Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) Modbus register map

Updated 17 November 2026

Short answer

Schneider Electric's Easy Altivar 610 pump and fan drive with Modbus RTU on its built-in serial port. Each parameter has a fixed decimal logical address sent as the holding-register address. This map covers the CiA402 command and status words, frequency and speed references, the main monitors, energy counters, fault and warning codes, I/O states and the Modbus and channel settings needed for network control.

This page lists 70 Modbus registers for the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
Easy Altivar ATV610 (embedded Modbus serial)
Equipment type
Variable frequency drive
Registers
70 (38 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D
Source document
ATV610 - Communication Parameters (Excel) · EAV64394 V1.6
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)

Integration in brief

Set Add (6001) to 1-247 and restart the drive, set FR1 to Modbus (164) with CHCF = SIM, then write CMD (8501) = 0006h followed by 000Fh with a non-zero LFR (8502, 0.1 Hz) or LFRD (8602, rpm). Poll ETA (3201), RFR (3202), HMIS (3240) and LFT (7121).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8501CMD - Command registerBITMAP16CMD: CiA402 run/stop/resetRead/write
HR 8502LFR - Reference frequencyINT16LFR: frequency reference, 0.1 HzRead/write
HR 3201ETA - Status RegisterBITMAP16ETA: CiA402 status wordRead
HR 3202RFR - Motor frequencyINT16RFR: output frequency, 0.1 HzRead
HR 3204LCR - Motor currentUINT16LCR: motor current (raw)Read
HR 3240HMIS - Device stateUINT16HMIS: drive state codeRead
HR 7121LFT - Last error occurredUINT16LFT: last fault codeRead
HR 3209THD - Drive thermal stateUINT16THD: drive thermal stateRead

Enable Modbus control & writes

Set [Modbus Address] Add (logical 6001) to 1-247; the factory value 0 (OFF) means the drive does not answer. Speed and format default to 19200 baud, 8-E-1 (tbr 6003, tFO 6004). A new Modbus address takes effect only after the drive is restarted. For combined CiA402 control use [Control Mode] CHCF = [Not separ.] SIM and set [Ref Freq 1 Config] FR1 = Modbus (164); for separate mode use CHCF = SEP with Cd1 = Modbus.

Communication loss & watchdog

[ModbusTimeout] ttO (6005), 0.1-30 s, factory 10 s. If no valid Modbus frame arrives within ttO on a monitored channel, the drive raises [Modbus Com Interruption] SLF1 and reacts per SLL (7010): factory freewheel stop, or ignore, configured stop, fallback speed LFF (7080), speed maintained, ramp stop, fast stop or DC injection.

Byte order & addressing

Network setup

Watch out for

Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

70 of 70 shown
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3102SFR - Switching frequencyRange 1.0 kHz to 16.0 kHz.UINT16× 0.1kHzRead/write
HR3103TFR - Max frequencyRange 10.0 Hz to 500.0 Hz. Write only when stopped.UINT16× 0.1HzRead/write
HR3104HSP - High speedRange 0.0 Hz to 500.0 Hz.UINT16× 0.1HzRead/write
HR3105LSP - Low speedRange 0.0 Hz to 500.0 Hz.UINT16× 0.1HzRead/write
HR3201ETA - Status RegisterCiA402 status word.BITMAP16Readbit 0 = Ready to switch on; bit 1 = Switched on; bit 2 = Operation enabled (running); bit 3 = Fault; bit 4 = Voltage enabled (power stage supplied); bit 5 = Quick stop (0 = quick stop active); bit 6 = Switch on disabled; bit 7 = Warning active; bit 9 = Remote: command or reference via network; bit 10 = Target reference reached; bit 11 = Reference outside LSP/HSP limits; bit 14 = Stop via STOP key; bit 15 = Reverse rotation at output
HR3202RFR - Motor frequencySigned; 0.1 Hz while CMI bit 9 = 0.INT16× 0.1HzRead
HR3203FRH - Reference frequency before rampRange -500.0 Hz to 500.0 Hz.INT16× 0.1HzRead
HR3204LCR - Motor currentRaw; resolution depends on drive rating (see notes).UINT16Read
HR3205OTR - Motor torqueRange -3276.7 % to 3276.7 %.INT16× 0.1%Read
HR3206ETI - Internal State registerBITMAP16Readbit 0 = Access to the EEPROM non-volatile memory in progress
HR3207ULN - Mains voltageRange 0.0 V to 6553.5 V.UINT16× 0.1VRead
HR3208UOP - Motor voltageRange 0 V to 65535 V.UINT16VRead
HR3209THD - Drive thermal stateRange 0 % to 200 %.UINT16%Read
HR3211OPR - Motor powerRange -32767 % to 32767 %.INT16%Read
HR3240HMIS - Device stateUINT16Read0 = Drive automatic tuning (TUN); 1 = DC injection (DCB); 2 = Ready (RDY); 3 = Freewheel stop (NST); 4 = Running (RUN); 5 = Accelerating (ACC); 6 = Decelerating (DEC); 7 = In current limitation (CLI); 8 = Fast stop (FST); 11 = No mains voltage (NLP); 13 = Control stopping (CTL); 14 = Dec ramp adaptation (OBR); 15 = Output cut (SOC); 17 = Undervoltage warning (USA); 18 = TC mode active (TC); 19 = In autotest (ST); 20 = Autotest error (FA); 21 = Autotest OK (OK); 22 = EEprom test (EP); 23 = Operating state "Fault" (FLT); 25 = DCP Flashing mode (DCP); 30 = STO active (STO); 35 = Energy Saving (IDLE); 36 = Firmware Update (FWUP); 37 = AFE Mains undervoltage (URA)
HR3243VBUS - DC bus voltageRange 0.0 V to 6553.5 V.UINT16× 0.1VRead
HR3263FSPD - Fan speedRange 0 rpm to 65535 rpm.UINT16rpmRead
HR3297EPR - Active electrical output powerRange -300 % to 300 %.INT16%Read
HR5202IL1R - Logic inputs statesBITMAP16Readbit 0 = LI1 input state; bit 1 = LI2 input state; bit 2 = LI3 input state; bit 3 = LI4 input state; bit 4 = LI5 input state; bit 5 = LI6 input state; bit 6 = LI7 input state; bit 7 = LI8 input state; bit 10 = LI11 input state; bit 11 = LI12 input state; bit 12 = LI13 input state; bit 13 = LI14 input state; bit 14 = LI15 input state; bit 15 = LI16 input state
HR5212OL1R - Logic outputs statesBITMAP16Read/writebit 0 = R1 relay state; bit 1 = R2 relay state; bit 2 = R3 relay state; bit 3 = R4 relay state; bit 4 = R5 relay state; bit 5 = R6 relay state; bit 8 = DO1 output state; bit 9 = DO2 output state; bit 12 = DO11 output state; bit 13 = DO12 output state
HR6001ADD - Device modbus addressRange 0 to 247. Factory 0. Write only when stopped.UINT16Read/write
HR6003TBR - Modbus baud rateFactory [19200 bps]. Write only when stopped.UINT16Read/write4 = Automatic (AUTO); 8 = 300 bps (300); 12 = 600 bps (600); 16 = 1.2 Kbps (1200); 20 = 2.4 Kbps (2400); 24 = 4800 bps (4800); 28 = 9600 bps (9600); 30 = 10 Kbps (10000); 32 = 19200 bps (19200); 34 = 20 Kbps (20000); 35 = 28.8 Kbps (28800); 36 = 38.4 Kbps (38400); 37 = 45.45 Kbps (45450); 38 = 50 Kbps (50000); 40 = 57.6 Kbps (57600); 41 = 76.8 Kbps (76800); 42 = 93.75 Kbps (93750); 44 = 100 Kbps (100K); 48 = 115.2 Kbps (115K2); 52 = 125 Kbps (125K); 53 = 156 Kbps (156K); 54 = 187.5 Kbps (187K5); 56 = 230.4 Kbps (230K4); 60 = 250 Kbps (250K); 64 = 460.8 Kbps (460K8); 68 = 500 Kbps (500K); 69 = 625 Kbps (625K); 70 = 800 Kbps (800K); 72 = 921.6 Kbps (921K6); 76 = 1 Mbps (1M); 80 = 1.5 Mbps (1M5); 81 = 2.5 Mbps (2M5); 82 = 3 Mbps (3M); 83 = 6 Mbps (6M); 84 = 10 Mbps (10M); 86 = 5 Mbps (5M); 88 = 12 Mbps (12M); 92 = 100 Mbps (100M)
HR6004TFO - Modbus formatFactory [8 bits even parity 1 stop bit]. Write only when stopped.UINT16Read/write2 = 8bit odd parity 1stop bit (8O1); 3 = 8 bits even parity 1 stop bit (8E1); 4 = 8bit no parity 1stop bit (8N1); 5 = 8bit no parity 2stop bits (8N2)
HR6005TTO - Modbus timeoutRange 0.1 s to 30.0 s. Factory 10.0 s. Write only when stopped.UINT16× 0.1sRead/write
HR6010M1EC - Mdb NET CRC errorsRange 0 to 65535.UINT16Read
HR6011M1CT - Mdb frame numberRange 0 to 65535.UINT16Read
HR7010SLL - Response to Modbus interruptionFactory [Freewheel stop]. Write only when stopped.UINT16Read/write0 = Ignore (NO); 1 = Freewheel stop (YES); 2 = Per STT (STT); 4 = Fallback speed (LFF); 5 = Speed maintained (RLS); 6 = Ramp stop (RMP); 7 = Fast stop (FST); 8 = DC injection (DCI)
HR7080LFF - Fall back speedRange 0.0 Hz to 500.0 Hz. Factory 0.0 Hz. Write only when stopped.UINT16× 0.1HzRead/write
HR7121LFT - Last error occurredUINT16Read0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 13 = AI2 4-20mA loss (LFF2); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 42 = PC communication interruption (SLF2); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = IGBT overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 60 = Internal error 12 (Internal current supply) (INFC); 64 = input contactor (LCF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 110 = AI2 thermal level error (TH2F); 111 = Thermal sensor error on AI2 (T2CF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 114 = Pump cycle start error (PCPF); 115 = Outlet pressure low (OPLF); 116 = High flow error (HFPF); 117 = Inlet pressure detected error (IPPF); 119 = Pump low flow detected error (PLFF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 124 = Anti Jam detected error (JAMF); 125 = Outlet pressure high (OPHF); 126 = Dry run detected error (DRYF); 127 = PID feedback detected error (PFMF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 130 = Lead pump not available (MPLF); 131 = Low level error (LCLF); 132 = High level error (LCHF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 173 = Cabinet overheat error (CHF); 174 = AFE Mains undervoltage (URF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 220 = Advanced function locked error (AFLF)
HR7200DP0 - Fault code on last faultUINT16Read0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 13 = AI2 4-20mA loss (LFF2); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 42 = PC communication interruption (SLF2); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = IGBT overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 60 = Internal error 12 (Internal current supply) (INFC); 64 = input contactor (LCF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 110 = AI2 thermal level error (TH2F); 111 = Thermal sensor error on AI2 (T2CF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 114 = Pump cycle start error (PCPF); 115 = Outlet pressure low (OPLF); 116 = High flow error (HFPF); 117 = Inlet pressure detected error (IPPF); 119 = Pump low flow detected error (PLFF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 124 = Anti Jam detected error (JAMF); 125 = Outlet pressure high (OPHF); 126 = Dry run detected error (DRYF); 127 = PID feedback detected error (PFMF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 130 = Lead pump not available (MPLF); 131 = Low level error (LCLF); 132 = High level error (LCHF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 173 = Cabinet overheat error (CHF); 174 = AFE Mains undervoltage (URF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 220 = Advanced function locked error (AFLF)
HR7201DP1 - Fault code on fault n-1UINT16Read0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 13 = AI2 4-20mA loss (LFF2); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 42 = PC communication interruption (SLF2); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = IGBT overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 60 = Internal error 12 (Internal current supply) (INFC); 64 = input contactor (LCF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 110 = AI2 thermal level error (TH2F); 111 = Thermal sensor error on AI2 (T2CF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 114 = Pump cycle start error (PCPF); 115 = Outlet pressure low (OPLF); 116 = High flow error (HFPF); 117 = Inlet pressure detected error (IPPF); 119 = Pump low flow detected error (PLFF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 124 = Anti Jam detected error (JAMF); 125 = Outlet pressure high (OPHF); 126 = Dry run detected error (DRYF); 127 = PID feedback detected error (PFMF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 130 = Lead pump not available (MPLF); 131 = Low level error (LCLF); 132 = High level error (LCHF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 173 = Cabinet overheat error (CHF); 174 = AFE Mains undervoltage (URF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 220 = Advanced function locked error (AFLF)
HR7202DP2 - Fault code on fault n-2UINT16Read0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 13 = AI2 4-20mA loss (LFF2); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 42 = PC communication interruption (SLF2); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = IGBT overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 60 = Internal error 12 (Internal current supply) (INFC); 64 = input contactor (LCF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 110 = AI2 thermal level error (TH2F); 111 = Thermal sensor error on AI2 (T2CF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 114 = Pump cycle start error (PCPF); 115 = Outlet pressure low (OPLF); 116 = High flow error (HFPF); 117 = Inlet pressure detected error (IPPF); 119 = Pump low flow detected error (PLFF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 124 = Anti Jam detected error (JAMF); 125 = Outlet pressure high (OPHF); 126 = Dry run detected error (DRYF); 127 = PID feedback detected error (PFMF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 130 = Lead pump not available (MPLF); 131 = Low level error (LCLF); 132 = High level error (LCHF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 173 = Cabinet overheat error (CHF); 174 = AFE Mains undervoltage (URF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 220 = Advanced function locked error (AFLF)
HR7203DP3 - Fault code on fault n-3UINT16Read0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 13 = AI2 4-20mA loss (LFF2); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 42 = PC communication interruption (SLF2); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = IGBT overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 60 = Internal error 12 (Internal current supply) (INFC); 64 = input contactor (LCF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 110 = AI2 thermal level error (TH2F); 111 = Thermal sensor error on AI2 (T2CF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 114 = Pump cycle start error (PCPF); 115 = Outlet pressure low (OPLF); 116 = High flow error (HFPF); 117 = Inlet pressure detected error (IPPF); 119 = Pump low flow detected error (PLFF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 124 = Anti Jam detected error (JAMF); 125 = Outlet pressure high (OPHF); 126 = Dry run detected error (DRYF); 127 = PID feedback detected error (PFMF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 130 = Lead pump not available (MPLF); 131 = Low level error (LCLF); 132 = High level error (LCHF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 173 = Cabinet overheat error (CHF); 174 = AFE Mains undervoltage (URF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 220 = Advanced function locked error (AFLF)
HR7393FNB - Fault counterRange 0 to 65535.UINT16Read
HR8401CHCF - Control mode configurationWrite only when stopped.UINT16Read/write1 = Combined channel mode (SIM); 2 = Separated channel mode (SEP); 3 = I/O mode (IO)
HR8413FR1 - Configuration reference frequency 1Write only when stopped.UINT16Read/write0 = Not configured (NO); 1 = AI1 Analog input (AI1); 2 = AI2 Analog input (AI2); 3 = AI3 Analog input (AI3); 4 = AI4 Analog input (AI4); 5 = AI5 Analog input (AI5); 129 = Motor current (OCR); 130 = Motor frequency (OFR); 131 = Ramp output (ORP); 132 = Motor torque (TRQ); 133 = Signed torque (STQ); 134 = Signed ramp (ORS); 135 = PID reference (OPS); 136 = PID feedback (OPF); 137 = PID error (OPE); 138 = PID output (OPI); 139 = Motor power (OPR); 140 = Motor thermal state (THR); 141 = Drive thermal state (THD); 160 = Reference frequency via DI (UPDT); 163 = Local HMI (LCC); 164 = Reference frequency via Modbus (MDB); 167 = Reference frequency via CANopen (CAN); 169 = Reference frequency via Com module (NET); 171 = Embedded Ethernet (ETH); 173 = Signed output frequency (OFS); 180 = Motor voltage (UOP); 183 = AI Virtual 1 (AIV1); 186 = DI5 pulseInput assignment (PI5); 187 = DI6 pulseInput assignment (PI6); 340 = Estimated pump flow (SLPF); 341 = Inlet pressure value (PS1V); 342 = Outlet pressure value (PS2V); 343 = Installation flow value (FS1V)
HR8423CD1 - Command channel 1 assignFactory [Terminal block]. Write only when stopped.UINT16Read/write1 = Terminal block (TER); 3 = Local HMI (LCC); 10 = Modbus communication (MDB); 20 = CANopen communication (CAN); 30 = Ext. communication module (NET); 40 = Ethernet (ETH)
HR8441CRC - Channel for reference frequencyBITMAP16Readbit 0 = Terminals; bit 1 = Local keypad; bit 2 = Remote keypad; bit 3 = Modbus; bit 6 = CANopen; bit 7 = Terminal up-Down speed; bit 8 = Remote keypad up-down speed; bit 9 = COM option board; bit 11 = Embedded Ethernet; bit 14 = Indus; bit 15 = PowerSuite
HR8442CCC - Active command channelBITMAP16Readbit 0 = Terminals; bit 1 = Local keypad; bit 2 = Remote keypad; bit 3 = Modbus; bit 6 = CANopen; bit 7 = Terminal up-Down speed; bit 8 = Remote keypad up-down speed; bit 9 = COM option board; bit 11 = Embedded Ethernet; bit 14 = Indus; bit 15 = PowerSuite
HR8501CMD - Command registerCiA402 control word (I/O-profile bits when CHCF = IO).BITMAP16Read/writebit 0 = CiA402: Switch on; bit 1 = CiA402: Enable voltage; bit 2 = CiA402: Quick stop (0 = quick stop active); bit 3 = CiA402: Enable operation (run); bit 7 = CiA402: Fault reset on 0->1 edge; bit 8 = CiA402: Halt (stop per Stt, stays in Operation enabled); bit 11 = CiA402: assignable, default reverse direction (rrS = C111); bit 12 = Assignable (C112); bit 13 = Assignable (C113); bit 14 = Assignable (C114); bit 15 = Assignable (C115)
HR8502LFR - Reference frequencySigned; 0.1 Hz while CMI bit 9 = 0.INT16× 0.1HzRead/write
HR8503PISP - PIDSet pointRange 0 to 1000.UINT16Read/write
HR8504CMI - Extended control wordSave to EEPROM, factory reset, LFR unit select.BITMAP16Read/writebit 0 = Restore factory settings (drive stopped); bit 1 = Save configuration to EEPROM (drive stopped); bit 9 = LFR/RFR unit: 0 = 0.1 Hz, 1 = signed value where 32767 = tFr; bit 15 = 1 = parameter consistency check off (drive locked in stop)
HR8602LFRD - Speed setpointSigned speed reference in rpm.INT16rpmRead/write
HR8604RFRD - Output velocityRange -32767 rpm to 32767 rpm.INT16rpmRead
HR8605FRHD - Speed reference before rampRange -32767 rpm to 32767 rpm.INT16rpmRead
HR9001ACC - Acceleration ramp timeRaw; resolution set by INR (factory 0.1 s).UINT16Read/write
HR9002DEC - Deceleration ramp timeRaw; resolution set by INR (factory 0.1 s).UINT16Read/write
HR9020INR - Ramp incrementFactory [Tenths of seconds].UINT16Read/write0 = hundredths of seconds (001); 1 = Tenths of seconds (01); 2 = seconds (1)
HR9601UNS - Nominal motor voltageRange 100 V to 690 V. Write only when stopped.UINT16VRead/write
HR9602FRS - Nominal motor frequencyRange 40.0 Hz to 500.0 Hz. Write only when stopped.UINT16× 0.1HzRead/write
HR9604NSP - Nominal motor speedRange 0 rpm to 65535 rpm. Write only when stopped.UINT16rpmRead/write
HR9630THR - Motor thermal stateRange 0 % to 200 %.UINT16%Read
HR10606OC0 - Electrical energy consumed by the motor (Wh)Range 0 Wh to 999 Wh. Write only when stopped.UINT16WhRead/write
HR10607OC1 - Electrical energy consumed by the motor (KWh)Range 0 kWh to 999 kWh. Write only when stopped.UINT16kWhRead/write
HR10608OC2 - Electrical energy consumed by the motor (MWh)Range 0 MWh to 999 MWh. Write only when stopped.UINT16MWhRead/write
HR10609OC3 - Electrical energy consumed by the motor (GWh)Range 0 GWh to 999 GWh. Write only when stopped.UINT16GWhRead/write
HR10610OC4 - Electrical energy consumed by the motor (TWh)Range 0 TWh to 999 TWh. Write only when stopped.UINT16TWhRead/write
HR10626IC0 - Input Energy (Wh)Range 0 Wh to 999 Wh. Write only when stopped.UINT16WhRead/write
HR10627IC1 - Input Energy (kWh)Range 0 kWh to 999 kWh. Write only when stopped.UINT16kWhRead/write
HR10628IC2 - Input Energy (MWh)Range 0 MWh to 999 MWh. Write only when stopped.UINT16MWhRead/write
HR10629IC3 - Input Energy (GWh)Range 0 GWh to 999 GWh. Write only when stopped.UINT16GWhRead/write
HR10630IC4 - Input Energy (TWh)Range 0 TWh to 999 TWh. Write only when stopped.UINT16TWhRead/write
HR11201STT - Type of stopFactory [On ramp]. Write only when stopped.UINT16Read/write0 = On ramp (RMP); 1 = Fast stop (FST); 2 = Freewheel stop (NST); 3 = DC injection (DCI)
HR11983RPO - PID outputRange -3276.7 Hz to 3276.7 Hz.INT16× 0.1HzRead
HR12701NMA1 - Scan input 1 addressRange 0 to 65535. Factory 3201. Write only when stopped.UINT16Read/write
HR12721NCA1 - Scan output 1 addressRange 0 to 65535. Factory 8501. Write only when stopped.UINT16Read/write
HR12741NM1 - Com scan input 1 valueRange 0 to 65535.UINT16Read
HR12761NC1 - Com scan output 1 valueRange 0 to 65535.UINT16Read
HR12890LALR - Last warningUINT16Read0 = No warning stored (NOA); 1 = Fallback frequency reaction (FRF); 2 = Speed maintained (RLS); 3 = Type of stop (STT); 4 = Reference frequency warning (SRA); 5 = Life cycle warning 1 (LCA1); 6 = Life cycle warning 2 (LCA2); 7 = Dry run warning (DRYA); 8 = Low flow warning (LFA); 9 = High flow warning (HFPA); 10 = Inlet pressure warning (IPPA); 11 = Outlet pressure low warning (OPLA); 12 = Outlet pressure high warning (OPHA); 13 = Pump cycle warning (PCPA); 14 = Anti-Jam warning (JAMA); 15 = Pump low flow (PLFA); 16 = Low pressure warning (LPA); 17 = Flow limit activated (FSA); 18 = PID error warning (PEE); 19 = PID feedback warning (PFA); 20 = PID high feedback warning (PFAH); 21 = PID low feedback warning (PFAL); 22 = Regulation warning (PISH); 26 = AI2 thermal sensor warning (TP2A); 27 = AI3 thermal sensor warning (TP3A); 28 = AI4 thermal sensor warning (TP4A); 29 = AI5 thermal sensor warning (TP5A); 30 = AI1 4-20 loss warning (AP1); 31 = AI2 4-20 loss warning (AP2); 32 = AI3 4-20 loss warning (AP3); 33 = AI4 4-20 loss warning (AP4); 34 = AI5 4-20 loss warning (AP5); 35 = Device thermal state warning (THA); 36 = IGBT thermal warning (TJA); 37 = Fan counter warning (FCTA); 38 = Fan feedback warning (FFDA); 40 = External error warning (EFA); 41 = Undervoltage warning (USA); 42 = Preventive undervoltage active (UPA); 44 = Motor frequency high threshold reached (FTA); 45 = Motor frequency low threshold reached (FTAL); 47 = Motor frequency low threshold 2 reached (F2AL); 48 = High speed reached (FLA); 49 = Reference frequency high threshold reached (RTAH); 50 = Reference frequency low threshold reached (RTAL); 51 = 2nd frequency threshold reached (F2A); 52 = Current threshold reached (CTA); 53 = Low current threshold reached (CTAL); 54 = High torque warning (TTHA); 55 = Low torque warning (TTLA); 56 = Process underload warning (ULA); 57 = Process overload warning (OLA); 60 = Device thermal threshold reached (TAD); 61 = Motor thermal threshold reached (TSA); 65 = Power high threshold reached (PTHA); 66 = Power low threshold reached (PTHL); 67 = Customer warning 1 (CAS1); 68 = Customer warning 2 (CAS2); 69 = Customer warning 3 (CAS3); 70 = Customer warning 4 (CAS4); 71 = Customer warning 5 (CAS5); 72 = AFE Mains undervoltage (URA); 73 = Power Consumption warning (POWD); 74 = Output pressure high switch warning (OPSA); 78 = Multi-Pump available capacity warning (MPCA); 79 = Lead pump not available (MPLA); 80 = High level warning (LCHA); 81 = Low level warning (LCLA); 82 = Level switch warning (LCWA); 110 = Fieldbus communication loss fallback channel is active (AFFL); 134 = Temperature sensor AI2 warning (TS2A); 135 = Temperature sensor AI3 warning (TS3A); 136 = Temperature sensor AI4 warning (TS4A); 137 = Temperature sensor AI5 warning (TS5A); 138 = DC bus ripple warning (DCRW); 146 = Modbus communication interruption warning (SLF1)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)

What Modbus registers does the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) have?

This map lists 70 registers: 70 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The parameter file gives each logical address in hex and decimal (16#0C81 = 3201); the decimal value goes into the request unchanged. The Modbus serial manual's example reads W3102-W3105 by sending start address 0C1E hex (= 3102) and writes W9001 at 2329 hex, so there is no 40001 offset and no minus 1.

What are the minimum Modbus registers to integrate the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)?

Start with HR 8501 CMD - Command register (CMD: CiA402 run/stop/reset); HR 8502 LFR - Reference frequency (LFR: frequency reference, 0.1 Hz); HR 3201 ETA - Status Register (ETA: CiA402 status word); HR 3202 RFR - Motor frequency (RFR: output frequency, 0.1 Hz); HR 3204 LCR - Motor current (LCR: motor current (raw)); HR 3240 HMIS - Device state (HMIS: drive state code); HR 7121 LFT - Last error occurred (LFT: last fault code); HR 3209 THD - Drive thermal state (THD: drive thermal state).

How do I enable Modbus control of the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)?

Set [Modbus Address] Add (logical 6001) to 1-247; the factory value 0 (OFF) means the drive does not answer. Speed and format default to 19200 baud, 8-E-1 (tbr 6003, tFO 6004). A new Modbus address takes effect only after the drive is restarted. For combined CiA402 control use [Control Mode] CHCF = [Not separ.] SIM and set [Ref Freq 1 Config] FR1 = Modbus (164); for separate mode use CHCF = SEP with Cd1 = Modbus.

What happens when the Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) loses Modbus communication?

[ModbusTimeout] ttO (6005), 0.1-30 s, factory 10 s. If no valid Modbus frame arrives within ttO on a monitored channel, the drive raises [Modbus Com Interruption] SLF1 and reacts per SLL (7010): factory freewheel stop, or ignore, configured stop, fallback speed LFF (7080), speed maintained, ramp stop, fast stop or DC injection.

Where is the official Schneider Electric Easy Altivar ATV610 (embedded Modbus serial) Modbus documentation?

The source is ATV610 - Communication Parameters (Excel) (EAV64394 V1.6), published free by Schneider Electric at https://download.schneider-electric.com/files?p_Doc_Ref=EAV64394.

More Schneider Electric Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: ATV610 - Communication Parameters (Excel) · EAV64394 V1.6. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.