Power meter (power quality analyser) · Modbus register map

Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map

Updated 29 October 2026

Short answer

The UMG 512-PRO is Janitza's power quality analyser with four voltage and four current channels; the list covers both its RS-485 settings and IP network settings. Measurements are big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block, total power factor, the fourth channel sum, energy totals, digital I/O, transformer ratios and the energy reset commands.

This page lists 72 Modbus registers for the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
Equipment type
Power meter (power quality analyser)
Registers
72 (17 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO
Source document
Power Quality Analyser UMG 512-PRO - Modbus-address and Formulary · 1.054.016.3.k · rev. 2023-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)

Integration in brief

Read holding registers (function 03) from 19000 over Modbus TCP or RTU: the block gives volts, amps, power, CosPhi, frequency, energy and THD as big-endian floats. For all-tariff energy totals read 6508 (consumed) and 6520 (delivered); 19636 gives the total power factor.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Current L1FLOAT32 ABCDCurrent L1Read
HR 19026Real power totalFLOAT32 ABCDTotal real powerRead
HR 19636Power factor totalFLOAT32 ABCDTotal power factorRead/write
HR 19050FrequencyFLOAT32 ABCDFrequencyRead
HR 6508Real energy L1-L3, consumedFLOAT32 ABCDConsumed real energy, all tariffsRead/write
HR 6520Real energy L1-L3, deliveredFLOAT32 ABCDDelivered real energy, all tariffsRead/write

Enable Modbus control & writes

The address list does not describe how to enable Modbus or pick the port; it only lists the RS-485 and IP settings rows (several marked internal use).

Byte order & addressing

Network setup

Watch out for

Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

72 of 72 shown
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3921Current sum L1-L4 (vector)Vector sum of all four current inputs.FLOAT32ABCDARead
HR3929CosPhi total (fundamental)CosPhi of the mains-frequency component, L1-L3.FLOAT32ABCDRead
HR3997Nominal frequencyFLOAT32ABCDHzRead
HR4209Internal temperatureFLOAT32ABCD°CRead
HR6474Apparent energy L1-L4FLOAT32ABCDVAhRead/write
HR6508Real energy L1-L3, consumedEnergy table copy; writable (preset).FLOAT32ABCDWhRead/write
HR6510Real energy L1-L4, consumedFLOAT32ABCDWhRead/write
HR6520Real energy L1-L3, deliveredEnergy table copy; writable (preset).FLOAT32ABCDWhRead/write
HR6522Real energy L1-L4, deliveredFLOAT32ABCDWhRead/write
HR6630Digital output 1 statusINT16Read/write0 = Not active; 1 = Active
HR6631Digital output 2 statusINT16Read/write0 = Not active; 1 = Active
HR6632Digital input 1 statusINT16Read0 = Not active; 1 = Active
HR6633Digital input 2 statusINT16Read0 = Not active; 1 = Active
HR6654Delete real energy countersWrite 1 to clear all real energy counters.INT16Read/write
HR6655Delete reactive energy countersWrite 1 to clear all reactive energy counters.INT16Read/write
HR6689CT L1-L3 primaryFLOAT32ABCDARead/write
HR6691CT L4 primaryFLOAT32ABCDARead/write
HR6693CT L1-L3 secondaryFLOAT32ABCDARead/write
HR6695CT L4 secondaryFLOAT32ABCDARead/write
HR6697VT L1-L3 primaryFLOAT32ABCDVRead/write
HR6699VT L4 primaryFLOAT32ABCDVRead/write
HR6701VT L1-L3 secondaryFLOAT32ABCDVRead/write
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Current L1FLOAT32ABCDARead
HR19014Current L2FLOAT32ABCDARead
HR19016Current L3FLOAT32ABCDARead
HR19018Neutral current (vector sum)Calculated vector sum of the three phase currents.FLOAT32ABCDARead
HR19020Real power L1FLOAT32ABCDWRead
HR19022Real power L2FLOAT32ABCDWRead
HR19024Real power L3FLOAT32ABCDWRead
HR19026Real power totalSum of L1-L3.FLOAT32ABCDWRead
HR19028Apparent power L1FLOAT32ABCDVARead
HR19030Apparent power L2FLOAT32ABCDVARead
HR19032Apparent power L3FLOAT32ABCDVARead
HR19034Apparent power totalSum of L1-L3.FLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental)FLOAT32ABCDvarRead
HR19042Reactive power total (fundamental)Sum of L1-L3.FLOAT32ABCDvarRead
HR19044CosPhi L1 (fundamental)FLOAT32ABCDRead
HR19046CosPhi L2 (fundamental)FLOAT32ABCDRead
HR19048CosPhi L3 (fundamental)FLOAT32ABCDRead
HR19050FrequencyFLOAT32ABCDHzRead
HR19052Rotation fieldFloat: 1 = clockwise, 0 = none, -1 = anticlockwise.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1-L3Three-phase total, not split into consumed and delivered.FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1-L3, deliveredFLOAT32ABCDWhRead
HR19084Apparent energy L1-L3FLOAT32ABCDVAhRead
HR19092Reactive energy L1-L3 (fundamental)FLOAT32ABCDvarhRead
HR19100Reactive energy inductive L1-L3 (fundamental)FLOAT32ABCDvarhRead
HR19108Reactive energy capacitive L1-L3 (fundamental)FLOAT32ABCDvarhRead
HR19110THD voltage L1-NFLOAT32ABCD%Read
HR19112THD voltage L2-NFLOAT32ABCD%Read
HR19114THD voltage L3-NFLOAT32ABCD%Read
HR19116THD current L1FLOAT32ABCD%Read
HR19118THD current L2FLOAT32ABCD%Read
HR19120THD current L3FLOAT32ABCD%Read
HR19636Power factor totalTotal real power / total apparent power (L1-L3).FLOAT32ABCDRead/write
HR19716Transformer ratio lockINT16Read0 = Not locked; 1 = Locked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)

What Modbus registers does the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) have?

This map lists 72 registers: 72 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (real-time clock), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total (Total real power); HR 19636 Power factor total (Total power factor); HR 19050 Frequency (Frequency); HR 6508 Real energy L1-L3, consumed (Consumed real energy, all tariffs); HR 6520 Real energy L1-L3, delivered (Delivered real energy, all tariffs).

How do I enable Modbus control of the Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)?

The address list does not describe how to enable Modbus or pick the port; it only lists the RS-485 and IP settings rows (several marked internal use).

Where is the official Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus documentation?

The source is Power Quality Analyser UMG 512-PRO - Modbus-address and Formulary (1.054.016.3.k), revision 2023-08, published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG512-PRO/janitza-mal-umg512pro-en.pdf.

More Janitza Modbus register maps

Source: Power Quality Analyser UMG 512-PRO - Modbus-address and Formulary · 1.054.016.3.k · rev. 2023-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.