- Home
- Modbus register maps
- SATEC
- BFM136/036 branch feeder monitor
Power meter (multi-circuit branch feeder monitor) · Modbus register map
SATEC BFM136/036 branch feeder monitor Modbus register map
Updated 17 November 2026
The BFM136/036 measures up to 36 current channels grouped into submeters (12 three-phase submeters by default) on shared voltage inputs. Each submeter answers on its own Modbus address counted up from the device base address, and every submeter exposes the same register map. This map covers the 1-second phase, total and auxiliary values, present demands and energy totals in 32-bit integer form, plus wiring, CT/PT, COM1 and password setup.
This page lists 72 Modbus registers for the SATEC BFM136/036 branch feeder monitor — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- SATEC
- Model
- BFM136/036 branch feeder monitor
- Equipment type
- Power meter (multi-circuit branch feeder monitor)
- Registers
- 72 (11 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Exported kWh/kvarh and exported kW/kvar demands need firmware 18.5.1 or later
- Also known as
- BFM136, BFM036, BFM 136, SATEC BFM136
Integration notes: SATEC BFM136/036 branch feeder monitor
Poll each submeter's address with FC 03: 13952-14017 for phase values, 14336-14355 for totals, 14464-14473 for frequency and unbalance, and 14720 onward for energy. Decode 32-bit integers low word first and apply the PT-ratio-dependent units.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1 Voltage | UINT32 CDAB | V1 voltage | Read |
| HR 13958 | I1 Current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Submeter total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Submeter total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 14722 | kWh export | UINT32 CDAB | kWh export | Read |
Enable Modbus control & writes
Pick Modbus RTU or ASCII and the base address in the COM1 setup (46448-46452) or on the front panel; Modbus/TCP runs on the Ethernet option at port 502 (network setup at 46576).
Byte order & addressing
- One physical device answers on many slave addresses: one per active submeter, counted up from the base address.
- 32-bit values are low word first (CDAB); the low word always sits at an even address.
- Voltage and power units jump from 0.1 V / 0.001 kW to 1 V / 1 kW when a PT ratio above 1 is configured.
Network setup
- Leave address gaps between devices on one bus: with 12 submeters each, use base addresses 1, 13, 25 and so on.
- Assign submeters without gaps in the channel assignment setup so the device does not use extra addresses.
- If password protection is on, write the password to 44378-44379 before any write.
Watch out for
- Broadcast address 0 is not supported.
- FC 04 returns the same data as FC 03.
SATEC BFM136/036 branch feeder monitor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 13952doc 13952-13953 | V1 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13954doc 13954-13955 | V2 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13956doc 13956-13957 | V3 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13958doc 13958-13959 | I1 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13960doc 13960-13961 | I2 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13962doc 13962-13963 | I3 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13966doc 13966-13967 | kW L2 | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13968doc 13968-13969 | kW L3 | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13970doc 13970-13971 | kvar L1 | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13972doc 13972-13973 | kvar L2 | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13974doc 13974-13975 | kvar L3 | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13976doc 13976-13977 | kVA L1 | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13978doc 13978-13979 | kVA L2 | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13980doc 13980-13981 | kVA L3 | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14012doc 14012-14013 | V12 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14014doc 14014-14015 | V23 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14016doc 14016-14017 | V31 Voltage | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14336doc 14336-14337 | Total kW | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14338doc 14338-14339 | Total kvar | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14340doc 14340-14341 | Total kVA | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14344doc 14344-14345 | Total PF lag | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14346doc 14346-14347 | Total PF lead | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14350doc 14350-14351 | Total kW export | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14352doc 14352-14353 | Total kvar import | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14354doc 14354-14355 | Total kvar export | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14466doc 14466-14467 | In (neutral) Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14470doc 14470-14471 | Voltage unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14472doc 14472-14473 | Current unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14592doc 14592-14593 | V1 Volt demand | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14594doc 14594-14595 | V2 Volt demand | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14596doc 14596-14597 | V3 Volt demand | 0.1 V with PT ratio 1; 1 V when PT ratio > 1. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14598doc 14598-14599 | I1 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14600doc 14600-14601 | I2 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14602doc 14602-14603 | I3 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14610doc 14610-14611 | kW import sliding window demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14612doc 14612-14613 | kvar import sliding window demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14614doc 14614-14615 | kVA sliding window demand | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14622doc 14622-14623 | kW import accumulated demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14624doc 14624-14625 | kvar import accumulated demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14626doc 14626-14627 | kVA accumulated demand | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | 0.001 kVA with PT ratio 1; 1 kVA when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14640doc 14640-14641 | kW export sliding window demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14642doc 14642-14643 | kvar export sliding window demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14644doc 14644-14645 | kW export accumulated demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14646doc 14646-14647 | kvar export accumulated demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | 0.001 kW with PT ratio 1; 1 kW when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | 0.001 kvar with PT ratio 1; 1 kvar when PT ratio > 1. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14720doc 14720-14721 | kWh import | UINT32 | CDAB | × 0.1 | kWh | Read | ||
| HR | 14722doc 14722-14723 | kWh export | UINT32 | CDAB | × 0.1 | kWh | Read | ||
| HR | 14728doc 14728-14729 | kvarh import | UINT32 | CDAB | × 0.1 | kvarh | Read | ||
| HR | 14730doc 14730-14731 | kvarh export | UINT32 | CDAB | × 0.1 | kvarh | Read | ||
| HR | 14736doc 14736-14737 | kVAh total | UINT32 | CDAB | × 0.1 | kVAh | Read | ||
| HR | 44378doc 44378-44379 | Device authorization (password) | Write the 8-digit password; reads 0 = access permitted, -1 = password needed. | INT32 | CDAB | Read/write | |||
| HR | 46208doc 46208 (+0) | Wiring mode | Basic setup; shared across submeters. | UINT16 | Read/write | 1 = 4LN3 (4-wire WYE) | |||
| HR | 46209doc 46208 (+1) | PT ratio | Primary-to-secondary ratio, 10-65000 raw. | UINT16 | × 0.1 | Read/write | |||
| HR | 46213doc 46208 (+5) | CT primary current | 1-10000 A. | UINT16 | A | Read/write | |||
| HR | 46214doc 46208 (+6) | CT secondary current | UINT16 | A | Read/write | 1 = 1 A; 5 = 5 A; 50 = 50 A | |||
| HR | 46225doc 46208 (+17) | Nominal line frequency | 50 or 60. | UINT16 | Hz | Read/write | |||
| HR | 46448doc 46448 (+0) | COM1 protocol | UINT16 | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII | ||||
| HR | 46450doc 46448 (+2) | COM1 device reference address | Base Modbus address of submeter 1 (1-247). | UINT16 | Read/write | ||||
| HR | 46451doc 46448 (+3) | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 46452doc 46448 (+4) | COM1 data format | UINT16 | Read/write | 0 = 7 bits / even parity; 1 = 8 bits / no parity; 2 = 8 bits / even parity | ||||
| HR | 46710doc 46704 (+2) | Password protection enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled |
Notes on this map
- Each submeter has its own Modbus slave address: submeter 1 = device base address N, submeter 2 = N+1 and so on (up to 40 addresses). The factory base address is 1 and the device occupies addresses 1-12 (12 three-phase submeters). Read the measurement registers from each submeter's address.
- Setup registers are shared by all submeters and can be written through any submeter address, except the COM port setup, which only the base address accepts.
- 32-bit values carry the low-order word in the first (even) register, so they are listed CDAB.
- Units U1 (voltage) and U3 (power) depend on PT ratio: with PT ratio 1 they are 0.1 V and 0.001 kW/kvar/kVA (the scales used here); with PT ratio above 1 they become 1 V and 1 kW/kvar/kVA. U2 (current) is always 0.01 A.
- Energy totals are in 0.1 kWh / 0.1 kvarh / 0.1 kVAh steps and roll over at the energy roll value set in the device options.
- Left out: 16-bit scaled registers (need per-site HI/LO arithmetic), 1-cycle values, phasors, min/max logs, maximum demands and the Billing/TOU tariff registers (the maximum-demand table repeats a 'V2' row label where V3 is expected), setpoints and file-transfer blocks.
- The guide's basic setup block (46208-46271) and demand setup block (46240-46255) overlap as printed; only basic setup offsets +0 to +17 are listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SATEC BFM136/036 branch feeder monitor
What Modbus registers does the SATEC BFM136/036 branch feeder monitor have?
This map lists 72 registers: 72 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SATEC BFM136/036 branch feeder monitor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers 0-65535 and says to add 40001 (or 400001 above 9999) to get the Modicon holding-register number, so printed addresses go straight into the frame: 13952 is wire address 13952 (Modicon 413953).
What byte order does the SATEC BFM136/036 branch feeder monitor use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the SATEC BFM136/036 branch feeder monitor?
Start with HR 13952 V1 Voltage (V1 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Submeter total kW); HR 14342 Total PF (Submeter total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).
How do I enable Modbus control of the SATEC BFM136/036 branch feeder monitor?
Pick Modbus RTU or ASCII and the base address in the COM1 setup (46448-46452) or on the front panel; Modbus/TCP runs on the Ethernet option at port 502 (network setup at 46576).
Where is the official SATEC BFM136/036 branch feeder monitor Modbus documentation?
The source is Branch Feeder Monitor BFM136/036 - MODBUS Communications Protocol Reference Guide (BG0395 Rev. A8), revision 2024-07, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2025/09/BFM136__036_MODBUS_Com_Guide.pdf.
More SATEC Modbus register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Energy meter (multifunction)
SATEC EM133-R residential multifunction meter
SATEC EM133-R (and EM133-XM) multifunction meters, per Modbus reference guide BG0520 Rev. A6 (Oct 2018).
Also known as: EM133, EM133-R, EM133-XM, SATEC EM133 - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180
Other power & energy meters register maps
- Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter
Accuenergy Acuvim-L Series
Accuenergy Acuvim-L series multifunction power and energy meters, user manual V4 (V 4.1.12, revised March 2026).
Also known as: Acuvim-CL, Acuvim-EL - Energy meter (DC)
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)
DCT1 300 A and 600 A / 1000 V DC meters, with and without signed data (S1/S2/S3), protocol version 1.1.
Also known as: DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC
All power & energy meters Modbus register maps →
Source: Branch Feeder Monitor BFM136/036 - MODBUS Communications Protocol Reference Guide · BG0395 Rev. A8 · rev. 2024-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.