Energy meter · Modbus register map
inepro Metering PRO380-Eichrecht three-phase energy meter Modbus register map
Updated 17 November 2026
The PRO380-Eichrecht is inepro's German calibration-law (Eichrecht) version of the PRO380, built into AC EV chargers. It has two RS485 Modbus RTU ports: RS485-1 for full access and RS485-2 as a read-only secondary. All registers are holding registers at hex addresses; live values are FLOAT32 in V, A, W, var and VA, and energy counters are INT32 in Wh by default. This map has its own register set and differs from the PRO380-Mod map.
This page lists 149 Modbus registers for the inepro Metering PRO380-Eichrecht three-phase energy meter — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.
- Manufacturer
- inepro Metering
- Model
- PRO380-Eichrecht three-phase energy meter
- Equipment type
- Energy meter
- Registers
- 149 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht
Integration notes: inepro Metering PRO380-Eichrecht three-phase energy meter
Connect to RS485-1 (terminals 22/23), poll unit 1 at 9600 baud, even parity with function 03. Read live values as ABCD floats from 5000h and energy as big-endian INT32 Wh from 6000h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20482 | Voltage L1 | FLOAT32 ABCD | Voltage L1 | Read |
| HR 20492 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 20498 | Total Active Power | FLOAT32 ABCD | Total active power (W) | Read |
| HR 20522 | Power Factor | FLOAT32 ABCD | Power factor | Read |
| HR 20488 | Grid Frequency | FLOAT32 ABCD | Grid frequency | Read |
| HR 24588 | Forward Active Energy | INT32 ABCD | Forward (import) active energy | Read |
| HR 24600 | Reverse Active Energy | INT32 ABCD | Reverse (export) active energy | Read |
| HR 16405 | Error code | BITMAP16 | Error bitfield | Read |
Enable Modbus control & writes
No enable step is described. Settings (ID, baud, parity, energy data type, combination code) can be written over Modbus or with inepro's EichrechtMeterConfig tool.
Byte order & addressing
- Addresses are hex: 0x5012 is decimal 20498.
- Power is in W/var/VA here, unlike the PRO380-Mod which reports kW.
- Energy is INT32 Wh by default; setting 4026h = 0 switches to FLOAT32 kWh, which keeps only about 6 significant digits.
- Baud rate is written as a code (6 = 9600), not as the number.
Network setup
- RS485-1 A/B on terminals 22/23 is the primary port; RS485-2 on 24/25 is read-only.
- Defaults: Modbus ID 1, 9600 baud, even parity.
- The optical port uses fixed settings: 4800 baud, even parity, ID 1.
Watch out for
- Forward and reverse counters are always positive; the combination code only affects the total counters, not power.
inepro Metering PRO380-Eichrecht three-phase energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 16387doc 0x4003 | Modbus ID | Device address 1-247. | INT16 | Read/write | ||||
| HR | 16388doc 0x4004 | Baud rate | Baud rate code. | INT16 | Read/write | 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | |||
| HR | 16389doc 0x4005 | Protocol version | COM firmware version, e.g. 1.0. | FLOAT32 | ABCD | Read | |||
| HR | 16391doc 0x4007 | Software version | MID firmware version. | FLOAT32 | ABCD | Read | |||
| HR | 16393doc 0x4009 | Hardware version | FLOAT32 | ABCD | Read | ||||
| HR | 16395doc 0x400b | Meter amps | Maximum current Imax, e.g. 40 A. | INT16 | A | Read | |||
| HR | 16399doc 0x400f | Combination code | How forward and reverse energy are combined into the total counters. | INT16 | Read/write | 1 = Forward only; 2 = Reverse only; 3 = Forward + reverse; 4 = Forward - reverse | |||
| HR | 16400doc 0x4010 | LCD cycle time | Minimum display time per LCD message (default 3 s). | INT16 | s | Read/write | |||
| HR | 16401doc 0x4011 | Parity | INT16 | Read/write | 1 = Even; 2 = None; 3 = Odd | ||||
| HR | 16405doc 0x4015 | Error code | Error bitfield; also shown on the LCD. | BITMAP16 | Read | bit 0 = MID firmware CRC error; bit 1 = EEPROM communication error; bit 2 = EEPROM data corruption; bit 3 = Measurement hardware error; bit 4 = Meter failed to calibrate; bit 7 = Production not marked completed; bit 8 = Firmware CRC error; bit 9 = Provisioning data error | |||
| HR | 16406doc 0x4016 | Power on/off counter | Power cycle count; write 0 to clear. | INT16 | Read/write | ||||
| HR | 16407doc 0x4017 | Total power quadrant | Quadrant 1-4 of total power. | INT16 | Read | ||||
| HR | 16408doc 0x4018 | L1 power quadrant | Quadrant 1-4. | INT16 | Read | ||||
| HR | 16409doc 0x4019 | L2 power quadrant | Quadrant 1-4. | INT16 | Read | ||||
| HR | 16410doc 0x401a | L3 power quadrant | Quadrant 1-4. | INT16 | Read | ||||
| HR | 16422doc 0x4026 | Energy data type | Encoding of the energy counters 6000h-6FFFh. | INT16 | Read/write | 0 = FLOAT32 (kWh); 1 = INT32 (Wh, default) | |||
| HR | 16512doc 0x4080 | Measurement update check | INT16 | Read | 0 = Busy; 1 = Measurement data ready | ||||
| HR | 16514doc 0x4082 | Phase order error status | INT16 | Read | 0 = OK; 1 = Invalid phase order | ||||
| HR | 16515doc 0x4083 | 3-wire detection status | Detected connection type. | INT16 | Read | 0 = 3P4W; 1 = 3P3W | |||
| HR | 16752doc 0x4170 | Measurement interval | Internal update interval (default 300 ms). | INT16 | Read/write | 0 = 600 ms; 1 = 300 ms; 2 = 100 ms; 3 = 50 ms | |||
| HR | 16753doc 0x4171 | Backlight level | 0-100. | INT16 | % | Read/write | |||
| HR | 16754doc 0x4172 | Power factor sign mode | INT16 | Read/write | 0 = IEC; 1 = IEEE; 2 = Positive | ||||
| HR | 16755doc 0x4173 | MID firmware updates | INT16 | Read/write | 0 = Allowed; 1 = Disabled | ||||
| HR | 16756doc 0x4174 | COM firmware updates | INT16 | Read/write | 0 = Allowed; 1 = Disabled | ||||
| HR | 16757doc 0x4175 | Peak power interval | Peak detection interval in minutes; 0 = off, 1-60 (default 15). | INT16 | min | Read/write | |||
| HR | 20480doc 0x5000 | Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20482doc 0x5002 | Voltage L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 20484doc 0x5004 | Voltage L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 20486doc 0x5006 | Voltage L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 20488doc 0x5008 | Grid Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 20490doc 0x500a | Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20492doc 0x500c | Current L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 20494doc 0x500e | Current L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 20496doc 0x5010 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 20498doc 0x5012 | Total Active Power | FLOAT32 | ABCD | W | Read | |||
| HR | 20500doc 0x5014 | Active Power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 20502doc 0x5016 | Active Power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 20504doc 0x5018 | Active Power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 20506doc 0x501a | Total reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 20508doc 0x501c | L1 reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 20510doc 0x501e | L2 reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 20512doc 0x5020 | L3 reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 20514doc 0x5022 | Total Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 20516doc 0x5024 | L1 Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 20518doc 0x5026 | L2 Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 20520doc 0x5028 | L3 Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 20522doc 0x502a | Power Factor | FLOAT32 | ABCD | Read | ||||
| HR | 20524doc 0x502c | L1 Power Factor | FLOAT32 | ABCD | Read | ||||
| HR | 20526doc 0x502e | L2 Power Factor | FLOAT32 | ABCD | Read | ||||
| HR | 20528doc 0x5030 | L3 Power Factor | FLOAT32 | ABCD | Read | ||||
| HR | 20530doc 0x5032 | L1-L2 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20532doc 0x5034 | L1-L3 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20534doc 0x5036 | L2-L3 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20536doc 0x5038 | LL Average Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20538doc 0x503a | Neutral Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20540doc 0x503c | Temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 20542doc 0x503e | L1 Voltage THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20544doc 0x5040 | L2 Voltage THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20546doc 0x5042 | L3 Voltage THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20548doc 0x5044 | L1 Current THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20550doc 0x5046 | L2 Current THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20552doc 0x5048 | L3 Current THD | FLOAT32 | ABCD | % | Read | |||
| HR | 20576doc 0x5060 | Forward Active Power Peak | Write 0 to clear. | FLOAT32 | ABCD | W | Read/write | ||
| HR | 20578doc 0x5062 | Reverse Active Power Peak | Write 0 to clear. | FLOAT32 | ABCD | W | Read/write | ||
| HR | 20580doc 0x5064 | Previous Forward Active Power Peak | Value before the last clear. | FLOAT32 | ABCD | W | Read | ||
| HR | 20582doc 0x5066 | Previous Forward Active Power Peak | Value before the last clear. | FLOAT32 | ABCD | W | Read | ||
| HR | 20608doc 0x5080 | Minutes above 70 degrees | INT32 | ABCD | min | Read | |||
| HR | 20610doc 0x5082 | Minutes above max current | INT32 | ABCD | min | Read | |||
| HR | 24576doc 0x6000 | Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24578doc 0x6002 | T1 Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24580doc 0x6004 | T2 Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24582doc 0x6006 | L1 Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24584doc 0x6008 | L2 Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24586doc 0x600a | L3 Total Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24588doc 0x600c | Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24590doc 0x600e | T1 Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24592doc 0x6010 | T2 Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24594doc 0x6012 | L1 Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24596doc 0x6014 | L2 Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24598doc 0x6016 | L3 Forward Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24600doc 0x6018 | Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24602doc 0x601a | T1 Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24604doc 0x601c | T2 Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24606doc 0x601e | L1 Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24608doc 0x6020 | L2 Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24610doc 0x6022 | L3 Reverse Active Energy | INT32 Wh when 4026h = 1 (default). | INT32 | ABCD | Wh | Read | ||
| HR | 24612doc 0x6024 | Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24614doc 0x6026 | T1 Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24616doc 0x6028 | T2 Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24618doc 0x602a | L1 Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24620doc 0x602c | L2 Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24622doc 0x602e | L3 Total Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24624doc 0x6030 | Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24626doc 0x6032 | T1 Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24628doc 0x6034 | T2 Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24630doc 0x6036 | L1 Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24632doc 0x6038 | L2 Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24634doc 0x603a | L3 Forward Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24636doc 0x603c | Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24638doc 0x603e | T1 Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24640doc 0x6040 | T2 Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24642doc 0x6042 | L1 Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24644doc 0x6044 | L2 Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24646doc 0x6046 | L3 Reverse Reactive Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24648doc 0x6048 | Tariff | Active tariff. | INT16 | Read/write | 0 = T1; 1 = T2 | |||
| HR | 24649doc 0x6049 | Resettable day counter | Write 0 to clear the day counter. | INT32 | ABCD | Wh | Read/write | ||
| HR | 24675doc 0x6063 | Reactive Energy Q1 (total) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24677doc 0x6065 | Reactive Energy Q1 (T1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24679doc 0x6067 | Reactive Energy Q1 (T2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24685doc 0x606d | Reactive Energy Q2 (total) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24687doc 0x606f | Reactive Energy Q2 (T1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24689doc 0x6071 | Reactive Energy Q2 (T2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24695doc 0x6077 | Reactive Energy Q3 (total) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24697doc 0x6079 | Reactive Energy Q3 (T1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24699doc 0x607b | Reactive Energy Q3 (T2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24705doc 0x6081 | Reactive Energy Q4 (total) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24707doc 0x6083 | Reactive Energy Q4 (T1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24709doc 0x6085 | Reactive Energy Q4 (T2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24721doc 0x6091 | Reactive Energy Q1 (L1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24723doc 0x6093 | Reactive Energy Q1 (L2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24725doc 0x6095 | Reactive Energy Q1 (L3) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24727doc 0x6097 | Reactive Energy Q2 (L1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24729doc 0x6099 | Reactive Energy Q2 (L2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24731doc 0x609b | Reactive Energy Q2 (L3) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24733doc 0x609d | Reactive Energy Q3 (L1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24735doc 0x609f | Reactive Energy Q3 (L2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24737doc 0x60a1 | Reactive Energy Q3 (L3) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24739doc 0x60a3 | Reactive Energy Q4 (L1) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24741doc 0x60a5 | Reactive Energy Q4 (L2) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24743doc 0x60a7 | Reactive Energy Q4 (L3) | INT32 when 4026h = 1 (default). | INT32 | ABCD | varh | Read | ||
| HR | 24745doc 0x60a9 | Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24747doc 0x60ab | T1 Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24749doc 0x60ad | T2 Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24751doc 0x60af | L1 Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24833doc 0x6101 | L2 Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24835doc 0x6103 | L3 Total Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24837doc 0x6105 | Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24839doc 0x6107 | T1 Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24841doc 0x6109 | T2 Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24843doc 0x610b | L1 Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24845doc 0x610d | L2 Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24847doc 0x610f | L3 Forward Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24849doc 0x6111 | Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24851doc 0x6113 | T1 Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24853doc 0x6115 | T2 Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24855doc 0x6117 | L1 Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24857doc 0x6119 | L2 Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 24859doc 0x611b | L3 Reverse Apparent Energy | INT32 when 4026h = 1 (default). | INT32 | ABCD | VAh | Read | ||
| HR | 25088doc 0x6200 | Previous day counter | Day counter value before the last clear. | INT32 | ABCD | Wh | Read |
Notes on this map
- Energy data type (configurator section): default INT32, big-endian 32-bit integers in 1 Wh units over two holding registers; the alternative FLOAT32 is 'float ABCD' in kWh. Switch with 4026h (0 = FLOAT32, 1 = INT32). The energy rows here assume the default INT32.
- Word order for the FLOAT32 live values is taken from the manual's description of its FLOAT32 type as 'float ABCD' (high word first).
- The map prints the unit 'var' for reactive energy counters 6024h-6046h; they are energy counters and are listed here as varh, as on the quadrant rows (6063h on).
- Left out: serial number and product id (packed BCD), meter code (marked TODO in the manual), phase direction (ASCII), CT ratio and S0 output rate (marked not used), checksums and active status word, LCD custom fields, the waveform sample buffer (47FDh-4800h) and the blocking 'update wait' register 4081h.
- Two power-peak registers (5064h and 5066h) are both named 'Previous Forward Active Power Peak' in the source; 5066h is most likely the reverse one, but the name is copied as printed.
- The RS485 spec lists baud rates 1200-115200, address range 0-247 and up to 31 meters per bus.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the inepro Metering PRO380-Eichrecht three-phase energy meter
What Modbus registers does the inepro Metering PRO380-Eichrecht three-phase energy meter have?
This map lists 149 registers: 149 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the inepro Metering PRO380-Eichrecht three-phase energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map is headed 'Holding register address (hex)'. The hex value goes on the wire unchanged, so 0x5012 (total active power) is decimal 20498, read with function 03.
What byte order does the inepro Metering PRO380-Eichrecht three-phase energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the inepro Metering PRO380-Eichrecht three-phase energy meter?
Start with HR 20482 Voltage L1 (Voltage L1); HR 20492 Current L1 (Current L1); HR 20498 Total Active Power (Total active power (W)); HR 20522 Power Factor (Power factor); HR 20488 Grid Frequency (Grid frequency); HR 24588 Forward Active Energy (Forward (import) active energy); HR 24600 Reverse Active Energy (Reverse (export) active energy); HR 16405 Error code (Error bitfield).
How do I enable Modbus control of the inepro Metering PRO380-Eichrecht three-phase energy meter?
No enable step is described. Settings (ID, baud, parity, energy data type, combination code) can be written over Modbus or with inepro's EichrechtMeterConfig tool.
Where is the official inepro Metering PRO380-Eichrecht three-phase energy meter Modbus documentation?
The source is PRO380-Eichrecht electricity meter - Full user manual EN (User Manual PRO380-Eichrecht Version 1.45), revision 2025-09, published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/68d24b7e4c7016ae54d2bc9a_PRO380-Eichrecht%20electricity%20meter%20-%20Full%20user%20manual%20EN.pdf.
More inepro Metering Modbus register maps
- Energy meter
inepro Metering 4PU / 4PS three-phase energy meter
4PU (meter code 1111) and 4PS (1112) MID three-phase DIN-rail meters with Modbus, user manual version 1.03 (2025).
Also known as: 4PU, 4PS, inepro 4PU, inepro 4PS - Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Energy meter
inepro Metering PRO380-Mod three-phase energy meter
PRO380-Mod and PRO380-Mod CT (RS485 Modbus RTU), current register map from PRO380 user manual version 2.18-8.
Also known as: PRO380 Mod, PRO380-Mod CT, PRO380-MOD, inepro PRO380, PRO380 MID
Other power & energy meters register maps
- Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E - Energy meter
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Legrand 2-module DIN energy meters cat. no. 046 77 and 046 79 with RS485 (Modbus/JBUS), per the 'Communication protocol' sheet dated 01/07/2011.
Also known as: 04677, 04679, 046 77, 046 79, Legrand 4 677, Legrand 4 679 - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H
All power & energy meters Modbus register maps →
Source: PRO380-Eichrecht electricity meter - Full user manual EN · User Manual PRO380-Eichrecht Version 1.45 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.