Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus register map
Updated 19 November 2026
The VF-nC3 is a small Toshiba inverter whose RS-485 port speaks either Toshiba's own protocol or a subset of Modbus RTU. Every value has a hex communication number that is used directly as the Modbus register address. This map covers the comms command words (FA..), the monitor block (FC../FD../FE..) and the communication setup parameters.
This page lists 52 Modbus registers for the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.
- Manufacturer
- Toshiba
- Model
- TOSVERT VF-nC3 compact inverter (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 52 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 0
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3
Integration notes: Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Set f829 = 1 (Modbus RTU) and f802 to a non-zero address, then power-cycle. Write FA00 = C400H (command and frequency priority + run forward) and the speed in FA01 (0.01 Hz), and poll FD00/FD01/FC90 for speed, status and trip.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 64000 | Command 1 | BITMAP16 | Run/stop and comms priority bits | Read/write |
| HR 64001 | Frequency command | UINT16 | Speed reference, 0.01 Hz | Read/write |
| HR 64768 | Output frequency | UINT16 | Output frequency | Read |
| HR 64769 | Inverter status 1 | BITMAP16 | Running / tripped / alarm status | Read |
| HR 64771 | Output current | UINT16 | Output current, % of rating | Read |
| HR 64656 | Trip code | UINT16 | Present trip code | Read |
| HR 64657 | Alarm information 1 | BITMAP16 | Pre-alarm bits | Read |
Enable Modbus control & writes
Set f829 (communication protocol) to 1 = MODBUS-RTU; the factory setting is 0 (Toshiba protocol). Baud f800, parity f801 and the protocol take effect only after a reset or power cycle. Comms run/frequency control is taken by setting FA00 bits 15 and 14, independent of cmod/fmod.
Communication loss & watchdog
f803 sets a communication time-out (0.0 = off, 0.1-100.0 s); f804 picks alarm only, trip with coast stop or trip with slowdown stop (trip shows err5); f808 sets when it is checked (always, during comms mode, or comms mode and running).
Byte order & addressing
- The inverter number factory value is 0, which Modbus treats as broadcast with no reply; set 1-247 first.
- FA00 bit 13 (fault reset) gets no reply from the drive.
- Missing communication numbers inside a multi-word read come back as 8000H.
- An input terminal set to function 48/49 (forced local) overrides comms commands and frequency.
- Function 03 reads at most 8 consecutive words in one request (direct block read); a plain read is one word.
Network setup
- f800 baud: 3 = 9600, 4 = 19200 (default), 5 = 38400.
- f801 parity: 0 none, 1 even (default), 2 odd.
- f802 address 1-247.
- f805 adds reply delay for slow RS-485 converters (CPU1 v108 and later).
- Power-cycle after changing f800, f801 or f829.
Watch out for
- Do not write EEPROM-backed parameters cyclically; the manual rates the EEPROM at about 10,000 writes.
- Comms do not answer for about one second after power-up.
- f700 = 2 blocks parameter writes over RS-485 (error code 04).
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2048doc 0800H | Baud rate (f800) | Applies after reset. | UINT16 | Read/write | 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps | |||
| HR | 2049doc 0801H | Parity (f801) | Applies after reset. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 2050doc 0802H | Inverter number (f802) | Modbus slave address 0-247; 0 is broadcast. | UINT16 | Read/write | ||||
| HR | 2051doc 0803H | Comm time-out time (f803) | 0.0 = disabled, 0.1-100.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 2052doc 0804H | Comm time-out action (f804) | UINT16 | Read/write | 0 = Alarm only; 1 = Trip, coast stop; 2 = Trip, slowdown stop | ||||
| HR | 2053doc 0805H | Send waiting time (f805) | 0.00 = normal, up to 2.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 2056doc 0808H | Comm time-out detection (f808) | UINT16 | Read/write | 0 = Always; 1 = During communication; 2 = During communication and running | ||||
| HR | 2089doc 0829H | Communication protocol (f829) | Applies after reset. | UINT16 | Read/write | 0 = TOSHIBA protocol; 1 = MODBUS-RTU | |||
| HR | 64000doc FA00H | Command 1 | Run/stop, direction, presets, reset; bits 14/15 hand control to comms. | BITMAP16 | Read/write | bit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = Motor 2 (THR2) select; bit 5 = PID control off; bit 6 = Accel/decel pattern 2 (AD2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Reverse (0 = forward); bit 10 = Run (0 = stop); bit 11 = Coast stop; bit 12 = Emergency stop (always enabled); bit 13 = Fault reset (no reply sent); bit 14 = Frequency priority: take frequency from comms; bit 15 = Command priority: take run commands from comms | |||
| HR | 64001doc FA01H | Frequency command | Comms frequency reference; needs FA00 bit 14 or fmod = 3. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 64003doc FA03H | Panel operation frequency | Between LL and UL; stored in EEPROM. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 64032doc FA20H | Command 2 | Needs FA00 bit 15 set; write 0 to reserved bits. | BITMAP16 | Read/write | bit 7 = Maximum deceleration forced stop; bit 12 = OC stall level 2 (F185) instead of 1 (F601) | |||
| HR | 64080doc FA50H | Terminal output data | Drives the OUT terminal when f130-f132 = 92/93. | BITMAP16 | Read/write | bit 0 = Specified data output 1 | |||
| HR | 64081doc FA51H | FM analog output data | Used when fmsl = 18; 8-bit resolution. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 64135doc FA87H | Reset information | Write 1; the drive clears it to 0 after it resets. | UINT16 | Read/write | ||||
| HR | 64263doc FB07H | Inverter series type | Reads 208 on a VF-nC3. | UINT16 | Read | ||||
| HR | 64656doc FC90H | Trip code | Present trip. | UINT16 | Read | 0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error | |||
| HR | 64657doc FC91H | Alarm information 1 | BITMAP16 | Read | bit 0 = Over-current alarm; bit 1 = Inverter overload alarm; bit 2 = Motor overload alarm; bit 3 = Overheat alarm; bit 4 = Overvoltage alarm; bit 5 = Main circuit undervoltage alarm; bit 6 = Main device overheat alarm; bit 7 = Low current alarm; bit 10 = Cumulative operation time alarm; bit 13 = Main circuit undervoltage (MOFF); bit 14 = Forced decel/stop on momentary power failure; bit 15 = Auto stop on prolonged lower-limit running | ||||
| HR | 64658doc FC92H | Alarm information 2 | BITMAP16 | Read | bit 2 = Life time alarm; bit 3 = Over-torque alarm; bit 4 = Overload stall alarm; bit 7 = Output frequency upper limit alarm | ||||
| HR | 64768doc FD00H | Output frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64769doc FD01H | Inverter status 1 | BITMAP16 | Read | bit 0 = FL fault output active; bit 1 = Tripped (incl. retry / trip hold); bit 2 = Alarm issued; bit 3 = Main circuit undervoltage; bit 4 = Motor 2 (THR2) selected; bit 5 = PID control prohibited; bit 6 = Accel/decel pattern 2 (AD2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Reverse (0 = forward); bit 10 = Run (0 = stop); bit 11 = Coast stop: ST off; bit 12 = Emergency stop state; bit 13 = Standby with ST on; bit 14 = Standby | ||||
| HR | 64770doc FD02H | Frequency command value | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64771doc FD03H | Output current | Percent of drive rated current. | UINT16 | × 0.01 | % | Read | ||
| HR | 64772doc FD04H | Input voltage (DC detection) | Percent value. | UINT16 | × 0.01 | % | Read | ||
| HR | 64773doc FD05H | Output voltage | Percent value. | UINT16 | × 0.01 | % | Read | ||
| HR | 64774doc FD06H | Input terminal information | BITMAP16 | Read | bit 0 = F; bit 1 = R; bit 2 = S1; bit 3 = S2; bit 4 = VI (logic input mode) | ||||
| HR | 64775doc FD07H | Output terminal information | BITMAP16 | Read | bit 0 = OUT; bit 2 = FL | ||||
| HR | 64789doc FD15H | Compensated frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64790doc FD16H | Estimated speed | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64802doc FD22H | PID feedback value | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64803doc FD23H | Motor overload factor (OL2) | UINT16 | × 0.01 | % | Read | |||
| HR | 64804doc FD24H | Inverter overload factor (OL1) | UINT16 | × 0.01 | % | Read | |||
| HR | 64806doc FD26H | Motor load factor | UINT16 | % | Read | ||||
| HR | 64807doc FD27H | Inverter load factor | UINT16 | % | Read | ||||
| HR | 64809doc FD29H | Input power | UINT16 | × 0.01 | kW | Read | |||
| HR | 64816doc FD30H | Output power | UINT16 | × 0.01 | kW | Read | |||
| HR | 64834doc FD42H | Inverter status 2 | BITMAP16 | Read | bit 7 = Maximum deceleration forced stop active; bit 8 = Accel/decel pattern 2 (AD2); bit 12 = OC stall level 2 | ||||
| HR | 64837doc FD45H | Command mode status | Which source the run command comes from. | UINT16 | Read | 0 = Terminal input; 1 = Operation panel; 2 = RS485 communication | |||
| HR | 64838doc FD46H | Frequency setting mode status | Which source sets the frequency. | UINT16 | Read | 0 = VI input; 1 = Operation panel (auto-save off); 2 = Operation panel (auto-save on); 3 = RS485 communication; 5 = UP/DOWN frequency; 255 = Preset speed operation | |||
| HR | 64841doc FD49H | Inverter status 3 | BITMAP16 | Read | bit 10 = Running at constant speed; bit 11 = Healthy signal; bit 12 = Accel/decel complete (RCH); bit 13 = Specified speed reached (RCHF); bit 14 = Accelerating; bit 15 = Decelerating | ||||
| HR | 65032doc FE08H | CPU version 1 (application) | UINT16 | Read | |||||
| HR | 65040doc FE10H | Past trip 1 (latest) | Same codes as FC90. | UINT16 | Read | 0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error | |||
| HR | 65041doc FE11H | Past trip 2 | UINT16 | Read | 0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error | ||||
| HR | 65042doc FE12H | Past trip 3 | UINT16 | Read | 0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error | ||||
| HR | 65043doc FE13H | Past trip 4 (earliest) | UINT16 | Read | 0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error | ||||
| HR | 65044doc FE14H | Cumulative operation time | UINT16 | h | Read | ||||
| HR | 65077doc FE35H | VI input | 10-bit analog input, 0-100%. | UINT16 | × 0.01 | % | Read | ||
| HR | 65136doc FE70H | Rated current | UINT16 | × 0.1 | A | Read | |||
| HR | 65137doc FE71H | Rated voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 65139doc FE73H | CPU version 2 (motor) | UINT16 | Read | |||||
| HR | 65145doc FE79H | Part replacement alarm information | BITMAP16 | Read | bit 0 = Fan life alarm; bit 1 = Circuit board life alarm; bit 2 = Main-circuit capacitor life alarm; bit 3 = Cumulative operation time alarm | ||||
| HR | 65152doc FE80H | Cumulative power-on time | UINT16 | h | Read |
Notes on this map
- Every register here is a single 16-bit word; the manual has no 32-bit values.
- FD.. registers give live values; the matching FE.. numbers (FE00-FE49) hold the same item frozen at the last trip. Only the live set is listed, plus the FE-only items.
- Left out: torque (FD18) and torque current (FD20), because the manual does not say whether these words are signed; FB05 capacity code (needs the Appendix 3 lookup); LED/keypad registers FA10/FA11/FA65-FA80; block-communication parameters f870-f879.
- Output current, output voltage and DC voltage are percentages of the drive rating, not amps or volts.
- Section 7.2 names the VI monitor FE35, while the block-read list calls it FE36; the monitor table on p. 61 says FE35, which is used here.
- The frequency command FA01 and command words FA00/FA20 are RAM only and reset at power-off, fault reset or factory reset.
- Other drive parameters follow the same rule (f### = communication number 0###); scale = the minimum setting unit in the drive's parameter list.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
What Modbus registers does the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) have?
This map lists 52 registers: 52 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Communication numbers are hex and go on the wire unchanged: the manual's read example sends 01 03 FD 00 00 01 for output frequency FD00, and the direct block-read example sends 01 03 01 30 for parameter f130 (communication number 0130). Parameters f### use communication number 0###.
What are the minimum Modbus registers to integrate the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)?
Start with HR 64000 Command 1 (Run/stop and comms priority bits); HR 64001 Frequency command (Speed reference, 0.01 Hz); HR 64768 Output frequency (Output frequency); HR 64769 Inverter status 1 (Running / tripped / alarm status); HR 64771 Output current (Output current, % of rating); HR 64656 Trip code (Present trip code); HR 64657 Alarm information 1 (Pre-alarm bits).
How do I enable Modbus control of the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)?
Set f829 (communication protocol) to 1 = MODBUS-RTU; the factory setting is 0 (Toshiba protocol). Baud f800, parity f801 and the protocol take effect only after a reset or power cycle. Comms run/frequency control is taken by setting FA00 bits 15 and 14, independent of cmod/fmod.
What happens when the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) loses Modbus communication?
f803 sets a communication time-out (0.0 = off, 0.1-100.0 s); f804 picks alarm only, trip with coast stop or trip with slowdown stop (trip shows err5); f808 sets when it is checked (always, during comms mode, or comms mode and running).
Where is the official Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus documentation?
The source is TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual (E6581657), published free by Toshiba at https://www.toshiba.com/tic/datafiles/manuals/NC3_RS485_Communication_Manual.pdf.
More Toshiba Modbus register maps
- Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3
Other variable frequency drives register maps
- Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program
All variable frequency drives Modbus register maps →
Source: TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual · E6581657. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.