Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The VF-nC3 is a small Toshiba inverter whose RS-485 port speaks either Toshiba's own protocol or a subset of Modbus RTU. Every value has a hex communication number that is used directly as the Modbus register address. This map covers the comms command words (FA..), the monitor block (FC../FD../FE..) and the communication setup parameters.

This page lists 52 Modbus registers for the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.

Manufacturer
Toshiba
Model
TOSVERT VF-nC3 compact inverter (Modbus RTU)
Equipment type
Variable frequency drive
Registers
52 (15 writable)
Transport
Modbus RTU
Default unit ID
0
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3
Source document
TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual · E6581657
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)

Integration in brief

Set f829 = 1 (Modbus RTU) and f802 to a non-zero address, then power-cycle. Write FA00 = C400H (command and frequency priority + run forward) and the speed in FA01 (0.01 Hz), and poll FD00/FD01/FC90 for speed, status and trip.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 64000Command 1BITMAP16Run/stop and comms priority bitsRead/write
HR 64001Frequency commandUINT16Speed reference, 0.01 HzRead/write
HR 64768Output frequencyUINT16Output frequencyRead
HR 64769Inverter status 1BITMAP16Running / tripped / alarm statusRead
HR 64771Output currentUINT16Output current, % of ratingRead
HR 64656Trip codeUINT16Present trip codeRead
HR 64657Alarm information 1BITMAP16Pre-alarm bitsRead

Enable Modbus control & writes

Set f829 (communication protocol) to 1 = MODBUS-RTU; the factory setting is 0 (Toshiba protocol). Baud f800, parity f801 and the protocol take effect only after a reset or power cycle. Comms run/frequency control is taken by setting FA00 bits 15 and 14, independent of cmod/fmod.

Communication loss & watchdog

f803 sets a communication time-out (0.0 = off, 0.1-100.0 s); f804 picks alarm only, trip with coast stop or trip with slowdown stop (trip shows err5); f808 sets when it is checked (always, during comms mode, or comms mode and running).

Byte order & addressing

Network setup

Watch out for

Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

52 of 52 shown
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2048doc 0800HBaud rate (f800)Applies after reset.UINT16Read/write3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps
HR2049doc 0801HParity (f801)Applies after reset.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR2050doc 0802HInverter number (f802)Modbus slave address 0-247; 0 is broadcast.UINT16Read/write
HR2051doc 0803HComm time-out time (f803)0.0 = disabled, 0.1-100.0 s.UINT16× 0.1sRead/write
HR2052doc 0804HComm time-out action (f804)UINT16Read/write0 = Alarm only; 1 = Trip, coast stop; 2 = Trip, slowdown stop
HR2053doc 0805HSend waiting time (f805)0.00 = normal, up to 2.00 s.UINT16× 0.01sRead/write
HR2056doc 0808HComm time-out detection (f808)UINT16Read/write0 = Always; 1 = During communication; 2 = During communication and running
HR2089doc 0829HCommunication protocol (f829)Applies after reset.UINT16Read/write0 = TOSHIBA protocol; 1 = MODBUS-RTU
HR64000doc FA00HCommand 1Run/stop, direction, presets, reset; bits 14/15 hand control to comms.BITMAP16Read/writebit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = Motor 2 (THR2) select; bit 5 = PID control off; bit 6 = Accel/decel pattern 2 (AD2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Reverse (0 = forward); bit 10 = Run (0 = stop); bit 11 = Coast stop; bit 12 = Emergency stop (always enabled); bit 13 = Fault reset (no reply sent); bit 14 = Frequency priority: take frequency from comms; bit 15 = Command priority: take run commands from comms
HR64001doc FA01HFrequency commandComms frequency reference; needs FA00 bit 14 or fmod = 3.UINT16× 0.01HzRead/write
HR64003doc FA03HPanel operation frequencyBetween LL and UL; stored in EEPROM.UINT16× 0.01HzRead/write
HR64032doc FA20HCommand 2Needs FA00 bit 15 set; write 0 to reserved bits.BITMAP16Read/writebit 7 = Maximum deceleration forced stop; bit 12 = OC stall level 2 (F185) instead of 1 (F601)
HR64080doc FA50HTerminal output dataDrives the OUT terminal when f130-f132 = 92/93.BITMAP16Read/writebit 0 = Specified data output 1
HR64081doc FA51HFM analog output dataUsed when fmsl = 18; 8-bit resolution.UINT16× 0.1%Read/write
HR64135doc FA87HReset informationWrite 1; the drive clears it to 0 after it resets.UINT16Read/write
HR64263doc FB07HInverter series typeReads 208 on a VF-nC3.UINT16Read
HR64656doc FC90HTrip codePresent trip.UINT16Read0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error
HR64657doc FC91HAlarm information 1BITMAP16Readbit 0 = Over-current alarm; bit 1 = Inverter overload alarm; bit 2 = Motor overload alarm; bit 3 = Overheat alarm; bit 4 = Overvoltage alarm; bit 5 = Main circuit undervoltage alarm; bit 6 = Main device overheat alarm; bit 7 = Low current alarm; bit 10 = Cumulative operation time alarm; bit 13 = Main circuit undervoltage (MOFF); bit 14 = Forced decel/stop on momentary power failure; bit 15 = Auto stop on prolonged lower-limit running
HR64658doc FC92HAlarm information 2BITMAP16Readbit 2 = Life time alarm; bit 3 = Over-torque alarm; bit 4 = Overload stall alarm; bit 7 = Output frequency upper limit alarm
HR64768doc FD00HOutput frequencyUINT16× 0.01HzRead
HR64769doc FD01HInverter status 1BITMAP16Readbit 0 = FL fault output active; bit 1 = Tripped (incl. retry / trip hold); bit 2 = Alarm issued; bit 3 = Main circuit undervoltage; bit 4 = Motor 2 (THR2) selected; bit 5 = PID control prohibited; bit 6 = Accel/decel pattern 2 (AD2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Reverse (0 = forward); bit 10 = Run (0 = stop); bit 11 = Coast stop: ST off; bit 12 = Emergency stop state; bit 13 = Standby with ST on; bit 14 = Standby
HR64770doc FD02HFrequency command valueUINT16× 0.01HzRead
HR64771doc FD03HOutput currentPercent of drive rated current.UINT16× 0.01%Read
HR64772doc FD04HInput voltage (DC detection)Percent value.UINT16× 0.01%Read
HR64773doc FD05HOutput voltagePercent value.UINT16× 0.01%Read
HR64774doc FD06HInput terminal informationBITMAP16Readbit 0 = F; bit 1 = R; bit 2 = S1; bit 3 = S2; bit 4 = VI (logic input mode)
HR64775doc FD07HOutput terminal informationBITMAP16Readbit 0 = OUT; bit 2 = FL
HR64789doc FD15HCompensated frequencyUINT16× 0.01HzRead
HR64790doc FD16HEstimated speedUINT16× 0.01HzRead
HR64802doc FD22HPID feedback valueUINT16× 0.01HzRead
HR64803doc FD23HMotor overload factor (OL2)UINT16× 0.01%Read
HR64804doc FD24HInverter overload factor (OL1)UINT16× 0.01%Read
HR64806doc FD26HMotor load factorUINT16%Read
HR64807doc FD27HInverter load factorUINT16%Read
HR64809doc FD29HInput powerUINT16× 0.01kWRead
HR64816doc FD30HOutput powerUINT16× 0.01kWRead
HR64834doc FD42HInverter status 2BITMAP16Readbit 7 = Maximum deceleration forced stop active; bit 8 = Accel/decel pattern 2 (AD2); bit 12 = OC stall level 2
HR64837doc FD45HCommand mode statusWhich source the run command comes from.UINT16Read0 = Terminal input; 1 = Operation panel; 2 = RS485 communication
HR64838doc FD46HFrequency setting mode statusWhich source sets the frequency.UINT16Read0 = VI input; 1 = Operation panel (auto-save off); 2 = Operation panel (auto-save on); 3 = RS485 communication; 5 = UP/DOWN frequency; 255 = Preset speed operation
HR64841doc FD49HInverter status 3BITMAP16Readbit 10 = Running at constant speed; bit 11 = Healthy signal; bit 12 = Accel/decel complete (RCH); bit 13 = Specified speed reached (RCHF); bit 14 = Accelerating; bit 15 = Decelerating
HR65032doc FE08HCPU version 1 (application)UINT16Read
HR65040doc FE10HPast trip 1 (latest)Same codes as FC90.UINT16Read0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error
HR65041doc FE11HPast trip 2UINT16Read0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error
HR65042doc FE12HPast trip 3UINT16Read0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error
HR65043doc FE13HPast trip 4 (earliest)UINT16Read0 = No error; 1 = Over-current during acceleration; 2 = Over-current during deceleration; 3 = Over-current at constant speed; 4 = Over-current in load at startup; 5 = Arm over-current at start-up; 8 = Input phase failure; 9 = Output phase failure; 10 = Overvoltage during acceleration; 11 = Overvoltage during deceleration; 12 = Overvoltage at constant speed; 13 = Inverter overload; 14 = Motor overload; 15 = Braking resistor overload; 16 = Overheat; 17 = Emergency stop; 18 = EEPROM fault; 19 = Initial read error; 20 = Initial read error; 21 = Inverter RAM fault; 22 = Inverter ROM fault; 23 = CPU fault; 24 = Communication time-out; 26 = Output current detector error; 27 = Option error; 29 = Low current operation; 30 = Main circuit undervoltage; 32 = Over-torque trip; 34 = Ground fault; 40 = Tuning error; 41 = Inverter type error; 42 = Analog input overvoltage; 45 = Speed error; 46 = External thermal; 50 = Terminal input error; 51 = CPU2 communication fault; 52 = V/f control error; 53 = CPU2 fault; 58 = CPU3 fault; 62 = Main device overheat; 81 = External power logic switching check alarm; 82 = Source logic switching check alarm; 83 = Sink logic switching check alarm; 84 = Auto-tuning error
HR65044doc FE14HCumulative operation timeUINT16hRead
HR65077doc FE35HVI input10-bit analog input, 0-100%.UINT16× 0.01%Read
HR65136doc FE70HRated currentUINT16× 0.1ARead
HR65137doc FE71HRated voltageUINT16× 0.1VRead
HR65139doc FE73HCPU version 2 (motor)UINT16Read
HR65145doc FE79HPart replacement alarm informationBITMAP16Readbit 0 = Fan life alarm; bit 1 = Circuit board life alarm; bit 2 = Main-circuit capacitor life alarm; bit 3 = Cumulative operation time alarm
HR65152doc FE80HCumulative power-on timeUINT16hRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)

What Modbus registers does the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) have?

This map lists 52 registers: 52 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Communication numbers are hex and go on the wire unchanged: the manual's read example sends 01 03 FD 00 00 01 for output frequency FD00, and the direct block-read example sends 01 03 01 30 for parameter f130 (communication number 0130). Parameters f### use communication number 0###.

What are the minimum Modbus registers to integrate the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)?

Start with HR 64000 Command 1 (Run/stop and comms priority bits); HR 64001 Frequency command (Speed reference, 0.01 Hz); HR 64768 Output frequency (Output frequency); HR 64769 Inverter status 1 (Running / tripped / alarm status); HR 64771 Output current (Output current, % of rating); HR 64656 Trip code (Present trip code); HR 64657 Alarm information 1 (Pre-alarm bits).

How do I enable Modbus control of the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)?

Set f829 (communication protocol) to 1 = MODBUS-RTU; the factory setting is 0 (Toshiba protocol). Baud f800, parity f801 and the protocol take effect only after a reset or power cycle. Comms run/frequency control is taken by setting FA00 bits 15 and 14, independent of cmod/fmod.

What happens when the Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) loses Modbus communication?

f803 sets a communication time-out (0.0 = off, 0.1-100.0 s); f804 picks alarm only, trip with coast stop or trip with slowdown stop (trip shows err5); f808 sets when it is checked (always, during comms mode, or comms mode and running).

Where is the official Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU) Modbus documentation?

The source is TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual (E6581657), published free by Toshiba at https://www.toshiba.com/tic/datafiles/manuals/NC3_RS485_Communication_Manual.pdf.

More Toshiba Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual · E6581657. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.