Easy Modbus
  1. Home
  2. Modbus register maps
  3. Panasonic
  4. KW8M Eco-POWER METER

Energy meter · Modbus register map

Panasonic KW8M Eco-POWER METER Modbus register map

Updated 17 November 2026

Short answer

The KW8M is a panel-mount energy meter for single- and three-phase circuits with a pulse counter input and an RS485 port running MEWTOCOL or Modbus RTU. Holding registers carry energy, current, voltage, power, PF, frequency, load on/off hours and pulse counts; the AKW8111H adds demand values and logging. This map covers the common table and the H-only demand and status registers.

This page lists 41 Modbus registers for the Panasonic KW8M Eco-POWER METER — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.

Manufacturer
Panasonic
Model
KW8M Eco-POWER METER
Equipment type
Energy meter
Registers
41 (27 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8O1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
AKW8111, AKW8111H
Source document
KW8M Eco-POWER METER User's Manual · ARCT1F440E-8 · rev. 2016-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Panasonic KW8M Eco-POWER METER

Integration in brief

Switch the protocol to MODBUS(RTU) in Mode 3, then poll with function 03: 0064H energy (2 words, 0.01 kWh), 00B0H active power, 006BH-006DH currents, 00AAH-00AEH voltages, 006FH PF and 0070H frequency.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100Integral active energyUINT32 CDABIntegral active energyRead/write
HR 176Instantaneous active powerUINT32 CDABActive powerRead
HR 107Current L1 (CT1)UINT16Current L1Read
HR 170Voltage L1 (P1-P0)UINT32 CDABVoltage L1Read
HR 111Power factorINT16Power factorRead
HR 112FrequencyUINT16FrequencyRead

Enable Modbus control & writes

Protocol defaults to MEWTOCOL; change it to MODBUS(RTU) in setting Mode 3 together with station number, speed, format and response time.

Byte order & addressing

Network setup

Watch out for

Panasonic KW8M Eco-POWER METER Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

41 of 41 shown
Panasonic KW8M Eco-POWER METER Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HContact output statusAKW8111H only.UINT16Read0 = Off; 1 = On
HR48doc 0030HHysteresis for demand alarm offAKW8111H only.UINT16%Read/write
HR49doc 0031HDemand monitor start timeAKW8111H only. 1-30.UINT16minRead/write
HR50doc 0032HRateElectricity rate per kWh used for the charge display.UINT16× 0.01Read/write
HR60doc 003CHCT typeDedicated CT rating: 5, 50, 100, 250, 400 or 600.UINT16ARead/write
HR61doc 003DHUnit for pulse outputUINT32CDABRead/write1 = 0.001 kWh; 10 = 0.01 kWh; 100 = 0.1 kWh; 222 = Demand alarm (00CDH); 333 = Stand-by alarm (004DH/004EH); 555 = Preset count output (preset 009EH); 777 = Current alarm (ratio 0045H); 999 = Power alarm (alarm value 0040H); 1000 = 1 kWh; 10000 = 10 kWh; 100000 = 100 kWh
HR63doc 003FHCT primary current (5 A CT)For a commercial 5 A secondary CT, 1-4000.UINT16ARead/write
HR64doc 0040HAlarm value (instantaneous active power)UINT32CDAB× 0.01kWRead/write
HR66doc 0042HVT ratioUINT16× 0.01Read/write
HR67doc 0043HCurrent threshold for time measurementLoad on/off-time threshold.UINT16× 0.1%Read/write
HR68doc 0044HCut-off currentUINT16× 0.1%Read/write
HR69doc 0045HCurrent alarm valueUINT16× 0.1%Read/write
HR70doc 0046HVoltage rangeUINT16Read/write1 = 400 V; 2 = 200 V
HR77doc 004DHCurrent ratio for stand-by alarmUINT16× 0.1%Read/write
HR78doc 004EHTime for stand-by alarm1-9999; unit not printed in the table.UINT16Read/write
HR80doc 0050HSRAM initializeAKW8111H only.UINT16Read/write0 = Off; 1 = On
HR98doc 0062HActive energy for arbitrary periodAKW8111H only. Table unit reads 0.01kW.UINT32CDAB× 0.01Read/write
HR100doc 0064HIntegral active energyUINT32CDAB× 0.01kWhRead/write
HR102doc 0066HIntegral reactive energyUINT32CDAB× 0.01kvarhRead/write
HR104doc 0068HIntegral apparent energyUINT32CDAB× 0.01kVAhRead/write
HR107doc 006BHCurrent L1 (CT1)UINT16× 0.1ARead
HR108doc 006CHCurrent L2 (CT2)UINT16× 0.1ARead
HR109doc 006DHCurrent L3 (CT3)UINT16× 0.1ARead
HR111doc 006FHPower factorINT16× 0.01Read
HR112doc 0070HFrequencyUINT16× 0.1HzRead
HR150doc 0096HLoad ON-timeUINT32CDAB× 0.1hRead/write
HR152doc 0098HLoad OFF-timeUINT32CDAB× 0.1hRead/write
HR154doc 009AHPulse count valueUINT32CDABRead/write
HR158doc 009EHPreset valuePulse count preset for the count output.UINT32CDABRead/write
HR160doc 00A0HPrescale valueUINT32CDAB× 0.001Read/write
HR162doc 00A2HMax. counting speedUINT16HzRead/write30 = 30 Hz; 2000 = 2000 Hz
HR163doc 00A3HAuto-off timeUINT16minRead/write
HR170doc 00AAHVoltage L1 (P1-P0)UINT32CDAB× 0.1VRead
HR172doc 00ACHVoltage L2 (P2-P0)UINT32CDAB× 0.1VRead
HR174doc 00AEHVoltage L3 (P3-P0)UINT32CDAB× 0.1VRead
HR176doc 00B0HInstantaneous active powerUINT32CDAB× 0.01kWRead
HR178doc 00B2HInstantaneous reactive powerINT32CDAB× 0.01kvarRead
HR180doc 00B4HInstantaneous apparent powerUINT32CDAB× 0.01kVARead
HR200doc 00C8HPresent demandAKW8111H only.UINT32CDAB× 0.01kWRead
HR203doc 00CBHEstimated demandAKW8111H only.UINT32CDAB× 0.01kWRead
HR205doc 00CDHDemand setting valueAKW8111H only.UINT32CDAB× 0.01kWRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Panasonic KW8M Eco-POWER METER

What Modbus registers does the Panasonic KW8M Eco-POWER METER have?

This map lists 41 registers: 41 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Panasonic KW8M Eco-POWER METER Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints hex data items (0064H) that go into the request unchanged; the manual's example resets energy by writing 2 words at 0064H. The MEWTOCOL DT number in decimal equals the hex Modbus address.

What byte order does the Panasonic KW8M Eco-POWER METER use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Panasonic KW8M Eco-POWER METER?

Start with HR 100 Integral active energy (Integral active energy); HR 176 Instantaneous active power (Active power); HR 107 Current L1 (CT1) (Current L1); HR 170 Voltage L1 (P1-P0) (Voltage L1); HR 111 Power factor (Power factor); HR 112 Frequency (Frequency).

How do I enable Modbus control of the Panasonic KW8M Eco-POWER METER?

Protocol defaults to MEWTOCOL; change it to MODBUS(RTU) in setting Mode 3 together with station number, speed, format and response time.

Where is the official Panasonic KW8M Eco-POWER METER Modbus documentation?

The source is KW8M Eco-POWER METER User's Manual (ARCT1F440E-8), revision 2016-08, published free by Panasonic at https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw8m_user_pidsx_en.pdf.

More Panasonic Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: KW8M Eco-POWER METER User's Manual · ARCT1F440E-8 · rev. 2016-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.