Energy meter (multi-circuit power monitor) · Modbus register map
Panasonic KW9M Eco-POWER METER Modbus register map
Updated 17 November 2026
The KW9M is a compact energy monitor that measures up to three single-phase circuits or one three-phase system and speaks MEWTOCOL, Modbus RTU or DL/T645 on RS485. In Modbus mode everything is a holding register read with function 03 and written with 06/16. This map covers the comm and metering settings, per-circuit and total energy, power, voltage, current, frequency, power factor, demand, THD and the conversion (cost) values.
This page lists 184 Modbus registers for the Panasonic KW9M Eco-POWER METER — 62 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Panasonic
- Model
- KW9M Eco-POWER METER
- Equipment type
- Energy meter (multi-circuit power monitor)
- Registers
- 184 (62 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8O1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- AKW91110
Integration notes: Panasonic KW9M Eco-POWER METER
Set the meter's protocol to MODBUS (MODr) on the front panel, then read holding registers with function 03: total active power 0092H, total import kWh 006AH, voltages from 00A4H and currents from 00B4H. All 32-bit values are low word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 106 | Total integral active energy | UINT32 CDAB | Total imported active energy (0.01 kWh) | Read |
| HR 130 | Total integral export active energy | UINT32 CDAB | Total exported active energy | Read |
| HR 146 | Total instantaneous active power | INT32 CDAB | Total active power (0.01 kW) | Read |
| HR 164 | Voltage 1 | UINT32 CDAB | Voltage 1 | Read |
| HR 180 | Current (1) | UINT32 CDAB | Current (1) | Read |
| HR 193 | Frequency average | UINT16 | Frequency average | Read |
| HR 197 | PF average | INT16 | PF average | Read |
Enable Modbus control & writes
Protocol defaults to MEWTOCOL. Select MODr (Modbus RTU) in the communication setting mode, or write 1 to register 0062H. Changing protocol resets device number, speed, format, stop bit and response time.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Only data bits 8 work with Modbus RTU; parity default is odd (8b-o).
- Writes outside the allowed range, or to a missing address, are acknowledged but ignored.
- Maximum 26 registers per read and 23 per write.
Network setup
- Defaults: device number 1, 19200 bps, 8 data bits, odd parity, 1 stop bit, response time 5 ms.
- Modbus device numbers 1-247; broadcast address 0 gets no reply.
- Set phase/wire, CT type and CT primary current to match the wiring or readings will be wrong.
Watch out for
- Settings written over Modbus go straight to non-volatile memory; avoid writing them cyclically.
- Most values exist twice: a 0.01-resolution block from 0064H and a 0.001-resolution block from 00C6H. Check which block you poll before scaling.
Panasonic KW9M Eco-POWER METER Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 50doc 0032H | RS485 device number | Modbus range 1-247. | UINT16 | Read/write | ||||
| HR | 51doc 0033H | RS485 transmission speed | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200 | ||||
| HR | 52doc 0034H | RS485 transmission format | UINT16 | Read/write | 0 = 8 bit odd; 1 = 8 bit none; 2 = 8 bit even | ||||
| HR | 53doc 0035H | RS485 stop bit | 1 or 2. | UINT16 | Read/write | ||||
| HR | 54doc 0036H | RS485 response time | 1-99 ms. | UINT16 | ms | Read/write | |||
| HR | 55doc 0037H | Phase/wire | UINT16 | Read/write | 0 = 1P2W; 1 = 1P3W; 2 = 3P3W; 3 = 3P4W | ||||
| HR | 56doc 0038H | CT type (secondary) | Rated CT secondary current, 1 or 5. | UINT16 | A | Read/write | |||
| HR | 57doc 0039H | CT primary current | UINT16 | A | Read/write | ||||
| HR | 58doc 003AH | VT ratio | UINT16 | × 0.01 | Read/write | ||||
| HR | 59doc 003BH | Temperature correction value | INT16 | × 0.1 | °C | Read/write | |||
| HR | 65doc 0041H | Update cycle | Raw 1-10, in 100 ms steps. | UINT16 | × 100 | ms | Read/write | ||
| HR | 70doc 0046H | Auto-off | Display auto-off time; 0 keeps the display on. | UINT16 | min | Read/write | |||
| HR | 87doc 0057H | Conversion rate (export) | Rate per kWh used for the export conversion value. | UINT16 | × 0.01 | Read/write | |||
| HR | 93doc 005DH | Conversion rate | Rate per kWh used for the conversion value. | UINT16 | × 0.01 | Read/write | |||
| HR | 94doc 005EH | Password | UINT16 | Read/write | |||||
| HR | 95doc 005FH | Auto display start | 0 keeps a fixed display item. | UINT16 | min | Read/write | |||
| HR | 96doc 0060H | Display cycle | UINT16 | s | Read/write | ||||
| HR | 97doc 0061H | Luminance | 1 (dark) to 5 (bright). | UINT16 | Read/write | ||||
| HR | 98doc 0062H | Protocol | UINT16 | Read/write | 0 = MEWTOCOL; 1 = Modbus RTU; 2 = DL/T645 | ||||
| HR | 100doc 0064H | Integral active energy (1) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 102doc 0066H | Integral active energy (2) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 104doc 0068H | Integral active energy (3) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 106doc 006AH | Total integral active energy | UINT32 | CDAB | × 0.01 | kWh | Read | ||
| HR | 108doc 006CH | Integral reactive energy (1) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 110doc 006EH | Integral reactive energy (2) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 112doc 0070H | Integral reactive energy (3) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 114doc 0072H | Total integral reactive energy | UINT32 | CDAB | × 0.01 | kvarh | Read | ||
| HR | 116doc 0074H | Integral apparent energy (1) | UINT32 | CDAB | × 0.01 | kVAh | Read/write | ||
| HR | 118doc 0076H | Integral apparent energy (2) | UINT32 | CDAB | × 0.01 | kVAh | Read/write | ||
| HR | 120doc 0078H | Integral apparent energy (3) | UINT32 | CDAB | × 0.01 | kVAh | Read/write | ||
| HR | 122doc 007AH | Total integral apparent energy | UINT32 | CDAB | × 0.01 | kVAh | Read | ||
| HR | 124doc 007CH | Integral export active energy (1) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 126doc 007EH | Integral export active energy (2) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 128doc 0080H | Integral export active energy (3) | UINT32 | CDAB | × 0.01 | kWh | Read/write | ||
| HR | 130doc 0082H | Total integral export active energy | UINT32 | CDAB | × 0.01 | kWh | Read | ||
| HR | 132doc 0084H | Integral export reactive energy (1) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 134doc 0086H | Integral export reactive energy (2) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 136doc 0088H | Integral export reactive energy (3) | UINT32 | CDAB | × 0.01 | kvarh | Read/write | ||
| HR | 138doc 008AH | Total integral export reactive energy | UINT32 | CDAB | × 0.01 | kvarh | Read | ||
| HR | 140doc 008CH | Instantaneous active power (1) | INT32 | CDAB | × 0.01 | kW | Read | ||
| HR | 142doc 008EH | Instantaneous active power (2) | INT32 | CDAB | × 0.01 | kW | Read | ||
| HR | 144doc 0090H | Instantaneous active power (3) | INT32 | CDAB | × 0.01 | kW | Read | ||
| HR | 146doc 0092H | Total instantaneous active power | INT32 | CDAB | × 0.01 | kW | Read | ||
| HR | 148doc 0094H | Instantaneous reactive power (1) | INT32 | CDAB | × 0.01 | kvar | Read | ||
| HR | 150doc 0096H | Instantaneous reactive power (2) | INT32 | CDAB | × 0.01 | kvar | Read | ||
| HR | 152doc 0098H | Instantaneous reactive power (3) | INT32 | CDAB | × 0.01 | kvar | Read | ||
| HR | 154doc 009AH | Total instantaneous reactive power | INT32 | CDAB | × 0.01 | kvar | Read | ||
| HR | 156doc 009CH | Instantaneous apparent power (1) | UINT32 | CDAB | × 0.01 | kVA | Read | ||
| HR | 158doc 009EH | Instantaneous apparent power (2) | UINT32 | CDAB | × 0.01 | kVA | Read | ||
| HR | 160doc 00A0H | Instantaneous apparent power (3) | UINT32 | CDAB | × 0.01 | kVA | Read | ||
| HR | 162doc 00A2H | Total instantaneous apparent power | UINT32 | CDAB | × 0.01 | kVA | Read | ||
| HR | 164doc 00A4H | Voltage 1 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 166doc 00A6H | Voltage 2 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 168doc 00A8H | Voltage 3 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 170doc 00AAH | Voltage average | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 172doc 00ACH | Line voltage 1-2 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 174doc 00AEH | Line voltage 2-3 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 176doc 00B0H | Line voltage 3-1 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 178doc 00B2H | Line voltage average | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 180doc 00B4H | Current (1) | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 182doc 00B6H | Current (2) | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 184doc 00B8H | Current (3) | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 188doc 00BCH | Current average | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 190doc 00BEH | Frequency (1) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 191doc 00BFH | Frequency (2) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 192doc 00C0H | Frequency (3) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 193doc 00C1H | Frequency average | UINT16 | × 0.1 | Hz | Read | |||
| HR | 194doc 00C2H | PF (1) | INT16 | × 0.001 | Read | ||||
| HR | 195doc 00C3H | PF (2) | INT16 | × 0.001 | Read | ||||
| HR | 196doc 00C4H | PF (3) | INT16 | × 0.001 | Read | ||||
| HR | 197doc 00C5H | PF average | INT16 | × 0.001 | Read | ||||
| HR | 198doc 00C6H | Integral active energy hi-res (1) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 200doc 00C8H | Integral active energy hi-res (2) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 202doc 00CAH | Integral active energy hi-res (3) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 204doc 00CCH | Total integral active energy hi-res | UINT32 | CDAB | × 0.001 | kWh | Read | ||
| HR | 206doc 00CEH | Integral reactive energy hi-res (1) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 208doc 00D0H | Integral reactive energy hi-res (2) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 210doc 00D2H | Integral reactive energy hi-res (3) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 212doc 00D4H | Total integral reactive energy hi-res | UINT32 | CDAB | × 0.001 | kvarh | Read | ||
| HR | 214doc 00D6H | Integral apparent energy hi-res (1) | UINT32 | CDAB | × 0.001 | kVAh | Read/write | ||
| HR | 216doc 00D8H | Integral apparent energy hi-res (2) | UINT32 | CDAB | × 0.001 | kVAh | Read/write | ||
| HR | 218doc 00DAH | Integral apparent energy hi-res (3) | UINT32 | CDAB | × 0.001 | kVAh | Read/write | ||
| HR | 220doc 00DCH | Total integral apparent energy hi-res | UINT32 | CDAB | × 0.001 | kVAh | Read | ||
| HR | 222doc 00DEH | Integral export active energy hi-res (1) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 224doc 00E0H | Integral export active energy hi-res (2) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 226doc 00E2H | Integral export active energy hi-res (3) | UINT32 | CDAB | × 0.001 | kWh | Read/write | ||
| HR | 228doc 00E4H | Total integral export active energy hi-res | UINT32 | CDAB | × 0.001 | kWh | Read | ||
| HR | 230doc 00E6H | Integral export reactive energy hi-res (1) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 232doc 00E8H | Integral export reactive energy hi-res (2) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 234doc 00EAH | Integral export reactive energy hi-res (3) | UINT32 | CDAB | × 0.001 | kvarh | Read/write | ||
| HR | 236doc 00ECH | Total integral export reactive energy hi-res | UINT32 | CDAB | × 0.001 | kvarh | Read | ||
| HR | 238doc 00EEH | Instantaneous active power hi-res (1) | INT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 240doc 00F0H | Instantaneous active power hi-res (2) | INT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 242doc 00F2H | Instantaneous active power hi-res (3) | INT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 244doc 00F4H | Total instantaneous active power hi-res | INT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 246doc 00F6H | Instantaneous reactive power hi-res (1) | INT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 248doc 00F8H | Instantaneous reactive power hi-res (2) | INT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 250doc 00FAH | Instantaneous reactive power hi-res (3) | INT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 252doc 00FCH | Total instantaneous reactive power hi-res | INT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 254doc 00FEH | Instantaneous apparent power hi-res (1) | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 256doc 0100H | Instantaneous apparent power hi-res (2) | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 258doc 0102H | Instantaneous apparent power hi-res (3) | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 260doc 0104H | Total instantaneous apparent power hi-res | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 262doc 0106H | Voltage 1 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 264doc 0108H | Voltage 2 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 266doc 010AH | Voltage 3 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 268doc 010CH | Voltage average hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 270doc 010EH | Line voltage 1-2 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 272doc 0110H | Line voltage 2-3 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 274doc 0112H | Line voltage 3-1 hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 276doc 0114H | Line voltage average hi-res | UINT32 | CDAB | × 0.01 | V | Read | ||
| HR | 278doc 0116H | Current (1) hi-res | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 280doc 0118H | Current (2) hi-res | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 282doc 011AH | Current (3) hi-res | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 286doc 011EH | Current average hi-res | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 288doc 0120H | Frequency (1) hi-res | UINT16 | × 0.01 | Hz | Read | |||
| HR | 289doc 0121H | Frequency (2) hi-res | UINT16 | × 0.01 | Hz | Read | |||
| HR | 290doc 0122H | Frequency (3) hi-res | UINT16 | × 0.01 | Hz | Read | |||
| HR | 291doc 0123H | Frequency average hi-res | UINT16 | × 0.01 | Hz | Read | |||
| HR | 305doc 0131H | Present demand active power | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 307doc 0133H | Present demand reactive power | UINT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 309doc 0135H | Present demand apparent power | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 311doc 0137H | Present demand export active power | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 313doc 0139H | Present demand export reactive power | UINT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 315doc 013BH | Present demand current (1) | The manual labels all three entries 'Present demand (current)'; listed in order. | UINT32 | CDAB | × 0.001 | A | Read | |
| HR | 317doc 013DH | Present demand current (2) | The manual labels all three entries 'Present demand (current)'; listed in order. | UINT32 | CDAB | × 0.001 | A | Read | |
| HR | 319doc 013FH | Present demand current (3) | The manual labels all three entries 'Present demand (current)'; listed in order. | UINT32 | CDAB | × 0.001 | A | Read | |
| HR | 324doc 0144H | PF status | UINT16 | Read | 0 = Even; 1 = Lag; 2 = Lead | ||||
| HR | 325doc 0145H | Total active energy | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.01 | kWh | Read | |
| HR | 327doc 0147H | Total reactive energy | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.01 | kvarh | Read | |
| HR | 329doc 0149H | Total apparent energy | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.01 | kVAh | Read | |
| HR | 331doc 014BH | Total export active energy | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.01 | kWh | Read | |
| HR | 333doc 014DH | Total export reactive energy | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.01 | kvarh | Read | |
| HR | 335doc 014FH | Total active energy (0.001) | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.001 | kWh | Read | |
| HR | 337doc 0151H | Total reactive energy (0.001) | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.001 | kvarh | Read | |
| HR | 339doc 0153H | Total apparent energy (0.001) | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.001 | kVAh | Read | |
| HR | 341doc 0155H | Total export active energy (0.001) | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.001 | kWh | Read | |
| HR | 343doc 0157H | Total export reactive energy (0.001) | Second total block (DT00325 onward). | UINT32 | CDAB | × 0.001 | kvarh | Read | |
| HR | 345doc 0159H | Integral active energy (1) Wh | UINT32 | CDAB | × 0.01 | Wh | Read | ||
| HR | 347doc 015BH | Integral active energy (2) Wh | UINT32 | CDAB | × 0.01 | Wh | Read | ||
| HR | 349doc 015DH | Integral active energy (3) Wh | UINT32 | CDAB | × 0.01 | Wh | Read | ||
| HR | 351doc 015FH | Total integral active energy Wh | UINT32 | CDAB | × 0.01 | Wh | Read | ||
| HR | 418doc 01A2H | Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 664doc 0298H | Phase voltage THD (1) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 666doc 029AH | Phase voltage THD (2) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 668doc 029CH | Phase voltage THD (3) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 670doc 029EH | Phase voltage THD average | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 672doc 02A0H | Line voltage THD 1-2 | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 674doc 02A2H | Line voltage THD 2-3 | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 676doc 02A4H | Line voltage THD 3-1 | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 678doc 02A6H | Line voltage THD average | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 680doc 02A8H | Current THD (1) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 682doc 02AAH | Current THD (2) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 684doc 02ACH | Current THD (3) | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 686doc 02AEH | Current THD average | INT32 | CDAB | × 0.001 | % | Read | ||
| HR | 5040doc 13B0H | Export power conversion value (1) | Export kWh times the export conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5042doc 13B2H | Export power conversion value (2) | Export kWh times the export conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5044doc 13B4H | Export power conversion value (3) | Export kWh times the export conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5046doc 13B6H | Total export power conversion value | UINT32 | CDAB | × 0.01 | Read | |||
| HR | 5090doc 13E2H | Conversion value (1) | kWh times the conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5092doc 13E4H | Conversion value (2) | kWh times the conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5094doc 13E6H | Conversion value (3) | kWh times the conversion rate. | UINT32 | CDAB | × 0.01 | Read | ||
| HR | 5096doc 13E8H | Total conversion value | UINT32 | CDAB | × 0.01 | Read | |||
| HR | 30108doc 759CH | Power demand type | UINT16 | Read/write | 1 = Sliding block; 2 = Fixed block | ||||
| HR | 30109doc 759DH | Power demand interval 1 | UINT16 | min | Read/write | ||||
| HR | 30110doc 759EH | Power demand interval 2 | UINT16 | min | Read/write | ||||
| HR | 30111doc 759FH | Current demand interval | UINT16 | min | Read/write | ||||
| HR | 30200doc 75F8H | Demand measurement status | Start/stop demand measurement; see notes for the value coding. | UINT16 | Read/write | ||||
| HR | 30300doc 765CH | Reset all integral values | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30301doc 765DH | Reset integral value 1 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30302doc 765EH | Reset integral value 2 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30303doc 765FH | Reset integral value 3 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30306doc 7662H | Reset logging data | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30307doc 7663H | Cut-off current | UINT16 | × 0.1 | % | Read/write | |||
| HR | 30309doc 7665H | Save display | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 30310doc 7666H | Initialize settings | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 31903doc 7C9FH | Max demand active power | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 31908doc 7CA4H | Max demand reactive power | UINT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 31913doc 7CA9H | Max demand apparent power | UINT32 | CDAB | × 0.001 | kVA | Read | ||
| HR | 31918doc 7CAEH | Max demand export active power | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 31923doc 7CB3H | Max demand export reactive power | UINT32 | CDAB | × 0.001 | kvar | Read | ||
| HR | 31928doc 7CB8H | Max demand current 1 | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 31933doc 7CBDH | Max demand current 2 | UINT32 | CDAB | × 0.001 | A | Read | ||
| HR | 31938doc 7CC2H | Max demand current 3 | UINT32 | CDAB | × 0.001 | A | Read |
Notes on this map
- Word order: each 32-bit value is printed as two rows marked <LSB> (lower address) and <MSB> (higher address), so the low word comes first (CDAB). The manual's footnote calls these 'byte', but each mark sits on a whole 16-bit register.
- The manual heads the measurement table 'Data registers for 3P3W'. For three-phase systems use the Total power and Average frequency / PF registers, as the manual says.
- Per-circuit integral (energy) registers can be written with function 16 (e.g. to zero them, as in the manual's example at 0064H); totals are read-only.
- The settings table text is laid out in two separate columns in the PDF; register-to-name pairing was checked against the MEWTOCOL DT list, where the DT number in decimal equals the Modbus hex address.
- Demand measurement status (75F8H): the Modbus table codes 0 = Start, 1 = Stop, but the MEWTOCOL table for the same setting codes 0 = Stop, 1 = Start. Value meanings are left out until checked on a live meter.
- Not included: logging data and any registers not listed in section 7.4.2. Registers not listed read 0.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Panasonic KW9M Eco-POWER METER
What Modbus registers does the Panasonic KW9M Eco-POWER METER have?
This map lists 184 registers: 184 holding registers. 62 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Panasonic KW9M Eco-POWER METER Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The Modbus table prints hex register numbers (0064H). That number goes straight into the request: the manual's example reads conversion rate 005DH with start address 005DH. Each Modbus address equals the MEWTOCOL DT number converted to hex (DT00100 = 0064H).
What byte order does the Panasonic KW9M Eco-POWER METER use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Panasonic KW9M Eco-POWER METER?
Start with HR 106 Total integral active energy (Total imported active energy (0.01 kWh)); HR 130 Total integral export active energy (Total exported active energy); HR 146 Total instantaneous active power (Total active power (0.01 kW)); HR 164 Voltage 1 (Voltage 1); HR 180 Current (1) (Current (1)); HR 193 Frequency average (Frequency average); HR 197 PF average (PF average).
How do I enable Modbus control of the Panasonic KW9M Eco-POWER METER?
Protocol defaults to MEWTOCOL. Select MODr (Modbus RTU) in the communication setting mode, or write 1 to register 0062H. Changing protocol resets device number, speed, format, stop bit and response time.
Where is the official Panasonic KW9M Eco-POWER METER Modbus documentation?
The source is KW9M Eco-POWER METER User's Manual (WUME-KW9M-10), revision 2018-12, published free by Panasonic at https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw9m_user_pidsx_en.pdf.
More Panasonic Modbus register maps
- Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus - Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H
Other power & energy meters register maps
- Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Energy meter
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
ALE3 unidirectional (ALE3D5FD10C3A00) and bidirectional (ALE3B5FD00C3A00) Modbus types, assembly and operating instructions 431951130.
Also known as: ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180 - Power meter (multi-circuit)
Setra Systems Setra Power Meter (SPM) multi-circuit power meter
Setra Power Meter (SPM) family, per Modbus register master list SS-SPM-MODBUS_G; this map covers the device block, both voltage inputs and Load 1.
Also known as: SPM, Setra Power Meter, SS-SPM-MODBUS_G
All power & energy meters Modbus register maps →
Source: KW9M Eco-POWER METER User's Manual · WUME-KW9M-10 · rev. 2018-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.