Power meter (multi-circuit branch feeder monitor) · Modbus register map

SATEC BFM136/036 branch feeder monitor Modbus register map

Updated 17 November 2026

Short answer

The BFM136/036 measures up to 36 current channels grouped into submeters (12 three-phase submeters by default) on shared voltage inputs. Each submeter answers on its own Modbus address counted up from the device base address, and every submeter exposes the same register map. This map covers the 1-second phase, total and auxiliary values, present demands and energy totals in 32-bit integer form, plus wiring, CT/PT, COM1 and password setup.

This page lists 72 Modbus registers for the SATEC BFM136/036 branch feeder monitor — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.

Manufacturer
SATEC
Model
BFM136/036 branch feeder monitor
Equipment type
Power meter (multi-circuit branch feeder monitor)
Registers
72 (11 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Exported kWh/kvarh and exported kW/kvar demands need firmware 18.5.1 or later
Also known as
BFM136, BFM036, BFM 136, SATEC BFM136
Source document
Branch Feeder Monitor BFM136/036 - MODBUS Communications Protocol Reference Guide · BG0395 Rev. A8 · rev. 2024-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: SATEC BFM136/036 branch feeder monitor

Integration in brief

Poll each submeter's address with FC 03: 13952-14017 for phase values, 14336-14355 for totals, 14464-14473 for frequency and unbalance, and 14720 onward for energy. Decode 32-bit integers low word first and apply the PT-ratio-dependent units.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13952V1 VoltageUINT32 CDABV1 voltageRead
HR 13958I1 CurrentUINT32 CDABI1 currentRead
HR 14336Total kWINT32 CDABSubmeter total kWRead
HR 14342Total PFINT32 CDABSubmeter total PFRead
HR 14468FrequencyUINT32 CDABFrequencyRead
HR 14720kWh importUINT32 CDABkWh importRead
HR 14722kWh exportUINT32 CDABkWh exportRead

Enable Modbus control & writes

Pick Modbus RTU or ASCII and the base address in the COM1 setup (46448-46452) or on the front panel; Modbus/TCP runs on the Ethernet option at port 502 (network setup at 46576).

Byte order & addressing

Network setup

Watch out for

SATEC BFM136/036 branch feeder monitor Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

72 of 72 shown
SATEC BFM136/036 branch feeder monitor Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR13952doc 13952-13953V1 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR13954doc 13954-13955V2 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR13956doc 13956-13957V3 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR13958doc 13958-13959I1 CurrentUINT32CDAB× 0.01ARead
HR13960doc 13960-13961I2 CurrentUINT32CDAB× 0.01ARead
HR13962doc 13962-13963I3 CurrentUINT32CDAB× 0.01ARead
HR13964doc 13964-13965kW L10.001 kW with PT ratio 1; 1 kW when PT ratio > 1.INT32CDAB× 0.001kWRead
HR13966doc 13966-13967kW L20.001 kW with PT ratio 1; 1 kW when PT ratio > 1.INT32CDAB× 0.001kWRead
HR13968doc 13968-13969kW L30.001 kW with PT ratio 1; 1 kW when PT ratio > 1.INT32CDAB× 0.001kWRead
HR13970doc 13970-13971kvar L10.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.INT32CDAB× 0.001kvarRead
HR13972doc 13972-13973kvar L20.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.INT32CDAB× 0.001kvarRead
HR13974doc 13974-13975kvar L30.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.INT32CDAB× 0.001kvarRead
HR13976doc 13976-13977kVA L10.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR13978doc 13978-13979kVA L20.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR13980doc 13980-13981kVA L30.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR13982doc 13982-13983Power factor L1INT32CDAB× 0.001Read
HR13984doc 13984-13985Power factor L2INT32CDAB× 0.001Read
HR13986doc 13986-13987Power factor L3INT32CDAB× 0.001Read
HR14012doc 14012-14013V12 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14014doc 14014-14015V23 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14016doc 14016-14017V31 Voltage0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14336doc 14336-14337Total kW0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.INT32CDAB× 0.001kWRead
HR14338doc 14338-14339Total kvar0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.INT32CDAB× 0.001kvarRead
HR14340doc 14340-14341Total kVA0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR14342doc 14342-14343Total PFINT32CDAB× 0.001Read
HR14344doc 14344-14345Total PF lagUINT32CDAB× 0.001Read
HR14346doc 14346-14347Total PF leadUINT32CDAB× 0.001Read
HR14348doc 14348-14349Total kW import0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14350doc 14350-14351Total kW export0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14352doc 14352-14353Total kvar import0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14354doc 14354-14355Total kvar export0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14466doc 14466-14467In (neutral) CurrentUINT32CDAB× 0.01ARead
HR14468doc 14468-14469FrequencyUINT32CDAB× 0.01HzRead
HR14470doc 14470-14471Voltage unbalanceUINT32CDAB× 0.1%Read
HR14472doc 14472-14473Current unbalanceUINT32CDAB× 0.1%Read
HR14592doc 14592-14593V1 Volt demand0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14594doc 14594-14595V2 Volt demand0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14596doc 14596-14597V3 Volt demand0.1 V with PT ratio 1; 1 V when PT ratio > 1.UINT32CDAB× 0.1VRead
HR14598doc 14598-14599I1 Ampere demandUINT32CDAB× 0.01ARead
HR14600doc 14600-14601I2 Ampere demandUINT32CDAB× 0.01ARead
HR14602doc 14602-14603I3 Ampere demandUINT32CDAB× 0.01ARead
HR14610doc 14610-14611kW import sliding window demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14612doc 14612-14613kvar import sliding window demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14614doc 14614-14615kVA sliding window demand0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR14622doc 14622-14623kW import accumulated demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14624doc 14624-14625kvar import accumulated demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14626doc 14626-14627kVA accumulated demand0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR14628doc 14628-14629kW import predicted sliding window demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14630doc 14630-14631kvar import predicted sliding window demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14632doc 14632-14633kVA predicted sliding window demand0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1.UINT32CDAB× 0.001kVARead
HR14640doc 14640-14641kW export sliding window demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14642doc 14642-14643kvar export sliding window demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14644doc 14644-14645kW export accumulated demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14646doc 14646-14647kvar export accumulated demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14648doc 14648-14649kW export predicted sliding window demand0.001 kW with PT ratio 1; 1 kW when PT ratio > 1.UINT32CDAB× 0.001kWRead
HR14650doc 14650-14651kvar export predicted sliding window demand0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1.UINT32CDAB× 0.001kvarRead
HR14720doc 14720-14721kWh importUINT32CDAB× 0.1kWhRead
HR14722doc 14722-14723kWh exportUINT32CDAB× 0.1kWhRead
HR14728doc 14728-14729kvarh importUINT32CDAB× 0.1kvarhRead
HR14730doc 14730-14731kvarh exportUINT32CDAB× 0.1kvarhRead
HR14736doc 14736-14737kVAh totalUINT32CDAB× 0.1kVAhRead
HR44378doc 44378-44379Device authorization (password)Write the 8-digit password; reads 0 = access permitted, -1 = password needed.INT32CDABRead/write
HR46208doc 46208 (+0)Wiring modeBasic setup; shared across submeters.UINT16Read/write1 = 4LN3 (4-wire WYE)
HR46209doc 46208 (+1)PT ratioPrimary-to-secondary ratio, 10-65000 raw.UINT16× 0.1Read/write
HR46213doc 46208 (+5)CT primary current1-10000 A.UINT16ARead/write
HR46214doc 46208 (+6)CT secondary currentUINT16ARead/write1 = 1 A; 5 = 5 A; 50 = 50 A
HR46225doc 46208 (+17)Nominal line frequency50 or 60.UINT16HzRead/write
HR46448doc 46448 (+0)COM1 protocolUINT16Read/write0 = Modbus RTU; 1 = Modbus ASCII
HR46450doc 46448 (+2)COM1 device reference addressBase Modbus address of submeter 1 (1-247).UINT16Read/write
HR46451doc 46448 (+3)COM1 baud rateUINT16Read/write1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR46452doc 46448 (+4)COM1 data formatUINT16Read/write0 = 7 bits / even parity; 1 = 8 bits / no parity; 2 = 8 bits / even parity
HR46710doc 46704 (+2)Password protection enableUINT16Read/write0 = Disabled; 1 = Enabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the SATEC BFM136/036 branch feeder monitor

What Modbus registers does the SATEC BFM136/036 branch feeder monitor have?

This map lists 72 registers: 72 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the SATEC BFM136/036 branch feeder monitor Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers 0-65535 and says to add 40001 (or 400001 above 9999) to get the Modicon holding-register number, so printed addresses go straight into the frame: 13952 is wire address 13952 (Modicon 413953).

What byte order does the SATEC BFM136/036 branch feeder monitor use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the SATEC BFM136/036 branch feeder monitor?

Start with HR 13952 V1 Voltage (V1 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Submeter total kW); HR 14342 Total PF (Submeter total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).

How do I enable Modbus control of the SATEC BFM136/036 branch feeder monitor?

Pick Modbus RTU or ASCII and the base address in the COM1 setup (46448-46452) or on the front panel; Modbus/TCP runs on the Ethernet option at port 502 (network setup at 46576).

Where is the official SATEC BFM136/036 branch feeder monitor Modbus documentation?

The source is Branch Feeder Monitor BFM136/036 - MODBUS Communications Protocol Reference Guide (BG0395 Rev. A8), revision 2024-07, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2025/09/BFM136__036_MODBUS_Com_Guide.pdf.