Power meter (power quality analyzer) · Modbus register map

SATEC PM180 expertmeter high performance analyzer Modbus register map

Updated 17 November 2026

Short answer

The PM180 expertmeter is SATEC's high-performance power quality analyzer with serial, Ethernet and expandable I/O. Its 32-bit register set carries 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, THD, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, COM1 settings, password and clear commands.

This page lists 129 Modbus registers for the SATEC PM180 expertmeter high performance analyzer — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.

Manufacturer
SATEC
Model
PM180 expertmeter high performance analyzer
Equipment type
Power meter (power quality analyzer)
Registers
129 (13 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
PM180, expertmeter PM180, SATEC PM180
Source document
expertmeter PM180 High Performance Analyzer - Modbus Communications Protocol Reference Guide · BG0527 Rev. A11 · rev. 2024-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: SATEC PM180 expertmeter high performance analyzer

Integration in brief

Read 13952 onward (phase values) and 14336 onward (totals) with function 03; decode 32-bit integers low word first. Energy totals start at 14720; check the energy decimal places setting (46258) before scaling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13952V1 voltageUINT32 CDABV1 voltageRead
HR 13958I1 currentUINT32 CDABI1 currentRead
HR 14336Total kWINT32 CDABTotal kWRead
HR 14342Total PFINT32 CDABTotal PFRead
HR 14468FrequencyUINT32 CDABFrequencyRead
HR 14720kWh importUINT32 CDABkWh importRead
HR 14722kWh exportUINT32 CDABkWh exportRead

Enable Modbus control & writes

Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.

Byte order & addressing

Network setup

Watch out for

SATEC PM180 expertmeter high performance analyzer Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

129 of 129 shown
SATEC PM180 expertmeter high performance analyzer Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR11906doc 11906-11907Phase rotation orderUINT32CDABRead0 = Error; 1 = Positive (ABC); 2 = Negative (CBA)
HR12544doc 12544-12545Digital inputs (bitmap)Bit 0 = DI1, bit 1 = DI2, and so on.UINT32CDABRead
HR12800doc 12800-12801Relay outputs (bitmap)Bit 0 = RO1, bit 1 = RO2, and so on.UINT32CDABRead
HR13952doc 13952-13953V1 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR13954doc 13954-13955V2 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR13956doc 13956-13957V3 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR13958doc 13958-13959I1 currentUINT32CDAB× 0.01ARead
HR13960doc 13960-13961I2 currentUINT32CDAB× 0.01ARead
HR13962doc 13962-13963I3 currentUINT32CDAB× 0.01ARead
HR13964doc 13964-13965kW L1Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.INT32CDAB× 0.001kWRead
HR13966doc 13966-13967kW L2Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.INT32CDAB× 0.001kWRead
HR13968doc 13968-13969kW L3Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.INT32CDAB× 0.001kWRead
HR13970doc 13970-13971kvar L1Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.INT32CDAB× 0.001kvarRead
HR13972doc 13972-13973kvar L2Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.INT32CDAB× 0.001kvarRead
HR13974doc 13974-13975kvar L3Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.INT32CDAB× 0.001kvarRead
HR13976doc 13976-13977kVA L1Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR13978doc 13978-13979kVA L2Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR13980doc 13980-13981kVA L3Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR13982doc 13982-13983Power factor L1INT32CDAB× 0.001Read
HR13984doc 13984-13985Power factor L2INT32CDAB× 0.001Read
HR13986doc 13986-13987Power factor L3INT32CDAB× 0.001Read
HR13988doc 13988-13989V1 voltage THDUINT32CDAB× 0.1%Read
HR13990doc 13990-13991V2 voltage THDUINT32CDAB× 0.1%Read
HR13992doc 13992-13993V3 voltage THDUINT32CDAB× 0.1%Read
HR13994doc 13994-13995I1 current THDUINT32CDAB× 0.1%Read
HR13996doc 13996-13997I2 current THDUINT32CDAB× 0.1%Read
HR13998doc 13998-13999I3 current THDUINT32CDAB× 0.1%Read
HR14000doc 14000-14001I1 K-FactorUINT32CDAB× 0.1Read
HR14002doc 14002-14003I2 K-FactorUINT32CDAB× 0.1Read
HR14004doc 14004-14005I3 K-FactorUINT32CDAB× 0.1Read
HR14006doc 14006-14007I1 current TDDUINT32CDAB× 0.1%Read
HR14008doc 14008-14009I2 current TDDUINT32CDAB× 0.1%Read
HR14010doc 14010-14011I3 current TDDUINT32CDAB× 0.1%Read
HR14012doc 14012-14013V12 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14014doc 14014-14015V23 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14016doc 14016-14017V31 voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14018doc 14018-14019I1x currentUINT32CDAB× 0.01ARead
HR14020doc 14020-14021I2x currentUINT32CDAB× 0.01ARead
HR14022doc 14022-14023I3x currentUINT32CDAB× 0.01ARead
HR14024doc 14024-14025V1x VoltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14026doc 14026-14027V2x VoltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14028doc 14028-14029V3x VoltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14336doc 14336-14337Total kWScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.INT32CDAB× 0.001kWRead
HR14338doc 14338-14339Total kvarScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.INT32CDAB× 0.001kvarRead
HR14340doc 14340-14341Total kVAScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR14342doc 14342-14343Total PFINT32CDAB× 0.001Read
HR14344doc 14344-14345Total PF lagUINT32CDAB× 0.001Read
HR14346doc 14346-14347Total PF leadUINT32CDAB× 0.001Read
HR14348doc 14348-14349Total kW importScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14350doc 14350-14351Total kW exportScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14352doc 14352-14353Total kvar importScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14354doc 14354-14355Total kvar exportScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14356doc 14356-143573-phase average L-N voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14358doc 14358-143593-phase average L-L voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14360doc 14360-143613-phase average currentUINT32CDAB× 0.01ARead
HR14362doc 14362-143633-phase average current, extended inputs I1x-I3xUINT32CDAB× 0.01ARead
HR14464doc 14464-14465I4 currentUINT32CDAB× 0.01ARead
HR14466doc 14466-14467In currentUINT32CDAB× 0.01ARead
HR14468doc 14468-14469FrequencyUINT32CDAB× 0.01HzRead
HR14470doc 14470-14471Voltage unbalanceUINT32CDAB× 0.1%Read
HR14472doc 14472-14473Current unbalanceUINT32CDAB× 0.1%Read
HR14478doc 14478-14479I4x currentUINT32CDAB× 0.01ARead
HR14480doc 14480-14481V4x (neutral-ground) voltageScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14482doc 14482-14483Internal temperatureINT32CDAB× 0.1ºCRead
HR14484doc 14484-14485Frequency (3 decimals)UINT32CDAB× 0.001HzRead
HR14486doc 14486-14487Lithium battery voltageUINT32CDAB× 0.001VRead
HR14490doc 14490-14491Frequency (4 decimals)UINT32CDAB× 0.0001HzRead
HR14496doc 14496-14497Active power oscillation, Posc%UINT32CDAB× 0.01%Read
HR14592doc 14592-14593V1 volt demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14594doc 14594-14595V2 volt demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14596doc 14596-14597V3 volt demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 V.UINT32CDAB× 0.1VRead
HR14598doc 14598-14599I1 ampere demandUINT32CDAB× 0.01ARead
HR14600doc 14600-14601I2 ampere demandUINT32CDAB× 0.01ARead
HR14602doc 14602-14603I3 ampere demandUINT32CDAB× 0.01ARead
HR14604doc 14604-14605kW import block demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14606doc 14606-14607kvar import block demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14608doc 14608-14609kVA block demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR14610doc 14610-14611kW import sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14612doc 14612-14613kvar import sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14614doc 14614-14615kVA sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR14622doc 14622-14623kW import accumulated demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14624doc 14624-14625kvar import accumulated demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14626doc 14626-14627kVA accumulated demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR14628doc 14628-14629kW import predicted sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14630doc 14630-14631kvar import predicted sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14632doc 14632-14633kVA predicted sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA.UINT32CDAB× 0.001kVARead
HR14634doc 14634-14635PF (import) at Max. kVA sliding window demandUINT32CDAB× 0.001Read
HR14636doc 14636-14637kW export block demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14638doc 14638-14639kvar export block demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14640doc 14640-14641kW export sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14642doc 14642-14643kvar export sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14644doc 14644-14645kW export accumulated demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14646doc 14646-14647kvar export accumulated demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14648doc 14648-14649kW export predicted sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW.UINT32CDAB× 0.001kWRead
HR14650doc 14650-14651kvar export predicted sliding window demandScale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar.UINT32CDAB× 0.001kvarRead
HR14658doc 14658-14659I4 ampere demandUINT32CDAB× 0.01ARead
HR14660doc 14660-14661In ampere demandUINT32CDAB× 0.01ARead
HR14720doc 14720-14721kWh importWhole units at the default 0 energy decimal places (46258).UINT32CDABkWhRead
HR14722doc 14722-14723kWh exportWhole units at the default 0 energy decimal places (46258).UINT32CDABkWhRead
HR14724doc 14724-14725kWh netWhole units at the default 0 energy decimal places (46258).INT32CDABkWhRead
HR14726doc 14726-14727kWh totalWhole units at the default 0 energy decimal places (46258).UINT32CDABkWhRead
HR14728doc 14728-14729kvarh importWhole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14730doc 14730-14731kvarh exportWhole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14732doc 14732-14733kvarh netWhole units at the default 0 energy decimal places (46258).INT32CDABkvarhRead
HR14734doc 14734-14735kvarh totalWhole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14736doc 14736-14737kVAh totalWhole units at the default 0 energy decimal places (46258).UINT32CDABkVAhRead
HR14738doc 14738-14739Vh totalUINT32CDABVhRead
HR14740doc 14740-14741Ah totalUINT32CDABAhRead
HR14742doc 14742-14743kVAh importWhole units at the default 0 energy decimal places (46258).UINT32CDABkVAhRead
HR14744doc 14744-14745kVAh exportWhole units at the default 0 energy decimal places (46258).UINT32CDABkVAhRead
HR14756doc 14756-14757kvarh Q1Whole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14758doc 14758-14759kvarh Q2Whole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14760doc 14760-14761kvarh Q3Whole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR14762doc 14762-14763kvarh Q4Whole units at the default 0 energy decimal places (46258).UINT32CDABkvarhRead
HR44102Clear energiesWrite 0.UINT16Write
HR44107Clear min/max logWrite 0.UINT16Write
HR44378doc 44378-44379Device authorization (8-digit password)Write the password before setup writes; reads 0 = allowed, -1 = needed.INT32CDABRead/write
HR46080doc 46080-46081Device serial numberUINT32CDABRead
HR46082doc 46082-46083Device model ID18000 for PM180.UINT32CDABRead
HR46208Wiring modeUINT16Read/write0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings
HR46209PT ratio10-65000 = 1.0-6500.0.UINT16× 0.1Read/write
HR46213CT primary current1-30000 A.UINT16ARead/write
HR46225Nominal line frequency50 or 60.UINT16HzRead/write
HR46226Phase orderUINT16Read/write0 = ABC; 1 = CBA
HR46258Number of energy decimal places0-3, default 0. Sets the resolution of the energy registers.UINT16Read/write
HR46448COM1 protocolUINT16Read/write0 = Modbus RTU; 1 = Modbus ASCII; 2 = DNP3.0; 7 = IEC 60870-5
HR46450COM1 device addressModbus 1-247.UINT16Read/write
HR46451COM1 baud rateUINT16Read/write1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR46452COM1 data formatUINT16Read/write0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the SATEC PM180 expertmeter high performance analyzer

What Modbus registers does the SATEC PM180 expertmeter high performance analyzer have?

This map lists 129 registers: 129 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the SATEC PM180 expertmeter high performance analyzer Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 0 and says to add 40001 (or 400001 above 9999) to get Modicon holding-register numbers, so the printed address is the wire address: 13952 is requested as 13952 (Modicon 413953).

What byte order does the SATEC PM180 expertmeter high performance analyzer use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the SATEC PM180 expertmeter high performance analyzer?

Start with HR 13952 V1 voltage (V1 voltage); HR 13958 I1 current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).

How do I enable Modbus control of the SATEC PM180 expertmeter high performance analyzer?

Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.

Where is the official SATEC PM180 expertmeter high performance analyzer Modbus documentation?

The source is expertmeter PM180 High Performance Analyzer - Modbus Communications Protocol Reference Guide (BG0527 Rev. A11), revision 2024-09, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2023/12/PM180-Modbus.pdf.

More SATEC Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: expertmeter PM180 High Performance Analyzer - Modbus Communications Protocol Reference Guide · BG0527 Rev. A11 · rev. 2024-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.