Energy meter · Modbus register map

inepro Metering PRO380-Eichrecht three-phase energy meter Modbus register map

Updated 17 November 2026

Short answer

The PRO380-Eichrecht is inepro's German calibration-law (Eichrecht) version of the PRO380, built into AC EV chargers. It has two RS485 Modbus RTU ports: RS485-1 for full access and RS485-2 as a read-only secondary. All registers are holding registers at hex addresses; live values are FLOAT32 in V, A, W, var and VA, and energy counters are INT32 in Wh by default. This map has its own register set and differs from the PRO380-Mod map.

This page lists 149 Modbus registers for the inepro Metering PRO380-Eichrecht three-phase energy meter — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.

Manufacturer
inepro Metering
Model
PRO380-Eichrecht three-phase energy meter
Equipment type
Energy meter
Registers
149 (17 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht
Source document
PRO380-Eichrecht electricity meter - Full user manual EN · User Manual PRO380-Eichrecht Version 1.45 · rev. 2025-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: inepro Metering PRO380-Eichrecht three-phase energy meter

Integration in brief

Connect to RS485-1 (terminals 22/23), poll unit 1 at 9600 baud, even parity with function 03. Read live values as ABCD floats from 5000h and energy as big-endian INT32 Wh from 6000h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20482Voltage L1FLOAT32 ABCDVoltage L1Read
HR 20492Current L1FLOAT32 ABCDCurrent L1Read
HR 20498Total Active PowerFLOAT32 ABCDTotal active power (W)Read
HR 20522Power FactorFLOAT32 ABCDPower factorRead
HR 20488Grid FrequencyFLOAT32 ABCDGrid frequencyRead
HR 24588Forward Active EnergyINT32 ABCDForward (import) active energyRead
HR 24600Reverse Active EnergyINT32 ABCDReverse (export) active energyRead
HR 16405Error codeBITMAP16Error bitfieldRead

Enable Modbus control & writes

No enable step is described. Settings (ID, baud, parity, energy data type, combination code) can be written over Modbus or with inepro's EichrechtMeterConfig tool.

Byte order & addressing

Network setup

Watch out for

inepro Metering PRO380-Eichrecht three-phase energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

149 of 149 shown
inepro Metering PRO380-Eichrecht three-phase energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR16387doc 0x4003Modbus IDDevice address 1-247.INT16Read/write
HR16388doc 0x4004Baud rateBaud rate code.INT16Read/write3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR16389doc 0x4005Protocol versionCOM firmware version, e.g. 1.0.FLOAT32ABCDRead
HR16391doc 0x4007Software versionMID firmware version.FLOAT32ABCDRead
HR16393doc 0x4009Hardware versionFLOAT32ABCDRead
HR16395doc 0x400bMeter ampsMaximum current Imax, e.g. 40 A.INT16ARead
HR16399doc 0x400fCombination codeHow forward and reverse energy are combined into the total counters.INT16Read/write1 = Forward only; 2 = Reverse only; 3 = Forward + reverse; 4 = Forward - reverse
HR16400doc 0x4010LCD cycle timeMinimum display time per LCD message (default 3 s).INT16sRead/write
HR16401doc 0x4011ParityINT16Read/write1 = Even; 2 = None; 3 = Odd
HR16405doc 0x4015Error codeError bitfield; also shown on the LCD.BITMAP16Readbit 0 = MID firmware CRC error; bit 1 = EEPROM communication error; bit 2 = EEPROM data corruption; bit 3 = Measurement hardware error; bit 4 = Meter failed to calibrate; bit 7 = Production not marked completed; bit 8 = Firmware CRC error; bit 9 = Provisioning data error
HR16406doc 0x4016Power on/off counterPower cycle count; write 0 to clear.INT16Read/write
HR16407doc 0x4017Total power quadrantQuadrant 1-4 of total power.INT16Read
HR16408doc 0x4018L1 power quadrantQuadrant 1-4.INT16Read
HR16409doc 0x4019L2 power quadrantQuadrant 1-4.INT16Read
HR16410doc 0x401aL3 power quadrantQuadrant 1-4.INT16Read
HR16422doc 0x4026Energy data typeEncoding of the energy counters 6000h-6FFFh.INT16Read/write0 = FLOAT32 (kWh); 1 = INT32 (Wh, default)
HR16512doc 0x4080Measurement update checkINT16Read0 = Busy; 1 = Measurement data ready
HR16514doc 0x4082Phase order error statusINT16Read0 = OK; 1 = Invalid phase order
HR16515doc 0x40833-wire detection statusDetected connection type.INT16Read0 = 3P4W; 1 = 3P3W
HR16752doc 0x4170Measurement intervalInternal update interval (default 300 ms).INT16Read/write0 = 600 ms; 1 = 300 ms; 2 = 100 ms; 3 = 50 ms
HR16753doc 0x4171Backlight level0-100.INT16%Read/write
HR16754doc 0x4172Power factor sign modeINT16Read/write0 = IEC; 1 = IEEE; 2 = Positive
HR16755doc 0x4173MID firmware updatesINT16Read/write0 = Allowed; 1 = Disabled
HR16756doc 0x4174COM firmware updatesINT16Read/write0 = Allowed; 1 = Disabled
HR16757doc 0x4175Peak power intervalPeak detection interval in minutes; 0 = off, 1-60 (default 15).INT16minRead/write
HR20480doc 0x5000VoltageFLOAT32ABCDVRead
HR20482doc 0x5002Voltage L1FLOAT32ABCDVRead
HR20484doc 0x5004Voltage L2FLOAT32ABCDVRead
HR20486doc 0x5006Voltage L3FLOAT32ABCDVRead
HR20488doc 0x5008Grid FrequencyFLOAT32ABCDHzRead
HR20490doc 0x500aCurrentFLOAT32ABCDARead
HR20492doc 0x500cCurrent L1FLOAT32ABCDARead
HR20494doc 0x500eCurrent L2FLOAT32ABCDARead
HR20496doc 0x5010Current L3FLOAT32ABCDARead
HR20498doc 0x5012Total Active PowerFLOAT32ABCDWRead
HR20500doc 0x5014Active Power L1FLOAT32ABCDWRead
HR20502doc 0x5016Active Power L2FLOAT32ABCDWRead
HR20504doc 0x5018Active Power L3FLOAT32ABCDWRead
HR20506doc 0x501aTotal reactive powerFLOAT32ABCDvarRead
HR20508doc 0x501cL1 reactive powerFLOAT32ABCDvarRead
HR20510doc 0x501eL2 reactive powerFLOAT32ABCDvarRead
HR20512doc 0x5020L3 reactive powerFLOAT32ABCDvarRead
HR20514doc 0x5022Total Apparent PowerFLOAT32ABCDVARead
HR20516doc 0x5024L1 Apparent PowerFLOAT32ABCDVARead
HR20518doc 0x5026L2 Apparent PowerFLOAT32ABCDVARead
HR20520doc 0x5028L3 Apparent PowerFLOAT32ABCDVARead
HR20522doc 0x502aPower FactorFLOAT32ABCDRead
HR20524doc 0x502cL1 Power FactorFLOAT32ABCDRead
HR20526doc 0x502eL2 Power FactorFLOAT32ABCDRead
HR20528doc 0x5030L3 Power FactorFLOAT32ABCDRead
HR20530doc 0x5032L1-L2 VoltageFLOAT32ABCDVRead
HR20532doc 0x5034L1-L3 VoltageFLOAT32ABCDVRead
HR20534doc 0x5036L2-L3 VoltageFLOAT32ABCDVRead
HR20536doc 0x5038LL Average VoltageFLOAT32ABCDVRead
HR20538doc 0x503aNeutral CurrentFLOAT32ABCDARead
HR20540doc 0x503cTemperatureFLOAT32ABCD°CRead
HR20542doc 0x503eL1 Voltage THDFLOAT32ABCD%Read
HR20544doc 0x5040L2 Voltage THDFLOAT32ABCD%Read
HR20546doc 0x5042L3 Voltage THDFLOAT32ABCD%Read
HR20548doc 0x5044L1 Current THDFLOAT32ABCD%Read
HR20550doc 0x5046L2 Current THDFLOAT32ABCD%Read
HR20552doc 0x5048L3 Current THDFLOAT32ABCD%Read
HR20576doc 0x5060Forward Active Power PeakWrite 0 to clear.FLOAT32ABCDWRead/write
HR20578doc 0x5062Reverse Active Power PeakWrite 0 to clear.FLOAT32ABCDWRead/write
HR20580doc 0x5064Previous Forward Active Power PeakValue before the last clear.FLOAT32ABCDWRead
HR20582doc 0x5066Previous Forward Active Power PeakValue before the last clear.FLOAT32ABCDWRead
HR20608doc 0x5080Minutes above 70 degreesINT32ABCDminRead
HR20610doc 0x5082Minutes above max currentINT32ABCDminRead
HR24576doc 0x6000Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24578doc 0x6002T1 Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24580doc 0x6004T2 Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24582doc 0x6006L1 Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24584doc 0x6008L2 Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24586doc 0x600aL3 Total Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24588doc 0x600cForward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24590doc 0x600eT1 Forward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24592doc 0x6010T2 Forward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24594doc 0x6012L1 Forward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24596doc 0x6014L2 Forward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24598doc 0x6016L3 Forward Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24600doc 0x6018Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24602doc 0x601aT1 Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24604doc 0x601cT2 Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24606doc 0x601eL1 Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24608doc 0x6020L2 Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24610doc 0x6022L3 Reverse Active EnergyINT32 Wh when 4026h = 1 (default).INT32ABCDWhRead
HR24612doc 0x6024Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24614doc 0x6026T1 Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24616doc 0x6028T2 Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24618doc 0x602aL1 Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24620doc 0x602cL2 Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24622doc 0x602eL3 Total Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24624doc 0x6030Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24626doc 0x6032T1 Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24628doc 0x6034T2 Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24630doc 0x6036L1 Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24632doc 0x6038L2 Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24634doc 0x603aL3 Forward Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24636doc 0x603cReverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24638doc 0x603eT1 Reverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24640doc 0x6040T2 Reverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24642doc 0x6042L1 Reverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24644doc 0x6044L2 Reverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24646doc 0x6046L3 Reverse Reactive EnergyINT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24648doc 0x6048TariffActive tariff.INT16Read/write0 = T1; 1 = T2
HR24649doc 0x6049Resettable day counterWrite 0 to clear the day counter.INT32ABCDWhRead/write
HR24675doc 0x6063Reactive Energy Q1 (total)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24677doc 0x6065Reactive Energy Q1 (T1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24679doc 0x6067Reactive Energy Q1 (T2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24685doc 0x606dReactive Energy Q2 (total)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24687doc 0x606fReactive Energy Q2 (T1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24689doc 0x6071Reactive Energy Q2 (T2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24695doc 0x6077Reactive Energy Q3 (total)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24697doc 0x6079Reactive Energy Q3 (T1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24699doc 0x607bReactive Energy Q3 (T2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24705doc 0x6081Reactive Energy Q4 (total)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24707doc 0x6083Reactive Energy Q4 (T1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24709doc 0x6085Reactive Energy Q4 (T2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24721doc 0x6091Reactive Energy Q1 (L1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24723doc 0x6093Reactive Energy Q1 (L2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24725doc 0x6095Reactive Energy Q1 (L3)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24727doc 0x6097Reactive Energy Q2 (L1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24729doc 0x6099Reactive Energy Q2 (L2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24731doc 0x609bReactive Energy Q2 (L3)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24733doc 0x609dReactive Energy Q3 (L1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24735doc 0x609fReactive Energy Q3 (L2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24737doc 0x60a1Reactive Energy Q3 (L3)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24739doc 0x60a3Reactive Energy Q4 (L1)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24741doc 0x60a5Reactive Energy Q4 (L2)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24743doc 0x60a7Reactive Energy Q4 (L3)INT32 when 4026h = 1 (default).INT32ABCDvarhRead
HR24745doc 0x60a9Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24747doc 0x60abT1 Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24749doc 0x60adT2 Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24751doc 0x60afL1 Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24833doc 0x6101L2 Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24835doc 0x6103L3 Total Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24837doc 0x6105Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24839doc 0x6107T1 Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24841doc 0x6109T2 Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24843doc 0x610bL1 Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24845doc 0x610dL2 Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24847doc 0x610fL3 Forward Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24849doc 0x6111Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24851doc 0x6113T1 Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24853doc 0x6115T2 Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24855doc 0x6117L1 Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24857doc 0x6119L2 Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR24859doc 0x611bL3 Reverse Apparent EnergyINT32 when 4026h = 1 (default).INT32ABCDVAhRead
HR25088doc 0x6200Previous day counterDay counter value before the last clear.INT32ABCDWhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the inepro Metering PRO380-Eichrecht three-phase energy meter

What Modbus registers does the inepro Metering PRO380-Eichrecht three-phase energy meter have?

This map lists 149 registers: 149 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the inepro Metering PRO380-Eichrecht three-phase energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map is headed 'Holding register address (hex)'. The hex value goes on the wire unchanged, so 0x5012 (total active power) is decimal 20498, read with function 03.

What byte order does the inepro Metering PRO380-Eichrecht three-phase energy meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the inepro Metering PRO380-Eichrecht three-phase energy meter?

Start with HR 20482 Voltage L1 (Voltage L1); HR 20492 Current L1 (Current L1); HR 20498 Total Active Power (Total active power (W)); HR 20522 Power Factor (Power factor); HR 20488 Grid Frequency (Grid frequency); HR 24588 Forward Active Energy (Forward (import) active energy); HR 24600 Reverse Active Energy (Reverse (export) active energy); HR 16405 Error code (Error bitfield).

How do I enable Modbus control of the inepro Metering PRO380-Eichrecht three-phase energy meter?

No enable step is described. Settings (ID, baud, parity, energy data type, combination code) can be written over Modbus or with inepro's EichrechtMeterConfig tool.

Where is the official inepro Metering PRO380-Eichrecht three-phase energy meter Modbus documentation?

The source is PRO380-Eichrecht electricity meter - Full user manual EN (User Manual PRO380-Eichrecht Version 1.45), revision 2025-09, published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/68d24b7e4c7016ae54d2bc9a_PRO380-Eichrecht%20electricity%20meter%20-%20Full%20user%20manual%20EN.pdf.

More inepro Metering Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PRO380-Eichrecht electricity meter - Full user manual EN · User Manual PRO380-Eichrecht Version 1.45 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.