Power meter (power quality analyser) · Modbus register map

Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map

Updated 28 October 2026

Short answer

The UMG 605-PRO is a Janitza power quality analyser with an RS-485 port and network (IP) settings. Measurements are big-endian 32-bit floats; the 19000-19120 'frequently required readings' block holds volts, amps, power, CosPhi, frequency, energy and THD, the same block as other Janitza meters. Its other address blocks differ from the UMG 604-PRO, so this map lists the 605-PRO's own addresses for the fourth channel, consumed energy, digital I/O, energy resets, transformer settings and network values.

This page lists 73 Modbus registers for the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
Equipment type
Power meter (power quality analyser)
Registers
73 (2 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Release 5.028 and higher
Also known as
UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605
Source document
Power Quality Analyser UMG 605-PRO - Modbus-address list and Formulary (firmware rel. 5.028 and higher) · 1.038.009.7.h · rev. 2022-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)

Integration in brief

Read holding registers (function 03) from 19000: 60 registers give volts, amps, power, CosPhi, frequency and per-phase energy as big-endian floats, and 19060-19077 adds three-phase and delivered energy in Wh. Read 6508 for the consumed energy total.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Current L1FLOAT32 ABCDCurrent L1Read
HR 19026Real power total L1-L3FLOAT32 ABCDTotal real powerRead
HR 19034Apparent power total L1-L3FLOAT32 ABCDTotal apparent powerRead
HR 3929CosPhi total L1-L3 (fundamental)FLOAT32 ABCDTotal CosPhiRead
HR 19050FrequencyFLOAT32 ABCDFrequencyRead
HR 6508Real energy L1-L3, consumedFLOAT32 ABCDConsumed energy totalRead
HR 19076Real energy L1-L3, deliveredFLOAT32 ABCDDelivered energy totalRead

Enable Modbus control & writes

Modbus is available on Ethernet and on the RS-485 port; set the Modbus address and IP settings on the device or in GridVis (see the device manual).

Byte order & addressing

Network setup

Watch out for

Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

73 of 73 shown
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3851Voltage L4-NFourth voltage input.FLOAT32ABCDVRead
HR3859Current L4Fourth current input (measured neutral or extra feeder).FLOAT32ABCDARead
HR3929CosPhi total L1-L3 (fundamental)Mains-frequency CosPhi over L1-L3.FLOAT32ABCDRead
HR4209Internal temperatureFLOAT32ABCD°CRead
HR6508Real energy L1-L3, consumedThree-phase consumed (import) energy total.FLOAT32ABCDWhRead
HR6630Digital output 1 statusINT16Read0 = Not active; 1 = Active
HR6631Digital output 2 statusINT16Read0 = Not active; 1 = Active
HR6632Digital input 1 statusINT16Read0 = Not active; 1 = Active
HR6633Digital input 2 statusINT16Read0 = Not active; 1 = Active
HR6654Delete real energyWrite 1 to clear all real energy counters.INT16Write
HR6655Delete reactive energyWrite 1 to clear all reactive energy counters.INT16Write
HR6689CT primary L1-L3One setting shared by L1, L2 and L3.FLOAT32ABCDARead
HR6691CT primary L4FLOAT32ABCDARead
HR6693CT secondary L1-L3One setting shared by L1, L2 and L3.FLOAT32ABCDARead
HR6695CT secondary L4FLOAT32ABCDARead
HR6697VT primary L1-L3One setting shared by L1, L2 and L3.FLOAT32ABCDVRead
HR6699VT primary L4FLOAT32ABCDVRead
HR6701VT secondary L1-L3One setting shared by L1, L2 and L3.FLOAT32ABCDVRead
HR6703VT secondary L4FLOAT32ABCDVRead
HR6745Nominal frequency50 or 60 Hz.FLOAT32ABCDHzRead
HR6870IP addressPacked 32-bit IPv4 address.UINT32ABCDRead
HR6872Subnet maskPacked 32-bit IPv4 mask.UINT32ABCDRead
HR6874Gateway addressPacked 32-bit IPv4 gateway.UINT32ABCDRead
HR6876DHCP modeINT32ABCDRead0 = DHCP off; 1 = DHCP on
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Current L1FLOAT32ABCDARead
HR19014Current L2FLOAT32ABCDARead
HR19016Current L3FLOAT32ABCDARead
HR19018Neutral current (vector sum L1-L3)Calculated vector sum of the three phase currents.FLOAT32ABCDARead
HR19020Real power L1FLOAT32ABCDWRead
HR19022Real power L2FLOAT32ABCDWRead
HR19024Real power L3FLOAT32ABCDWRead
HR19026Real power total L1-L3FLOAT32ABCDWRead
HR19028Apparent power L1FLOAT32ABCDVARead
HR19030Apparent power L2FLOAT32ABCDVARead
HR19032Apparent power L3FLOAT32ABCDVARead
HR19034Apparent power total L1-L3FLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental)FLOAT32ABCDvarRead
HR19042Reactive power total L1-L3 (fundamental)FLOAT32ABCDvarRead
HR19044CosPhi L1 (fundamental)FLOAT32ABCDRead
HR19046CosPhi L2 (fundamental)FLOAT32ABCDRead
HR19048CosPhi L3 (fundamental)FLOAT32ABCDRead
HR19050FrequencyFLOAT32ABCDHzRead
HR19052Rotation fieldFloat: 1 = clockwise, 0 = none, -1 = anticlockwise.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1-L3Three-phase total, not split into consumed and delivered.FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1-L3, deliveredFLOAT32ABCDWhRead
HR19084Apparent energy L1-L3FLOAT32ABCDVAhRead
HR19092Reactive energy L1-L3 (fundamental)FLOAT32ABCDvarhRead
HR19100Reactive energy inductive L1-L3FLOAT32ABCDvarhRead
HR19108Reactive energy capacitive L1-L3FLOAT32ABCDvarhRead
HR19110THD voltage L1-NFLOAT32ABCD%Read
HR19112THD voltage L2-NFLOAT32ABCD%Read
HR19114THD voltage L3-NFLOAT32ABCD%Read
HR19116THD current L1FLOAT32ABCD%Read
HR19118THD current L2FLOAT32ABCD%Read
HR19120THD current L3FLOAT32ABCD%Read
HR19716Transformer ratio lockINT16Read0 = Not locked; 1 = Locked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)

What Modbus registers does the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) have?

This map lists 73 registers: 73 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (system time), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total L1-L3 (Total real power); HR 19034 Apparent power total L1-L3 (Total apparent power); HR 3929 CosPhi total L1-L3 (fundamental) (Total CosPhi); HR 19050 Frequency (Frequency); HR 6508 Real energy L1-L3, consumed (Consumed energy total); HR 19076 Real energy L1-L3, delivered (Delivered energy total).

How do I enable Modbus control of the Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)?

Modbus is available on Ethernet and on the RS-485 port; set the Modbus address and IP settings on the device or in GridVis (see the device manual).

Where is the official Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus documentation?

The source is Power Quality Analyser UMG 605-PRO - Modbus-address list and Formulary (firmware rel. 5.028 and higher) (1.038.009.7.h), revision 2022-09, published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG605-PRO/janitza-mal-umg605pro-en.pdf.

More Janitza Modbus register maps

Source: Power Quality Analyser UMG 605-PRO - Modbus-address list and Formulary (firmware rel. 5.028 and higher) · 1.038.009.7.h · rev. 2022-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.