Power meter (power quality analyser) · Modbus register map

Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map

Updated 28 October 2026

Short answer

The UMG 509-PRO is a Janitza power quality analyser with a fourth voltage and current channel, an RS-485 port and network (IP) settings. Measurements are big-endian 32-bit floats; the 19000-19120 'frequently required readings' block is the same one used across Janitza meters. This map covers that block, the fourth channel, total power factor, consumed energy, digital I/O, transformer ratios and identity/network settings, with access rights as printed in the list.

This page lists 81 Modbus registers for the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
Equipment type
Power meter (power quality analyser)
Registers
81 (19 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509
Source document
Power Analyser UMG 509-PRO - Modbus-address and Formulary · 1.059.004.2.n · rev. 2024-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)

Integration in brief

Read holding registers (function 03) from 19000: 60 registers give volts, amps, power, CosPhi, frequency and per-phase energy as big-endian floats; 19060-19077 adds three-phase and delivered energy in Wh. Use Modbus TCP over Ethernet or RTU on RS-485.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Current L1FLOAT32 ABCDCurrent L1Read
HR 19026Real power total L1-L3FLOAT32 ABCDTotal real powerRead
HR 19034Apparent power total L1-L3FLOAT32 ABCDTotal apparent powerRead
HR 2109Power factor total L1-L3FLOAT32 ABCDTotal power factorRead
HR 19050FrequencyFLOAT32 ABCDFrequencyRead
HR 13995Real energy L1-L3, consumedFLOAT32 ABCDConsumed energy totalRead
HR 19076Real energy L1-L3, deliveredFLOAT32 ABCDDelivered energy totalRead

Enable Modbus control & writes

Modbus is available on Ethernet and on the RS-485 port. Set the Modbus address (14326) and IP/DHCP settings on the device or in GridVis.

Byte order & addressing

Network setup

Watch out for

Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

81 of 81 shown
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2059Voltage L4-NFourth voltage input.FLOAT32ABCDVRead
HR2067Current L4Fourth current input (measured neutral or extra feeder).FLOAT32ABCDARead
HR2109Power factor total L1-L3P sum / sqrt(P sum^2 + Q sum^2) over L1-L3.FLOAT32ABCDRead
HR2197Internal temperatureFLOAT32ABCD°CRead
HR13995Real energy L1-L3, consumedThree-phase consumed (import) energy total.FLOAT32ABCDWhRead
HR14117Digital output 1 statusINT16Read/write0 = Not active; 1 = Active
HR14118Digital output 2 statusINT16Read/write0 = Not active; 1 = Active
HR14119Digital input 1 statusINT16Read0 = Not active; 1 = Active
HR14120Digital input 2 statusINT16Read0 = Not active; 1 = Active
HR14176CT primary L1FLOAT32ABCDARead/write
HR14178CT primary L2FLOAT32ABCDARead/write
HR14180CT primary L3FLOAT32ABCDARead/write
HR14182CT primary L4FLOAT32ABCDARead/write
HR14184CT secondary L1FLOAT32ABCDARead/write
HR14186CT secondary L2FLOAT32ABCDARead/write
HR14188CT secondary L3FLOAT32ABCDARead/write
HR14190CT secondary L4FLOAT32ABCDARead/write
HR14192VT primary L1FLOAT32ABCDVRead/write
HR14194VT primary L2FLOAT32ABCDVRead/write
HR14196VT primary L3FLOAT32ABCDVRead/write
HR14200VT secondary L1FLOAT32ABCDVRead/write
HR14202VT secondary L2FLOAT32ABCDVRead/write
HR14204VT secondary L3FLOAT32ABCDVRead/write
HR14322Serial numberThe list marks this row 'only for internal use'.UINT32ABCDRead
HR14326RS-485 Modbus addressINT32ABCDRead/write
HR14332IP addressPacked 32-bit IPv4 address.UINT32ABCDRead
HR14334Subnet maskPacked 32-bit IPv4 mask.UINT32ABCDRead
HR14336Gateway addressPacked 32-bit IPv4 gateway.UINT32ABCDRead
HR14338DHCP modeINT32ABCDRead/write0 = DHCP off; 1 = DHCP on
HR14406Nominal frequencyFLOAT32ABCDHzRead
HR17435Firmware releaseText, 16 characters (8 registers).STRING[16]Read
HR17477Gateway timeoutReply timeout when the device acts as Modbus gateway/master.UINT32ABCDmsRead/write
HR17998Hardware indexINT32ABCDRead
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Current L1FLOAT32ABCDARead
HR19014Current L2FLOAT32ABCDARead
HR19016Current L3FLOAT32ABCDARead
HR19018Neutral current (vector sum L1-L3)Calculated vector sum of the three phase currents.FLOAT32ABCDARead
HR19020Real power L1FLOAT32ABCDWRead
HR19022Real power L2FLOAT32ABCDWRead
HR19024Real power L3FLOAT32ABCDWRead
HR19026Real power total L1-L3FLOAT32ABCDWRead
HR19028Apparent power L1FLOAT32ABCDVARead
HR19030Apparent power L2FLOAT32ABCDVARead
HR19032Apparent power L3FLOAT32ABCDVARead
HR19034Apparent power total L1-L3FLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental)FLOAT32ABCDvarRead
HR19042Reactive power total L1-L3 (fundamental)FLOAT32ABCDvarRead
HR19044CosPhi L1 (fundamental)FLOAT32ABCDRead
HR19046CosPhi L2 (fundamental)FLOAT32ABCDRead
HR19048CosPhi L3 (fundamental)FLOAT32ABCDRead
HR19050FrequencyFLOAT32ABCDHzRead
HR19052Rotation fieldFloat: 1 = clockwise, 0 = none, -1 = anticlockwise.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1-L3Three-phase total, not split into consumed and delivered.FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1-L3, deliveredFLOAT32ABCDWhRead
HR19084Apparent energy L1-L3FLOAT32ABCDVAhRead
HR19092Reactive energy L1-L3 (fundamental)FLOAT32ABCDvarhRead
HR19100Reactive energy inductive L1-L3FLOAT32ABCDvarhRead
HR19108Reactive energy capacitive L1-L3FLOAT32ABCDvarhRead
HR19110THD voltage L1-NFLOAT32ABCD%Read
HR19112THD voltage L2-NFLOAT32ABCD%Read
HR19114THD voltage L3-NFLOAT32ABCD%Read
HR19116THD current L1FLOAT32ABCD%Read
HR19118THD current L2FLOAT32ABCD%Read
HR19120THD current L3FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)

What Modbus registers does the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) have?

This map lists 81 registers: 81 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (system time), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total L1-L3 (Total real power); HR 19034 Apparent power total L1-L3 (Total apparent power); HR 2109 Power factor total L1-L3 (Total power factor); HR 19050 Frequency (Frequency); HR 13995 Real energy L1-L3, consumed (Consumed energy total); HR 19076 Real energy L1-L3, delivered (Delivered energy total).

How do I enable Modbus control of the Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)?

Modbus is available on Ethernet and on the RS-485 port. Set the Modbus address (14326) and IP/DHCP settings on the device or in GridVis.