Panasonic KW9M Eco-POWER METER Modbus register map

Updated 17 November 2026

Short answer

The KW9M is a compact energy monitor that measures up to three single-phase circuits or one three-phase system and speaks MEWTOCOL, Modbus RTU or DL/T645 on RS485. In Modbus mode everything is a holding register read with function 03 and written with 06/16. This map covers the comm and metering settings, per-circuit and total energy, power, voltage, current, frequency, power factor, demand, THD and the conversion (cost) values.

This page lists 184 Modbus registers for the Panasonic KW9M Eco-POWER METER — 62 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.

Manufacturer
Panasonic
Model
KW9M Eco-POWER METER
Equipment type
Energy meter (multi-circuit power monitor)
Registers
184 (62 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8O1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
AKW91110
Source document
KW9M Eco-POWER METER User's Manual · WUME-KW9M-10 · rev. 2018-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Panasonic KW9M Eco-POWER METER

Integration in brief

Set the meter's protocol to MODBUS (MODr) on the front panel, then read holding registers with function 03: total active power 0092H, total import kWh 006AH, voltages from 00A4H and currents from 00B4H. All 32-bit values are low word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 106Total integral active energyUINT32 CDABTotal imported active energy (0.01 kWh)Read
HR 130Total integral export active energyUINT32 CDABTotal exported active energyRead
HR 146Total instantaneous active powerINT32 CDABTotal active power (0.01 kW)Read
HR 164Voltage 1UINT32 CDABVoltage 1Read
HR 180Current (1)UINT32 CDABCurrent (1)Read
HR 193Frequency averageUINT16Frequency averageRead
HR 197PF averageINT16PF averageRead

Enable Modbus control & writes

Protocol defaults to MEWTOCOL. Select MODr (Modbus RTU) in the communication setting mode, or write 1 to register 0062H. Changing protocol resets device number, speed, format, stop bit and response time.

Byte order & addressing

Network setup

Watch out for

Panasonic KW9M Eco-POWER METER Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

184 of 184 shown
Panasonic KW9M Eco-POWER METER Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR50doc 0032HRS485 device numberModbus range 1-247.UINT16Read/write
HR51doc 0033HRS485 transmission speedUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200
HR52doc 0034HRS485 transmission formatUINT16Read/write0 = 8 bit odd; 1 = 8 bit none; 2 = 8 bit even
HR53doc 0035HRS485 stop bit1 or 2.UINT16Read/write
HR54doc 0036HRS485 response time1-99 ms.UINT16msRead/write
HR55doc 0037HPhase/wireUINT16Read/write0 = 1P2W; 1 = 1P3W; 2 = 3P3W; 3 = 3P4W
HR56doc 0038HCT type (secondary)Rated CT secondary current, 1 or 5.UINT16ARead/write
HR57doc 0039HCT primary currentUINT16ARead/write
HR58doc 003AHVT ratioUINT16× 0.01Read/write
HR59doc 003BHTemperature correction valueINT16× 0.1°CRead/write
HR65doc 0041HUpdate cycleRaw 1-10, in 100 ms steps.UINT16× 100msRead/write
HR70doc 0046HAuto-offDisplay auto-off time; 0 keeps the display on.UINT16minRead/write
HR87doc 0057HConversion rate (export)Rate per kWh used for the export conversion value.UINT16× 0.01Read/write
HR93doc 005DHConversion rateRate per kWh used for the conversion value.UINT16× 0.01Read/write
HR94doc 005EHPasswordUINT16Read/write
HR95doc 005FHAuto display start0 keeps a fixed display item.UINT16minRead/write
HR96doc 0060HDisplay cycleUINT16sRead/write
HR97doc 0061HLuminance1 (dark) to 5 (bright).UINT16Read/write
HR98doc 0062HProtocolUINT16Read/write0 = MEWTOCOL; 1 = Modbus RTU; 2 = DL/T645
HR100doc 0064HIntegral active energy (1)UINT32CDAB× 0.01kWhRead/write
HR102doc 0066HIntegral active energy (2)UINT32CDAB× 0.01kWhRead/write
HR104doc 0068HIntegral active energy (3)UINT32CDAB× 0.01kWhRead/write
HR106doc 006AHTotal integral active energyUINT32CDAB× 0.01kWhRead
HR108doc 006CHIntegral reactive energy (1)UINT32CDAB× 0.01kvarhRead/write
HR110doc 006EHIntegral reactive energy (2)UINT32CDAB× 0.01kvarhRead/write
HR112doc 0070HIntegral reactive energy (3)UINT32CDAB× 0.01kvarhRead/write
HR114doc 0072HTotal integral reactive energyUINT32CDAB× 0.01kvarhRead
HR116doc 0074HIntegral apparent energy (1)UINT32CDAB× 0.01kVAhRead/write
HR118doc 0076HIntegral apparent energy (2)UINT32CDAB× 0.01kVAhRead/write
HR120doc 0078HIntegral apparent energy (3)UINT32CDAB× 0.01kVAhRead/write
HR122doc 007AHTotal integral apparent energyUINT32CDAB× 0.01kVAhRead
HR124doc 007CHIntegral export active energy (1)UINT32CDAB× 0.01kWhRead/write
HR126doc 007EHIntegral export active energy (2)UINT32CDAB× 0.01kWhRead/write
HR128doc 0080HIntegral export active energy (3)UINT32CDAB× 0.01kWhRead/write
HR130doc 0082HTotal integral export active energyUINT32CDAB× 0.01kWhRead
HR132doc 0084HIntegral export reactive energy (1)UINT32CDAB× 0.01kvarhRead/write
HR134doc 0086HIntegral export reactive energy (2)UINT32CDAB× 0.01kvarhRead/write
HR136doc 0088HIntegral export reactive energy (3)UINT32CDAB× 0.01kvarhRead/write
HR138doc 008AHTotal integral export reactive energyUINT32CDAB× 0.01kvarhRead
HR140doc 008CHInstantaneous active power (1)INT32CDAB× 0.01kWRead
HR142doc 008EHInstantaneous active power (2)INT32CDAB× 0.01kWRead
HR144doc 0090HInstantaneous active power (3)INT32CDAB× 0.01kWRead
HR146doc 0092HTotal instantaneous active powerINT32CDAB× 0.01kWRead
HR148doc 0094HInstantaneous reactive power (1)INT32CDAB× 0.01kvarRead
HR150doc 0096HInstantaneous reactive power (2)INT32CDAB× 0.01kvarRead
HR152doc 0098HInstantaneous reactive power (3)INT32CDAB× 0.01kvarRead
HR154doc 009AHTotal instantaneous reactive powerINT32CDAB× 0.01kvarRead
HR156doc 009CHInstantaneous apparent power (1)UINT32CDAB× 0.01kVARead
HR158doc 009EHInstantaneous apparent power (2)UINT32CDAB× 0.01kVARead
HR160doc 00A0HInstantaneous apparent power (3)UINT32CDAB× 0.01kVARead
HR162doc 00A2HTotal instantaneous apparent powerUINT32CDAB× 0.01kVARead
HR164doc 00A4HVoltage 1UINT32CDAB× 0.1VRead
HR166doc 00A6HVoltage 2UINT32CDAB× 0.1VRead
HR168doc 00A8HVoltage 3UINT32CDAB× 0.1VRead
HR170doc 00AAHVoltage averageUINT32CDAB× 0.1VRead
HR172doc 00ACHLine voltage 1-2UINT32CDAB× 0.1VRead
HR174doc 00AEHLine voltage 2-3UINT32CDAB× 0.1VRead
HR176doc 00B0HLine voltage 3-1UINT32CDAB× 0.1VRead
HR178doc 00B2HLine voltage averageUINT32CDAB× 0.1VRead
HR180doc 00B4HCurrent (1)UINT32CDAB× 0.01ARead
HR182doc 00B6HCurrent (2)UINT32CDAB× 0.01ARead
HR184doc 00B8HCurrent (3)UINT32CDAB× 0.01ARead
HR188doc 00BCHCurrent averageUINT32CDAB× 0.01ARead
HR190doc 00BEHFrequency (1)UINT16× 0.1HzRead
HR191doc 00BFHFrequency (2)UINT16× 0.1HzRead
HR192doc 00C0HFrequency (3)UINT16× 0.1HzRead
HR193doc 00C1HFrequency averageUINT16× 0.1HzRead
HR194doc 00C2HPF (1)INT16× 0.001Read
HR195doc 00C3HPF (2)INT16× 0.001Read
HR196doc 00C4HPF (3)INT16× 0.001Read
HR197doc 00C5HPF averageINT16× 0.001Read
HR198doc 00C6HIntegral active energy hi-res (1)UINT32CDAB× 0.001kWhRead/write
HR200doc 00C8HIntegral active energy hi-res (2)UINT32CDAB× 0.001kWhRead/write
HR202doc 00CAHIntegral active energy hi-res (3)UINT32CDAB× 0.001kWhRead/write
HR204doc 00CCHTotal integral active energy hi-resUINT32CDAB× 0.001kWhRead
HR206doc 00CEHIntegral reactive energy hi-res (1)UINT32CDAB× 0.001kvarhRead/write
HR208doc 00D0HIntegral reactive energy hi-res (2)UINT32CDAB× 0.001kvarhRead/write
HR210doc 00D2HIntegral reactive energy hi-res (3)UINT32CDAB× 0.001kvarhRead/write
HR212doc 00D4HTotal integral reactive energy hi-resUINT32CDAB× 0.001kvarhRead
HR214doc 00D6HIntegral apparent energy hi-res (1)UINT32CDAB× 0.001kVAhRead/write
HR216doc 00D8HIntegral apparent energy hi-res (2)UINT32CDAB× 0.001kVAhRead/write
HR218doc 00DAHIntegral apparent energy hi-res (3)UINT32CDAB× 0.001kVAhRead/write
HR220doc 00DCHTotal integral apparent energy hi-resUINT32CDAB× 0.001kVAhRead
HR222doc 00DEHIntegral export active energy hi-res (1)UINT32CDAB× 0.001kWhRead/write
HR224doc 00E0HIntegral export active energy hi-res (2)UINT32CDAB× 0.001kWhRead/write
HR226doc 00E2HIntegral export active energy hi-res (3)UINT32CDAB× 0.001kWhRead/write
HR228doc 00E4HTotal integral export active energy hi-resUINT32CDAB× 0.001kWhRead
HR230doc 00E6HIntegral export reactive energy hi-res (1)UINT32CDAB× 0.001kvarhRead/write
HR232doc 00E8HIntegral export reactive energy hi-res (2)UINT32CDAB× 0.001kvarhRead/write
HR234doc 00EAHIntegral export reactive energy hi-res (3)UINT32CDAB× 0.001kvarhRead/write
HR236doc 00ECHTotal integral export reactive energy hi-resUINT32CDAB× 0.001kvarhRead
HR238doc 00EEHInstantaneous active power hi-res (1)INT32CDAB× 0.001kWRead
HR240doc 00F0HInstantaneous active power hi-res (2)INT32CDAB× 0.001kWRead
HR242doc 00F2HInstantaneous active power hi-res (3)INT32CDAB× 0.001kWRead
HR244doc 00F4HTotal instantaneous active power hi-resINT32CDAB× 0.001kWRead
HR246doc 00F6HInstantaneous reactive power hi-res (1)INT32CDAB× 0.001kvarRead
HR248doc 00F8HInstantaneous reactive power hi-res (2)INT32CDAB× 0.001kvarRead
HR250doc 00FAHInstantaneous reactive power hi-res (3)INT32CDAB× 0.001kvarRead
HR252doc 00FCHTotal instantaneous reactive power hi-resINT32CDAB× 0.001kvarRead
HR254doc 00FEHInstantaneous apparent power hi-res (1)UINT32CDAB× 0.001kVARead
HR256doc 0100HInstantaneous apparent power hi-res (2)UINT32CDAB× 0.001kVARead
HR258doc 0102HInstantaneous apparent power hi-res (3)UINT32CDAB× 0.001kVARead
HR260doc 0104HTotal instantaneous apparent power hi-resUINT32CDAB× 0.001kVARead
HR262doc 0106HVoltage 1 hi-resUINT32CDAB× 0.01VRead
HR264doc 0108HVoltage 2 hi-resUINT32CDAB× 0.01VRead
HR266doc 010AHVoltage 3 hi-resUINT32CDAB× 0.01VRead
HR268doc 010CHVoltage average hi-resUINT32CDAB× 0.01VRead
HR270doc 010EHLine voltage 1-2 hi-resUINT32CDAB× 0.01VRead
HR272doc 0110HLine voltage 2-3 hi-resUINT32CDAB× 0.01VRead
HR274doc 0112HLine voltage 3-1 hi-resUINT32CDAB× 0.01VRead
HR276doc 0114HLine voltage average hi-resUINT32CDAB× 0.01VRead
HR278doc 0116HCurrent (1) hi-resUINT32CDAB× 0.001ARead
HR280doc 0118HCurrent (2) hi-resUINT32CDAB× 0.001ARead
HR282doc 011AHCurrent (3) hi-resUINT32CDAB× 0.001ARead
HR286doc 011EHCurrent average hi-resUINT32CDAB× 0.001ARead
HR288doc 0120HFrequency (1) hi-resUINT16× 0.01HzRead
HR289doc 0121HFrequency (2) hi-resUINT16× 0.01HzRead
HR290doc 0122HFrequency (3) hi-resUINT16× 0.01HzRead
HR291doc 0123HFrequency average hi-resUINT16× 0.01HzRead
HR305doc 0131HPresent demand active powerUINT32CDAB× 0.001kWRead
HR307doc 0133HPresent demand reactive powerUINT32CDAB× 0.001kvarRead
HR309doc 0135HPresent demand apparent powerUINT32CDAB× 0.001kVARead
HR311doc 0137HPresent demand export active powerUINT32CDAB× 0.001kWRead
HR313doc 0139HPresent demand export reactive powerUINT32CDAB× 0.001kvarRead
HR315doc 013BHPresent demand current (1)The manual labels all three entries 'Present demand (current)'; listed in order.UINT32CDAB× 0.001ARead
HR317doc 013DHPresent demand current (2)The manual labels all three entries 'Present demand (current)'; listed in order.UINT32CDAB× 0.001ARead
HR319doc 013FHPresent demand current (3)The manual labels all three entries 'Present demand (current)'; listed in order.UINT32CDAB× 0.001ARead
HR324doc 0144HPF statusUINT16Read0 = Even; 1 = Lag; 2 = Lead
HR325doc 0145HTotal active energySecond total block (DT00325 onward).UINT32CDAB× 0.01kWhRead
HR327doc 0147HTotal reactive energySecond total block (DT00325 onward).UINT32CDAB× 0.01kvarhRead
HR329doc 0149HTotal apparent energySecond total block (DT00325 onward).UINT32CDAB× 0.01kVAhRead
HR331doc 014BHTotal export active energySecond total block (DT00325 onward).UINT32CDAB× 0.01kWhRead
HR333doc 014DHTotal export reactive energySecond total block (DT00325 onward).UINT32CDAB× 0.01kvarhRead
HR335doc 014FHTotal active energy (0.001)Second total block (DT00325 onward).UINT32CDAB× 0.001kWhRead
HR337doc 0151HTotal reactive energy (0.001)Second total block (DT00325 onward).UINT32CDAB× 0.001kvarhRead
HR339doc 0153HTotal apparent energy (0.001)Second total block (DT00325 onward).UINT32CDAB× 0.001kVAhRead
HR341doc 0155HTotal export active energy (0.001)Second total block (DT00325 onward).UINT32CDAB× 0.001kWhRead
HR343doc 0157HTotal export reactive energy (0.001)Second total block (DT00325 onward).UINT32CDAB× 0.001kvarhRead
HR345doc 0159HIntegral active energy (1) WhUINT32CDAB× 0.01WhRead
HR347doc 015BHIntegral active energy (2) WhUINT32CDAB× 0.01WhRead
HR349doc 015DHIntegral active energy (3) WhUINT32CDAB× 0.01WhRead
HR351doc 015FHTotal integral active energy WhUINT32CDAB× 0.01WhRead
HR418doc 01A2HTemperatureINT16× 0.1°CRead
HR664doc 0298HPhase voltage THD (1)INT32CDAB× 0.001%Read
HR666doc 029AHPhase voltage THD (2)INT32CDAB× 0.001%Read
HR668doc 029CHPhase voltage THD (3)INT32CDAB× 0.001%Read
HR670doc 029EHPhase voltage THD averageINT32CDAB× 0.001%Read
HR672doc 02A0HLine voltage THD 1-2INT32CDAB× 0.001%Read
HR674doc 02A2HLine voltage THD 2-3INT32CDAB× 0.001%Read
HR676doc 02A4HLine voltage THD 3-1INT32CDAB× 0.001%Read
HR678doc 02A6HLine voltage THD averageINT32CDAB× 0.001%Read
HR680doc 02A8HCurrent THD (1)INT32CDAB× 0.001%Read
HR682doc 02AAHCurrent THD (2)INT32CDAB× 0.001%Read
HR684doc 02ACHCurrent THD (3)INT32CDAB× 0.001%Read
HR686doc 02AEHCurrent THD averageINT32CDAB× 0.001%Read
HR5040doc 13B0HExport power conversion value (1)Export kWh times the export conversion rate.UINT32CDAB× 0.01Read
HR5042doc 13B2HExport power conversion value (2)Export kWh times the export conversion rate.UINT32CDAB× 0.01Read
HR5044doc 13B4HExport power conversion value (3)Export kWh times the export conversion rate.UINT32CDAB× 0.01Read
HR5046doc 13B6HTotal export power conversion valueUINT32CDAB× 0.01Read
HR5090doc 13E2HConversion value (1)kWh times the conversion rate.UINT32CDAB× 0.01Read
HR5092doc 13E4HConversion value (2)kWh times the conversion rate.UINT32CDAB× 0.01Read
HR5094doc 13E6HConversion value (3)kWh times the conversion rate.UINT32CDAB× 0.01Read
HR5096doc 13E8HTotal conversion valueUINT32CDAB× 0.01Read
HR30108doc 759CHPower demand typeUINT16Read/write1 = Sliding block; 2 = Fixed block
HR30109doc 759DHPower demand interval 1UINT16minRead/write
HR30110doc 759EHPower demand interval 2UINT16minRead/write
HR30111doc 759FHCurrent demand intervalUINT16minRead/write
HR30200doc 75F8HDemand measurement statusStart/stop demand measurement; see notes for the value coding.UINT16Read/write
HR30300doc 765CHReset all integral valuesUINT16Read/write0 = No; 1 = Yes
HR30301doc 765DHReset integral value 1UINT16Read/write0 = No; 1 = Yes
HR30302doc 765EHReset integral value 2UINT16Read/write0 = No; 1 = Yes
HR30303doc 765FHReset integral value 3UINT16Read/write0 = No; 1 = Yes
HR30306doc 7662HReset logging dataUINT16Read/write0 = No; 1 = Yes
HR30307doc 7663HCut-off currentUINT16× 0.1%Read/write
HR30309doc 7665HSave displayUINT16Read/write0 = No; 1 = Yes
HR30310doc 7666HInitialize settingsUINT16Read/write0 = No; 1 = Yes
HR31903doc 7C9FHMax demand active powerUINT32CDAB× 0.001kWRead
HR31908doc 7CA4HMax demand reactive powerUINT32CDAB× 0.001kvarRead
HR31913doc 7CA9HMax demand apparent powerUINT32CDAB× 0.001kVARead
HR31918doc 7CAEHMax demand export active powerUINT32CDAB× 0.001kWRead
HR31923doc 7CB3HMax demand export reactive powerUINT32CDAB× 0.001kvarRead
HR31928doc 7CB8HMax demand current 1UINT32CDAB× 0.001ARead
HR31933doc 7CBDHMax demand current 2UINT32CDAB× 0.001ARead
HR31938doc 7CC2HMax demand current 3UINT32CDAB× 0.001ARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Panasonic KW9M Eco-POWER METER

What Modbus registers does the Panasonic KW9M Eco-POWER METER have?

This map lists 184 registers: 184 holding registers. 62 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Panasonic KW9M Eco-POWER METER Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The Modbus table prints hex register numbers (0064H). That number goes straight into the request: the manual's example reads conversion rate 005DH with start address 005DH. Each Modbus address equals the MEWTOCOL DT number converted to hex (DT00100 = 0064H).

What byte order does the Panasonic KW9M Eco-POWER METER use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Panasonic KW9M Eco-POWER METER?

Start with HR 106 Total integral active energy (Total imported active energy (0.01 kWh)); HR 130 Total integral export active energy (Total exported active energy); HR 146 Total instantaneous active power (Total active power (0.01 kW)); HR 164 Voltage 1 (Voltage 1); HR 180 Current (1) (Current (1)); HR 193 Frequency average (Frequency average); HR 197 PF average (PF average).

How do I enable Modbus control of the Panasonic KW9M Eco-POWER METER?

Protocol defaults to MEWTOCOL. Select MODr (Modbus RTU) in the communication setting mode, or write 1 to register 0062H. Changing protocol resets device number, speed, format, stop bit and response time.

Where is the official Panasonic KW9M Eco-POWER METER Modbus documentation?

The source is KW9M Eco-POWER METER User's Manual (WUME-KW9M-10), revision 2018-12, published free by Panasonic at https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw9m_user_pidsx_en.pdf.

More Panasonic Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: KW9M Eco-POWER METER User's Manual · WUME-KW9M-10 · rev. 2018-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.