Power meter (power quality analyzer) · Modbus register map
SATEC PM180 expertmeter high performance analyzer Modbus register map
Updated 17 November 2026
The PM180 expertmeter is SATEC's high-performance power quality analyzer with serial, Ethernet and expandable I/O. Its 32-bit register set carries 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, THD, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, COM1 settings, password and clear commands.
This page lists 129 Modbus registers for the SATEC PM180 expertmeter high performance analyzer — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- SATEC
- Model
- PM180 expertmeter high performance analyzer
- Equipment type
- Power meter (power quality analyzer)
- Registers
- 129 (13 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- PM180, expertmeter PM180, SATEC PM180
Integration notes: SATEC PM180 expertmeter high performance analyzer
Read 13952 onward (phase values) and 14336 onward (totals) with function 03; decode 32-bit integers low word first. Energy totals start at 14720; check the energy decimal places setting (46258) before scaling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1 voltage | UINT32 CDAB | V1 voltage | Read |
| HR 13958 | I1 current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 14722 | kWh export | UINT32 CDAB | kWh export | Read |
Enable Modbus control & writes
Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Voltage and power units change from 0.1 V / 1 W to 1 V / 1 kW when a PT ratio above 1 is set.
- Energy resolution depends on 46258.
Network setup
- Set wiring mode, PT ratio and CT primary at 46208-46213 first.
- Write the 8-digit password to 44378 if protection is on.
Watch out for
- Changing the PT ratio from 1 changes the meaning of every voltage and power register.
SATEC PM180 expertmeter high performance analyzer Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 11906doc 11906-11907 | Phase rotation order | UINT32 | CDAB | Read | 0 = Error; 1 = Positive (ABC); 2 = Negative (CBA) | |||
| HR | 12544doc 12544-12545 | Digital inputs (bitmap) | Bit 0 = DI1, bit 1 = DI2, and so on. | UINT32 | CDAB | Read | |||
| HR | 12800doc 12800-12801 | Relay outputs (bitmap) | Bit 0 = RO1, bit 1 = RO2, and so on. | UINT32 | CDAB | Read | |||
| HR | 13952doc 13952-13953 | V1 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13954doc 13954-13955 | V2 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13956doc 13956-13957 | V3 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13958doc 13958-13959 | I1 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13960doc 13960-13961 | I2 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13962doc 13962-13963 | I3 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13966doc 13966-13967 | kW L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13968doc 13968-13969 | kW L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13970doc 13970-13971 | kvar L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13972doc 13972-13973 | kvar L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13974doc 13974-13975 | kvar L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13976doc 13976-13977 | kVA L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13978doc 13978-13979 | kVA L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13980doc 13980-13981 | kVA L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13988doc 13988-13989 | V1 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13990doc 13990-13991 | V2 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13992doc 13992-13993 | V3 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13994doc 13994-13995 | I1 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13996doc 13996-13997 | I2 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13998doc 13998-13999 | I3 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14000doc 14000-14001 | I1 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14002doc 14002-14003 | I2 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14004doc 14004-14005 | I3 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14006doc 14006-14007 | I1 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14008doc 14008-14009 | I2 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14010doc 14010-14011 | I3 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14012doc 14012-14013 | V12 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14014doc 14014-14015 | V23 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14016doc 14016-14017 | V31 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14018doc 14018-14019 | I1x current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14020doc 14020-14021 | I2x current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14022doc 14022-14023 | I3x current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14024doc 14024-14025 | V1x Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14026doc 14026-14027 | V2x Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14028doc 14028-14029 | V3x Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14336doc 14336-14337 | Total kW | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14338doc 14338-14339 | Total kvar | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14340doc 14340-14341 | Total kVA | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14344doc 14344-14345 | Total PF lag | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14346doc 14346-14347 | Total PF lead | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14350doc 14350-14351 | Total kW export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14352doc 14352-14353 | Total kvar import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14354doc 14354-14355 | Total kvar export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14356doc 14356-14357 | 3-phase average L-N voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14358doc 14358-14359 | 3-phase average L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14360doc 14360-14361 | 3-phase average current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14362doc 14362-14363 | 3-phase average current, extended inputs I1x-I3x | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14464doc 14464-14465 | I4 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14466doc 14466-14467 | In current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14470doc 14470-14471 | Voltage unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14472doc 14472-14473 | Current unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14478doc 14478-14479 | I4x current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14480doc 14480-14481 | V4x (neutral-ground) voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14482doc 14482-14483 | Internal temperature | INT32 | CDAB | × 0.1 | ºC | Read | ||
| HR | 14484doc 14484-14485 | Frequency (3 decimals) | UINT32 | CDAB | × 0.001 | Hz | Read | ||
| HR | 14486doc 14486-14487 | Lithium battery voltage | UINT32 | CDAB | × 0.001 | V | Read | ||
| HR | 14490doc 14490-14491 | Frequency (4 decimals) | UINT32 | CDAB | × 0.0001 | Hz | Read | ||
| HR | 14496doc 14496-14497 | Active power oscillation, Posc% | UINT32 | CDAB | × 0.01 | % | Read | ||
| HR | 14592doc 14592-14593 | V1 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14594doc 14594-14595 | V2 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14596doc 14596-14597 | V3 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14598doc 14598-14599 | I1 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14600doc 14600-14601 | I2 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14602doc 14602-14603 | I3 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14604doc 14604-14605 | kW import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14606doc 14606-14607 | kvar import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14608doc 14608-14609 | kVA block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14610doc 14610-14611 | kW import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14612doc 14612-14613 | kvar import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14614doc 14614-14615 | kVA sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14622doc 14622-14623 | kW import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14624doc 14624-14625 | kvar import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14626doc 14626-14627 | kVA accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14634doc 14634-14635 | PF (import) at Max. kVA sliding window demand | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14636doc 14636-14637 | kW export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14638doc 14638-14639 | kvar export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14640doc 14640-14641 | kW export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14642doc 14642-14643 | kvar export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14644doc 14644-14645 | kW export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14646doc 14646-14647 | kvar export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14658doc 14658-14659 | I4 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14660doc 14660-14661 | In ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14720doc 14720-14721 | kWh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14722doc 14722-14723 | kWh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14724doc 14724-14725 | kWh net | Whole units at the default 0 energy decimal places (46258). | INT32 | CDAB | kWh | Read | ||
| HR | 14726doc 14726-14727 | kWh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14728doc 14728-14729 | kvarh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14730doc 14730-14731 | kvarh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14732doc 14732-14733 | kvarh net | Whole units at the default 0 energy decimal places (46258). | INT32 | CDAB | kvarh | Read | ||
| HR | 14734doc 14734-14735 | kvarh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14736doc 14736-14737 | kVAh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14738doc 14738-14739 | Vh total | UINT32 | CDAB | Vh | Read | |||
| HR | 14740doc 14740-14741 | Ah total | UINT32 | CDAB | Ah | Read | |||
| HR | 14742doc 14742-14743 | kVAh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14744doc 14744-14745 | kVAh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14756doc 14756-14757 | kvarh Q1 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14758doc 14758-14759 | kvarh Q2 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14760doc 14760-14761 | kvarh Q3 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14762doc 14762-14763 | kvarh Q4 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 44102 | Clear energies | Write 0. | UINT16 | Write | ||||
| HR | 44107 | Clear min/max log | Write 0. | UINT16 | Write | ||||
| HR | 44378doc 44378-44379 | Device authorization (8-digit password) | Write the password before setup writes; reads 0 = allowed, -1 = needed. | INT32 | CDAB | Read/write | |||
| HR | 46080doc 46080-46081 | Device serial number | UINT32 | CDAB | Read | ||||
| HR | 46082doc 46082-46083 | Device model ID | 18000 for PM180. | UINT32 | CDAB | Read | |||
| HR | 46208 | Wiring mode | UINT16 | Read/write | 0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings | ||||
| HR | 46209 | PT ratio | 10-65000 = 1.0-6500.0. | UINT16 | × 0.1 | Read/write | |||
| HR | 46213 | CT primary current | 1-30000 A. | UINT16 | A | Read/write | |||
| HR | 46225 | Nominal line frequency | 50 or 60. | UINT16 | Hz | Read/write | |||
| HR | 46226 | Phase order | UINT16 | Read/write | 0 = ABC; 1 = CBA | ||||
| HR | 46258 | Number of energy decimal places | 0-3, default 0. Sets the resolution of the energy registers. | UINT16 | Read/write | ||||
| HR | 46448 | COM1 protocol | UINT16 | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII; 2 = DNP3.0; 7 = IEC 60870-5 | ||||
| HR | 46450 | COM1 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 46451 | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 46452 | COM1 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity |
Notes on this map
- Addressing: the guide says to add 40001 to a register address to get the Modicon holding-register number (400001 above 9999), so printed addresses are 0-based wire addresses.
- Word order: 32-bit values are sent with the low-order word in the first (even) register and the high-order word in the second, so they are CDAB here.
- Units U1 (voltage) and U3 (power) depend on the PT ratio: with PT ratio = 1 they are 0.1 V and 0.001 kW/kvar/kVA (the scales used here); with PT ratio > 1 they become 1 V and 1 kW/kvar/kVA. U2 (current) is always 0.01 A.
- Function 04 can be used the same way as function 03.
- Energy registers use unit U5, set by 'number of energy decimal places' (46258, 0-3, default 0). The scale here (1 kWh/kvarh/kVAh) is for the default; with 1, 2 or 3 decimals use 0.1, 0.01 or 0.001.
- The Total Energies block header prints 14720-14741, but its rows run to +42,43 (kvarh Q4 at 14762); the per-row offsets are used here.
- V4 voltage (14476) uses unit U4 (V4 PT ratio) and is left out.
- Left out: 16-bit scaled registers, 1/2-cycle, 0.2-second and 3-second values, low/high phase values, harmonics and interharmonics, IEEE 519 statistics, min/max logs, billing/TOU, setpoints, files and COM2-COM5 settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SATEC PM180 expertmeter high performance analyzer
What Modbus registers does the SATEC PM180 expertmeter high performance analyzer have?
This map lists 129 registers: 129 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SATEC PM180 expertmeter high performance analyzer Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 0 and says to add 40001 (or 400001 above 9999) to get Modicon holding-register numbers, so the printed address is the wire address: 13952 is requested as 13952 (Modicon 413953).
What byte order does the SATEC PM180 expertmeter high performance analyzer use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the SATEC PM180 expertmeter high performance analyzer?
Start with HR 13952 V1 voltage (V1 voltage); HR 13958 I1 current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).
How do I enable Modbus control of the SATEC PM180 expertmeter high performance analyzer?
Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.
Where is the official SATEC PM180 expertmeter high performance analyzer Modbus documentation?
The source is expertmeter PM180 High Performance Analyzer - Modbus Communications Protocol Reference Guide (BG0527 Rev. A11), revision 2024-09, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2023/12/PM180-Modbus.pdf.
More SATEC Modbus register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Energy meter (multifunction)
SATEC EM133-R residential multifunction meter
SATEC EM133-R (and EM133-XM) multifunction meters, per Modbus reference guide BG0520 Rev. A6 (Oct 2018).
Also known as: EM133, EM133-R, EM133-XM, SATEC EM133 - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175
Other power & energy meters register maps
- Power meter (multi-circuit)
Setra Systems Setra Power Meter (SPM) multi-circuit power meter
Setra Power Meter (SPM) family, per Modbus register master list SS-SPM-MODBUS_G; this map covers the device block, both voltage inputs and Load 1.
Also known as: SPM, Setra Power Meter, SS-SPM-MODBUS_G - Energy meter (heat / cooling meter)
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
Sontex Modbus EIA-485 plug-in module in a Supercal 531 integrator or Superstatic 440/449 heat meter, integrator firmware 3.7 or later; user manual V05 (2019-09).
Also known as: Supercal 531, Superstatic 440, Superstatic 449, Sontex Modbus EIA-485 module, 0531P217 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Power meter
Accuenergy AcuRev 1310 series DIN-rail power meter
Accuenergy AcuRev 1310 series (1312/1313/1314) DIN-rail meters, Modbus map workbook revision 1.1.
Also known as: AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 - Power meter (universal measuring / power quality device)
Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)
SINEAX CAM with Ethernet (Modbus/TCP) bus card; document W 157471, change 2014-018. Instantaneous values, THD/TDD, system analysis, analog inputs, I/O states.
Also known as: SINEAX CAM, CAM - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB
All power & energy meters Modbus register maps →
Source: expertmeter PM180 High Performance Analyzer - Modbus Communications Protocol Reference Guide · BG0527 Rev. A11 · rev. 2024-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.