INT16 | × 10^SF (HR 40086) | Hz | Read | ||
| HR | 40086doc 40087 | Hz_SF | Scale factor for frequency. | INT16 | Read | ||||
| HR | 40087doc 40088 | W | Total active power (sign depends on meter location) | INT16 | × 10^SF (HR 40091) | W | Read | ||
| HR | 40088doc 40089 | WphA | Phase A active power | INT16 | × 10^SF (HR 40091) | W | Read | ||
| HR | 40089doc 40090 | WphB | Phase B active power | INT16 | × 10^SF (HR 40091) | W | Read | ||
| HR | 40090doc 40091 | WphC | Phase C active power | INT16 | × 10^SF (HR 40091) | W | Read | ||
| HR | 40091doc 40092 | W_SF | Scale factor for active power. | INT16 | Read | ||||
| HR | 40092doc 40093 | VA | Total apparent power | INT16 | × 10^SF (HR 40096) | VA | Read | ||
| HR | 40093doc 40094 | VAphA | Phase A apparent power | INT16 | × 10^SF (HR 40096) | VA | Read | ||
| HR | 40094doc 40095 | VAphB | Phase B apparent power | INT16 | × 10^SF (HR 40096) | VA | Read | ||
| HR | 40095doc 40096 | VAphC | Phase C apparent power | INT16 | × 10^SF (HR 40096) | VA | Read | ||
| HR | 40096doc 40097 | VA_SF | Scale factor for apparent power. | INT16 | Read | ||||
| HR | 40097doc 40098 | VAR | Total reactive power | INT16 | × 10^SF (HR 40101) | VAr | Read | ||
| HR | 40098doc 40099 | VARphA | Phase A reactive power | INT16 | × 10^SF (HR 40101) | VAr | Read | ||
| HR | 40099doc 40100 | VARphB | Phase B reactive power | INT16 | × 10^SF (HR 40101) | VAr | Read | ||
| HR | 40100doc 40101 | VARphC | Phase C reactive power | INT16 | × 10^SF (HR 40101) | VAr | Read | ||
| HR | 40101doc 40102 | VAR_SF | Scale factor for reactive power. | INT16 | Read | ||||
| HR | 40102doc 40103 | PF | Total power factor | INT16 | × 10^SF (HR 40106) | % | Read | ||
| HR | 40103doc 40104 | PFphA | Phase A power factor | INT16 | × 10^SF (HR 40106) | % | Read | ||
| HR | 40104doc 40105 | PFphB | Phase B power factor | INT16 | × 10^SF (HR 40106) | % | Read | ||
| HR | 40105doc 40106 | PFphC | Phase C power factor | INT16 | × 10^SF (HR 40106) | % | Read | ||
| HR | 40106doc 40107 | PF_SF | Scale factor for power factor. | INT16 | Read | ||||
| HR | 40176doc 40177 | ID (end block) | End block marker, reads 0xFFFF. | UINT16 | Read | ||||
| HR | 40177doc 40178 | L (end block) | End block length, reads 0. | UINT16 | Read |
Notes on this map
- Register table comes from Fronius' official 'Meter_Register_Map_Int&SF_v1.0.xlsx' in the Modbus SunSpec maps ZIP published next to the PDF; behaviour and device IDs come from the PDF.
- Addresses assume SunSpec Model Type = int+SF. With the default float setting the meter shows model 211/212/213 and the register layout is different.
- Word order: neither the PDF nor the XLSX states the order of 32-bit values, so the 32-bit SID (40001-40002), all acc32 energy counters (TotWhExp 40108, TotWhImp 40116, TotVAhExp 40125, TotVAhImp 40133 and the per-phase/VArh counters, most of which the XLSX marks unsupported) and the 32-bit event field (40175) are left out, together with their energy scale-factor registers.
- Phase B/C values are only meaningful on a three-phase meter (model 203).
- The sign of W and the meaning of the import/export energy counters depend on the meter location set in the Datamanager (0 grid, 1 load, 3 external generator, 256-511 sub-load); see the location table in the PDF.
- The PDF says unsupported int16 values read 0x8000 and unsupported scale factors read 0x8000.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
What Modbus registers does the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) have?
This map lists 48 registers: 48 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Fronius numbers registers from 1 (SunSpec base register 40001) and tells you to request the register number minus one, so register 40072 is read at wire address 40071. The manual's RTU example reads register 40005 with address bytes 9C 44 (40004).
What are the minimum Modbus registers to integrate the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)?
Start with HR 40069 ID (meter model) (Model ID (203 = three-phase) confirms the int+SF layout); HR 40087 W (Total active power); HR 40091 W_SF (Power scale factor); HR 40071 A (Total current); HR 40075 A_SF (Current scale factor); HR 40077 PhVphA (Phase A voltage); HR 40084 V_SF (Voltage scale factor); HR 40085 Hz (Frequency).
How do I enable Modbus control of the Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)?
In the Datamanager web interface open Settings > Modbus, set data output to tcp, and choose SunSpec Model Type int+SF. The meter must already be configured under Settings > Meter.
Where is the official Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF) Modbus documentation?
The source is Fronius Datamanager Modbus TCP & RTU (operating instructions) + Meter_Register_Map_Int&SF_v1.0.xlsx (42,0410,2049 (033-24022026)), revision 2026-02, published free by Fronius at https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2049.pdf.
More Fronius Modbus register maps
- Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus - Solar inverter
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Fronius Primo/Symo GEN24 (Plus) US variants with a battery configured, SunSpec Model Type int+SF; the US map appends IEEE 1547 models 701-713 after storage model 124.
Also known as: Primo GEN24 Plus US, Symo GEN24 Plus US, Primo GEN24 10.0 208-240, Primo GEN24 3.8 208-240, Primo GEN24 6.0 208-240 - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0 - Solar inverter
Fronius Tauro 50-3 (SunSpec int+SF)
Fronius Tauro 50-3-P / 50-3-D commercial inverters (rest-of-world map, 3 MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro, Tauro 50-3-P, Tauro 50-3-D - Solar inverter
Fronius Tauro ECO 50-100 (SunSpec int+SF)
Fronius Tauro ECO 50-100 kW commercial inverters (rest-of-world map, single MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro ECO, Tauro ECO 50-3-P, Tauro ECO 99-3-D, Tauro ECO 100-3-P, Tauro ECO 100-3-D
Other power & energy meters register maps
- Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Sensor (electromagnetic flowmeter)
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
IFC 100 signal converter with the Modbus option, supplementary instructions 4001410101 R01 (08/2014).
Also known as: IFC100, IFC 100 Modbus, KROHNE IFC 100 - Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG
All power & energy meters Modbus register maps →
Source: Fronius Datamanager Modbus TCP & RTU (operating instructions) + Meter_Register_Map_Int&SF_v1.0.xlsx · 42,0410,2049 (033-24022026) · rev. 2026-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.