Energy meter · Modbus register map

inepro Metering PRO2 single-phase energy meter (2026 PRO line) Modbus register map

Updated 17 November 2026

Short answer

The PRO2 is a MID-certified single-phase 100 A DIN-rail energy meter from inepro's 2026 PRO line; the -Mod versions add an RS485 Modbus RTU port. Live values are IEEE 754 floats (high word first) in input registers from hex 5000h, energy counters sit from 6000h and settings from 4000h. This map covers the default register map: instantaneous values, THD, demand peaks, energy totals and tariff registers (as floats) and the main communication and display settings.

This page lists 104 Modbus registers for the inepro Metering PRO2 single-phase energy meter (2026 PRO line) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.

Manufacturer
inepro Metering
Model
PRO2 single-phase energy meter (2026 PRO line)
Equipment type
Energy meter
Registers
104 (9 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202
Source document
PRO2 energy meter - Full User Manual EN · User manual version 1.3 · rev. 2026
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: inepro Metering PRO2 single-phase energy meter (2026 PRO line)

Integration in brief

Wire RS485 to terminals 9 (A) and 10 (B), poll unit 1 at 9600 baud 8E1 with function 04 and decode live values as high-word-first floats from 5000h. Write 2 to 4026h once (function 06) so the 6000h energy registers come back as floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 20482Voltage L1FLOAT32 ABCDVoltage L1Read
IR 20492Current L1FLOAT32 ABCDCurrent L1Read
IR 20498Total Active PowerFLOAT32 ABCDTotal active power (kW)Read
IR 20522Total Power FactorFLOAT32 ABCDTotal power factorRead
IR 20488Grid FrequencyFLOAT32 ABCDGrid frequencyRead
IR 24588Total Forward Active EnergyFLOAT32 ABCDTotal forward (import) active energyRead
IR 24600Total Reverse Active EnergyFLOAT32 ABCDTotal reverse (export) active energyRead
HR 16422Data format settingUINT16Switch energy registers to floatRead/write

Enable Modbus control & writes

Modbus is only on the -Mod and -Mod-Ba versions. Set ID, baud and parity on the display, with inepro's configuration software, or over Modbus at 4003h/4004h/4011h.

Byte order & addressing

Network setup

Watch out for

inepro Metering PRO2 single-phase energy meter (2026 PRO line) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

104 of 104 shown
inepro Metering PRO2 single-phase energy meter (2026 PRO line) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR16389doc 0X4005Protocol Version NumberFLOAT32ABCDRead
IR16391doc 0X4007Version NumberFLOAT32ABCDRead
IR16393doc 0X4009Hardware Version NumberFLOAT32ABCDRead
IR16395doc 0X400BMaximum currentCurrent rating of the meter.UINT16ARead
IR16421doc 0X4025Product codeUINT16Read
IR20096doc 0X4E80Year of manufactureUINT16Read
IR20482doc 0X5002Voltage L1FLOAT32ABCDVRead
IR20488doc 0X5008Grid FrequencyFLOAT32ABCDHzRead
IR20490doc 0X500ACurrentFLOAT32ABCDARead
IR20492doc 0X500CCurrent L1FLOAT32ABCDARead
IR20498doc 0X5012Total Active PowerFLOAT32ABCDkWRead
IR20500doc 0X5014Active Power L1FLOAT32ABCDkWRead
IR20506doc 0X501ATotal Reactive PowerFLOAT32ABCDkvarRead
IR20508doc 0X501CReactive Power L1FLOAT32ABCDkvarRead
IR20514doc 0X5022Total Apparent PowerFLOAT32ABCDRead
IR20516doc 0X5024Apparent Power L1FLOAT32ABCDkVARead
IR20522doc 0X502ATotal Power FactorFLOAT32ABCDRead
IR20524doc 0X502CPower Factor L1FLOAT32ABCDRead
IR20542doc 0X503ETHD+N Voltage L1FLOAT32ABCD%Read
IR20548doc 0X5044THD+N Current L1FLOAT32ABCD%Read
IR20554doc 0X504ATHD+N Average VoltageFLOAT32ABCD%Read
IR20556doc 0X504CTHD+N Average CurrentFLOAT32ABCD%Read
IR20576doc 0X5060Forward Active Power Demand PeakRead with function 04; reset by writing 0 here with function 16.FLOAT32ABCDkWRead
IR20578doc 0X5062Reverse Active Power Demand PeakRead with function 04; reset by writing 0 here with function 16.FLOAT32ABCDkWRead
IR24576doc 0X6000Total Active EnergyFloat only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24578doc 0X6002Total Active Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24580doc 0X6004Total Active Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24588doc 0X600CTotal Forward Active EnergyFloat only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24590doc 0X600ETotal Forward Active Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24592doc 0X6010Total Forward Active Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24600doc 0X6018Total Reverse Active EnergyFloat only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24602doc 0X601ATotal Reverse Active Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24604doc 0X601CTotal Reverse Active Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkWhRead
IR24612doc 0X6024Total Reactive EnergyFloat only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24614doc 0X6026Total Reactive Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24616doc 0X6028Total Reactive Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24624doc 0X6030Total Forward Reactive energyFloat only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24626doc 0X6032Total Forward Reactive Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24628doc 0X6034Total Forward Reactive Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24636doc 0X603CTotal Reverse Reactive energyFloat only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24638doc 0X603ETotal Reverse Reactive Energy DS-T1Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24640doc 0X6040Total Reverse Reactive Energy DS-T2Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24675doc 0X6063Import inductive reactive energy in Q1 (total)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24677doc 0X6065Import inductive reactive energy in Q1 (DS-T1)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24679doc 0X6067Import capacitive reactive energy in Q1 (DS-T2)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24685doc 0X606DImport capacitive reactive energy in Q2 (total)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24687doc 0X606FExport capacitive reactive energy in Q2 (DS-T1)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24689doc 0X6071Export inductive reactive energy in Q2 (DS-T2)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24695doc 0X6077Export inductive reactive energy in Q3 (total)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24697doc 0X6079Import capacitive reactive energy in Q3 (DS-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24699doc 0X607BImport inductive reactive energy in Q3 (DS-T2)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24705doc 0X6081Export capacitive reactive energy in Q4 (total)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24707doc 0X6083Export inductive reactive energy in Q4 (DS-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24709doc 0X6085Export capacitive reactive energy in Q4 (DS-T2)Float only after 4026h is set to 2.FLOAT32ABCDkvarhRead
IR24761doc 0X60B9Total Apparent energyFloat only after 4026h is set to 2.FLOAT32ABCDkVAhRead
IR24873doc 0X6129Import inductive reactive energy in Q1 (RTC-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24891doc 0X613BImport capacitive reactive energy in Q2 (RTC-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24893doc 0X613DExport inductive reactive energy in Q3 (RTC-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24895doc 0X613FExport capacitive reactive energy in Q4 (RTC-T1)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24897doc 0X6141Import inductive reactive energy in Q1 (RTC-T2)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24899doc 0X6143Import capacitive reactive energy in Q2 (RTC-T2)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24901doc 0X6145Export inductive reactive energy in Q3 (RTC-T2)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24903doc 0X6147Export capacitive reactive energy in Q4 (RTC-T2)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24905doc 0X6149Import inductive reactive energy in Q1 (RTC-T3)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24907doc 0X614BExport inductive reactive energy in Q2 (RTC-T3)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24909doc 0X614DImport capacitive reactive energy in Q3 (RTC-T3)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24911doc 0X614FExport capacitive reactive energy in Q4 (RTC-T3)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24913doc 0X6151Import inductive reactive energy in Q1 (RTC-T4)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24915doc 0X6153Export inductive reactive energy in Q2 (RTC-T4)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24917doc 0X6155Import capacitive reactive energy in Q3 (RTC-T4)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24919doc 0X6157Export capacitive reactive energy in Q4 (RTC-T4)Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24921doc 0X6159Total Forward Active Energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24939doc 0X616BTotal Forward Active Energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24941doc 0X616DTotal Forward Active Energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24943doc 0X616FTotal Forward Active Energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24945doc 0X6171Total Reverse Active Energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24947doc 0X6173Total Reverse Active Energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24949doc 0X6175Total Reverse Active Energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24951doc 0X6177Total Reverse Active Energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24953doc 0X6179Total Forward Reactive energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24971doc 0X618BTotal Forward Reactive energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24973doc 0X618DTotal Forward Reactive energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24975doc 0X618FTotal Forward Reactive energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24977doc 0X6191Total Reverse Reactive Energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24979doc 0X6193Total Reverse Reactive Energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24981doc 0X6195Total Reverse Reactive Energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24983doc 0X6197Total Reverse Reactive Energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR24985doc 0X6199Total Active Energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24987doc 0X619BTotal Active Energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24989doc 0X619DTotal Active Energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR24991doc 0X619FTotal Active Energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkWhRead
IR25089doc 0X6201Total Reactive Energy RTC-T1Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR25091doc 0X6203Total Reactive Energy RTC-T2Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR25093doc 0X6205Total Reactive Energy RTC-T3Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
IR25095doc 0X6207Total Reactive Energy RTC-T4Ba (RTC) variant only; float after 4026h = 2.FLOAT32ABCDkvarhRead
HR16387doc 0X4003Modbus IDSlave address 1-247; write with function 06.UINT16Read/write
HR16388doc 0X4004Baud rateBaud rate code.UINT16Read/write6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR16399doc 0X400FCombination codeHow forward and reverse energy are combined into total energy.UINT16Read/write1 = Forward only (mode C); 2 = Reverse only (mode D); 3 = Forward + reverse (mode A, default); 4 = Forward - reverse (mode B)
HR16400doc 0X4010LCD cycle timeDisplay scroll time 0-30 s; 0 keeps the home page.UINT16sRead/write
HR16401doc 0X4011ParityUINT16Read/write1 = Even; 2 = None; 3 = Odd
HR16422doc 0X4026Data format settingSelects INT32 or float encoding for the energy registers.UINT16Read/write1 = INT32 (default); 2 = FLOAT
HR16757doc 0X4175Demand intervalPower demand interval in minutes: 1, 5, 10, 15 (default), 20, 30 or 60.UINT16minRead/write
HR19458doc 0X4C02Backlight modeUINT16Read/write0 = Always on; 1 = Off; 2 = On at button press (default)
HR19460doc 0X4C04Backlight timeBacklight on-time after a button press (button mode only).UINT16Read/write1 = 1 min (default); 2 = 2 min; 3 = 5 min; 4 = 10 min; 5 = 15 min; 6 = 30 min; 7 = 60 min

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the inepro Metering PRO2 single-phase energy meter (2026 PRO line)

What Modbus registers does the inepro Metering PRO2 single-phase energy meter (2026 PRO line) have?

This map lists 104 registers: 95 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the inepro Metering PRO2 single-phase energy meter (2026 PRO line) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints hex addresses that go into the request unchanged; the manual's example frames are 01 06 4003 000A (set Modbus ID) and 01 10 5060 0002 ... (reset demand peak). So 5012h is wire address 20498. Rows typed 'input' are read with function 04; rows typed 'input /holding' are listed here as holding registers (read 03, write 06/16).

What byte order does the inepro Metering PRO2 single-phase energy meter (2026 PRO line) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the inepro Metering PRO2 single-phase energy meter (2026 PRO line)?

Start with IR 20482 Voltage L1 (Voltage L1); IR 20492 Current L1 (Current L1); IR 20498 Total Active Power (Total active power (kW)); IR 20522 Total Power Factor (Total power factor); IR 20488 Grid Frequency (Grid frequency); IR 24588 Total Forward Active Energy (Total forward (import) active energy); IR 24600 Total Reverse Active Energy (Total reverse (export) active energy); HR 16422 Data format setting (Switch energy registers to float).

How do I enable Modbus control of the inepro Metering PRO2 single-phase energy meter (2026 PRO line)?

Modbus is only on the -Mod and -Mod-Ba versions. Set ID, baud and parity on the display, with inepro's configuration software, or over Modbus at 4003h/4004h/4011h.

Where is the official inepro Metering PRO2 single-phase energy meter (2026 PRO line) Modbus documentation?