  4. ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)

Power meter (circuit breaker trip unit) · Modbus register map

Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) Modbus register map

Updated 19 November 2026

Short answer

MicroLogic trip units in ComPact NSX breakers are read over Modbus through an IFM serial interface or an IFE Ethernet interface. Schneider publishes a 'standard dataset' at registers 32000-32341 that gathers breaker status, trip causes, currents, voltages, power, energy, demand and power factor in one block. Floats and 64-bit energies are big-endian; values are already in engineering units.

This page lists 98 Modbus registers for the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Equipment type
Power meter (circuit breaker trip unit)
Registers
98 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ
Source document
ComPact NSX - Modbus Communication User Guide · DOCA0091EN-09 · rev. 2022-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)

Integration in brief

Read the dataset with function 03 in three requests, as the guide does: 32000-32123, 32124-32241 and 32340 onward. Breaker status is at 32001, currents from 32028, voltages from 32056, power from 32072, energy from 32096, power factor at 32206-32213.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 32000Circuit breaker statusBITMAP16Open/closed/tripped statusRead
HR 32006Tripping cause, standard protectionsBITMAP16Trip causeRead
HR 32027RMS current phase 1FLOAT32 ABCDPhase 1 currentRead
HR 32055Voltage V12FLOAT32 ABCDVoltage V12Read
HR 32077Total active powerFLOAT32 ABCDTotal active powerRead
HR 32095Total active energyINT64 ABCDTotal active energyRead
HR 32211Total power factorFLOAT32 ABCDTotal power factorRead

Enable Modbus control & writes

Fit an IFM (RS-485 Modbus) or IFE (Ethernet) interface and connect it to the trip unit over the ULP cord. No enable step is needed to read the dataset; remote control needs the locking pad open and the command interface.

Byte order & addressing

Network setup

Watch out for

Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

98 of 98 shown
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR31999doc 32000Quality of breaker status bitsPer-bit validity for 32001 (1 = valid).UINT16Read
HR32000doc 32001Circuit breaker statusCheck the validity bits in the preceding register.BITMAP16Readbit 0 = OF contact: 1 = closed, 0 = open; bit 1 = SD trip indication: 1 = tripped; bit 2 = SDE fault-trip indication: 1 = tripped on electrical fault; bit 3 = CH spring charged (MasterPact only); bit 5 = PF ready to close (MasterPact only); bit 15 = 1 = data not available
HR32006doc 32007Tripping cause, standard protectionsCheck the validity bits in the preceding register.BITMAP16Readbit 0 = Long-time protection Ir; bit 1 = Short-time protection Isd; bit 2 = Instantaneous protection Ii; bit 3 = Ground-fault protection Ig; bit 4 = Earth-leakage protection IΔn; bit 5 = Integrated instantaneous protection; bit 6 = Internal failure (STOP) on NSX; other protections / internal temperature on NT/NW/NS; bit 7 = Internal failure (overvoltage); bit 8 = Other protection (see 32009); bit 10 = Motor unbalance (NSX); bit 11 = Motor jam (NSX); bit 12 = Motor underload (NSX); bit 13 = Motor long start (NSX); bit 14 = Reflex tripping (NSX); bit 15 = 1 = bits 0-14 not valid
HR32008doc 32009Tripping cause, advanced protectionsNT/NW/NS P and H trip units; validity bits in 32008.BITMAP16Readbit 0 = Current unbalance; bit 1 = Overcurrent phase 1; bit 2 = Overcurrent phase 2; bit 3 = Overcurrent phase 3; bit 4 = Overcurrent neutral; bit 5 = Undervoltage; bit 6 = Overvoltage; bit 7 = Voltage unbalance; bit 8 = Overpower; bit 9 = Reverse power; bit 10 = Underfrequency; bit 11 = Overfrequency; bit 12 = Phase rotation; bit 13 = Load shedding on current; bit 14 = Load shedding on power; bit 15 = 1 = bits 0-14 not valid
HR32014doc 32015Standard protection setpoint overrunCheck the validity bits in the preceding register.BITMAP16Readbit 0 = Long-time protection pick-up; bit 15 = 1 = bit 0 not valid
HR32027doc 32028-32029RMS current phase 1Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32029doc 32030-32031RMS current phase 2Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32031doc 32032-32033RMS current phase 3Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32033doc 32034-32035RMS current neutralOnly when the system type register reads 30 or 41. Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32035doc 32036-32037Max RMS current of the most loaded phaseAvailable on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32037doc 32038-32039Ground current ratio (Ig setting ratio)Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDRead
HR32039doc 32040-32041Earth-leakage current ratio (IΔn ratio)Available on: NSX E, NT/NW/NS A/P/H, MTZ.FLOAT32ABCDRead
HR32041doc 32042-32043Maximum RMS current phase 1Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32043doc 32044-32045Maximum RMS current phase 2Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32045doc 32046-32047Maximum RMS current phase 3Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32047doc 32048-32049Maximum RMS current neutralAvailable on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32049doc 32050-32051Highest maximum current (any phase)Available on: NSX A/E, NT/NW/NS A/E/P/H, MTZ.FLOAT32ABCDARead
HR32055doc 32056-32057Voltage V12Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32057doc 32058-32059Voltage V23Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32059doc 32060-32061Voltage V31Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32061doc 32062-32063Voltage V1NOnly when the system type register reads 40 or 41. Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32063doc 32064-32065Voltage V2NOnly when the system type register reads 40 or 41. Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32065doc 32066-32067Voltage V3NOnly when the system type register reads 40 or 41. Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32067doc 32068-32069FrequencyAvailable on: NSX E, NT/NW/NS P/H, MTZ.FLOAT32ABCDHzRead
HR32069doc 32070-32071Maximum frequencyAvailable on: NSX E, NT/NW/NS P/H, MTZ.FLOAT32ABCDHzRead
HR32071doc 32072-32073Active power phase 1Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDWRead
HR32073doc 32074-32075Active power phase 2Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDWRead
HR32075doc 32076-32077Active power phase 3Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDWRead
HR32077doc 32078-32079Total active powerAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDWRead
HR32079doc 32080-32081Reactive power phase 1Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARRead
HR32081doc 32082-32083Reactive power phase 2Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARRead
HR32083doc 32084-32085Reactive power phase 3Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARRead
HR32085doc 32086-32087Total reactive powerAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARRead
HR32087doc 32088-32089Apparent power phase 1Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARead
HR32089doc 32090-32091Apparent power phase 2Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARead
HR32091doc 32092-32093Apparent power phase 3Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARead
HR32093doc 32094-32095Total apparent powerAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVARead
HR32095doc 32096-32099Total active energyAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.INT64ABCDWhRead
HR32099doc 32100-32103Total reactive energyAvailable on: NSX E, NT/NW/NS E/P/H(1), MTZ.INT64ABCDVARhRead
HR32103doc 32104-32107Active energy deliveredAvailable on: NSX E, NT/NW/NS P/H, MTZ.UINT64ABCDWhRead
HR32107doc 32108-32111Active energy receivedAvailable on: NSX E, NT/NW/NS P/H, MTZ.UINT64ABCDWhRead
HR32111doc 32112-32115Reactive energy deliveredAvailable on: NSX E, NT/NW/NS P/H, MTZ.UINT64ABCDVARhRead
HR32115doc 32116-32119Reactive energy receivedAvailable on: NSX E, NT/NW/NS P/H, MTZ.UINT64ABCDVARhRead
HR32119doc 32120-32123Total apparent energyAvailable on: NSX E, MTZ.UINT64ABCDVAhRead
HR32123doc 32124-32127Cumulative active energy delivered (non-resettable)Available on: NSX E, MTZ.UINT64ABCDWhRead
HR32127doc 32128-32131Cumulative active energy received (non-resettable)Available on: NSX E, MTZ.UINT64ABCDWhRead
HR32131doc 32132-32133Average of 3 phase currentsAvailable on: MTZ.FLOAT32ABCDARead
HR32133doc 32134-32135Average phase-to-phase voltageAvailable on: MTZ.FLOAT32ABCDVRead
HR32135doc 32136-32137Average phase-to-neutral voltageAvailable on: MTZ.FLOAT32ABCDVRead
HR32137doc 32138-32139Maximum total active powerAvailable on: MTZ.FLOAT32ABCDWRead
HR32139doc 32140-32141Maximum total reactive powerAvailable on: MTZ.FLOAT32ABCDVARRead
HR32141doc 32142-32143Maximum total apparent powerAvailable on: MTZ.FLOAT32ABCDVARead
HR32143doc 32144-32145Maximum average 3-phase currentAvailable on: MTZ.FLOAT32ABCDARead
HR32145doc 32146-32147Maximum average phase-to-phase voltageAvailable on: MTZ.FLOAT32ABCDVRead
HR32147doc 32148-32149Maximum average phase-to-neutral voltageAvailable on: MTZ.FLOAT32ABCDVRead
HR32149doc 32150-32151Ground-fault currentAvailable on: MTZ.FLOAT32ABCDARead
HR32151doc 32152-32153Earth-leakage currentAvailable on: MTZ.FLOAT32ABCDARead
HR32155doc 32156-32157Current demand phase 1Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDARead
HR32157doc 32158-32159Current demand phase 2Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDARead
HR32159doc 32160-32161Current demand phase 3Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDARead
HR32161doc 32162-32163Current demand neutralAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDARead
HR32163doc 32164-32165Total active power demandAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDWRead
HR32165doc 32166-32167Total reactive power demandAvailable on: NSX E, NT/NW/NS P/H, MTZ.FLOAT32ABCDVARRead
HR32167doc 32168-32169Total apparent power demandAvailable on: NSX E, NT/NW/NS P/H, MTZ.FLOAT32ABCDVARead
HR32169doc 32170-32171Peak current demand phase 1Available on: MTZ.FLOAT32ABCDARead
HR32171doc 32172-32173Peak current demand phase 2Available on: MTZ.FLOAT32ABCDARead
HR32173doc 32174-32175Peak current demand phase 3Available on: MTZ.FLOAT32ABCDARead
HR32175doc 32176-32177Peak current demand neutralAvailable on: MTZ.FLOAT32ABCDARead
HR32177doc 32178-32179Peak active power demandAvailable on: MTZ.FLOAT32ABCDWRead
HR32179doc 32180-32181Peak reactive power demandAvailable on: MTZ.FLOAT32ABCDVARRead
HR32181doc 32182-32183Peak apparent power demandAvailable on: MTZ.FLOAT32ABCDVARead
HR32183doc 32184-32185Maximum ground-fault currentAvailable on: MTZ.FLOAT32ABCDARead
HR32193doc 32194-32195Maximum voltage V12Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32195doc 32196-32197Maximum voltage V23Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32197doc 32198-32199Maximum voltage V31Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32199doc 32200-32201Maximum voltage V1NAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32201doc 32202-32203Maximum voltage V2NAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32203doc 32204-32205Maximum voltage V3NAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDVRead
HR32205doc 32206-32207Power factor phase 1Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDRead
HR32207doc 32208-32209Power factor phase 2Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDRead
HR32209doc 32210-32211Power factor phase 3Available on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDRead
HR32211doc 32212-32213Total power factorAvailable on: NSX E, NT/NW/NS E/P/H, MTZ.FLOAT32ABCDRead
HR32213doc 32214-32215Fundamental power factor phase 1 (cos phi)Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32215doc 32216-32217Fundamental power factor phase 2 (cos phi)Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32217doc 32218-32219Fundamental power factor phase 3 (cos phi)Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32219doc 32220-32221Total fundamental power factorAvailable on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32221doc 32222-32223THD voltage V12Ratio to the fundamental, 0-2. Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32223doc 32224-32225THD voltage V23Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32225doc 32226-32227THD voltage V31Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32227doc 32228-32229THD voltage V1NAvailable on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32229doc 32230-32231THD voltage V2NAvailable on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32231doc 32232-32233THD voltage V3NAvailable on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32233doc 32234-32235THD current phase 1Ratio to the fundamental, 0-2. Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32235doc 32236-32237THD current phase 2Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32237doc 32238-32239THD current phase 3Available on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32239doc 32240-32241Average THD of 3 phase currentsAvailable on: NSX E, NT/NW/NS H, MTZ.FLOAT32ABCDRead
HR32241doc 32242-32243Maximum total power factorAvailable on: MTZ.FLOAT32ABCDRead
HR32340doc 32341Inhibit close order statusBITMAP16Readbit 0 = Close inhibited by IO module; bit 1 = Close inhibited by communication

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)

What Modbus registers does the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) have?

This map lists 98 registers: 98 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide lists a hex address and a decimal register for every row, with register = address + 1 (register 32028 = 0x7D1B). Its readout example requests 0x7D1B for register 32028.

What byte order does the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)?

Start with HR 32000 Circuit breaker status (Open/closed/tripped status); HR 32006 Tripping cause, standard protections (Trip cause); HR 32027 RMS current phase 1 (Phase 1 current); HR 32055 Voltage V12 (Voltage V12); HR 32077 Total active power (Total active power); HR 32095 Total active energy (Total active energy); HR 32211 Total power factor (Total power factor).

How do I enable Modbus control of the Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)?

Fit an IFM (RS-485 Modbus) or IFE (Ethernet) interface and connect it to the trip unit over the ULP cord. No enable step is needed to read the dataset; remote control needs the locking pad open and the command interface.

Where is the official Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface) Modbus documentation?

The source is ComPact NSX - Modbus Communication User Guide (DOCA0091EN-09), revision 2022-07, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0091EN.

More Schneider Electric Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: ComPact NSX - Modbus Communication User Guide · DOCA0091EN-09 · rev. 2022-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.