ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's ACS310 is a compact drive for pumps and fans with Modbus RTU built in on its I/O terminals. Every value is a 16-bit holding register: 40001-40006 carry the ABB Drives control word, two references, status word and two selectable actual values, 40031-40034 the DCU profile words, and each parameter NNNN sits at register 4NNNN. This map covers the control block, the main actual signals, fault and alarm words, fault history and the communication set-up parameters.
This page lists 57 Modbus registers for the ABB ACS310 pump and fan drive (embedded Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- ACS310 pump and fan drive (embedded Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 57 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U
Integration notes: ABB ACS310 pump and fan drive (embedded Modbus RTU)
Set 9802 = STD MODBUS and the group 53 link settings, then 5305 = ABB DRV FULL, point 1001 EXT1 COMMANDS and 1103 REF1 SELECT at COMM, write the control word and REF1 at 40001/40002 and poll the status word plus 0103/0104 at 40103/40104.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control word (ABB Drives) | BITMAP16 | Control word: start/stop/reset | Read/write |
| HR 1 | Reference 1 (REF1) | INT16 | REF1 frequency setpoint (20000 = 1105) | Read/write |
| HR 3 | Status word (ABB Drives) | BITMAP16 | Status word: ready/running/fault/remote | Read |
| HR 102 | 0103 Output freq | UINT16 | 0103 Output frequency, 0.1 Hz | Read |
| HR 103 | 0104 Current | UINT16 | 0104 Motor current, 0.1 A | Read |
| HR 106 | 0107 DC bus voltage | UINT16 | 0107 DC bus voltage | Read |
| HR 400 | 0401 Last fault | UINT16 | 0401 Last fault code | Read |
| HR 304 | 0305 Fault word 1 | BITMAP16 | 0305 Fault word 1 | Read |
Enable Modbus control & writes
Set 1611 PARAMETER VIEW = LONG VIEW, then 9802 COMM PROT SEL = STD MODBUS (EIA-485 on terminals 23-26) or MODBUS RS232 (panel connector). Set 5302 station ID, 5303 baud, 5304 parity and 5305 profile. For control set 1001 EXT1 COMMANDS = COMM (1002 for EXT2), 1103 REF1 SELECT = COMM, and optionally 1102, 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Save fieldbus parameter writes with 1607 PARAM SAVE.
Communication loss & watchdog
3018 COMM FAULT FUNC (NOT SEL default / FAULT / CONST SP 7 / LAST SPEED) after the delay in 3019 COMM FAULT TIME (default 3.0 s, 0.1 s steps). FAULT trips SERIAL 1 ERR and coasts; the other two raise alarm IO COMM and keep running.
Byte order & addressing
- Register 4xxxx is wire address xxxx - 1 (40001 = 0); parameter NNNN is register 4NNNN.
- Everything is 16-bit; there is no word order to worry about.
- Start per the state diagram (p. 306): write 0x0476 (ready to switch on), then 0x0477 once status bit 0 is 1 (ready to operate), then 0x047F to run; bits 4 and 10 in these values only matter with ABB DRV FULL. Control word bit 3 also needs the run enable (1601). Fault reset is a 0->1 edge on bit 7 with 1604 = COMM.
- Parameter writes over Modbus are volatile until 1607 PARAM SAVE is used.
Network setup
- Parameter-list defaults: station 1, 9.6 kbit/s, 8 data bits, no parity, 1 stop bit.
- The RS-232 option uses the control panel connector.
Watch out for
- Reading or writing a register that is not a parameter returns exception 02; writing a read-only parameter, an out-of-range value, or a parameter while started returns exception 03.
- With the default ABB DRV LIM profile, control word bits 4 and 10 are ignored.
ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Control word (ABB Drives) | ABB DRV LIM/FULL only (5305). | BITMAP16 | Read/write | bit 0 = OFF1 CONTROL: 1 = ready to operate, 0 = ramp stop; bit 1 = OFF2 CONTROL: 0 = emergency OFF, coast to stop; bit 2 = OFF3 CONTROL: 0 = emergency stop (2208 time); bit 3 = INHIBIT OPERATION: 1 = operation enabled (run), 0 = inhibit; bit 4 = RAMP_OUT_ZERO (ABB DRV FULL only): 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 0 = halt ramping; bit 6 = RAMP_IN_ZERO: 0 = force ramp input to zero; bit 7 = RESET: 0->1 = fault reset (1604 = COMM); bit 8 = Not in use; bit 9 = Not in use; bit 10 = REMOTE_CMD (ABB DRV FULL only): 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = EXT2, 0 = EXT1 (1102 = COMM); bit 12 = MOTOR_HEAT: 1 = start motor heating; bit 13 = Reserved; bit 14 = Reserved; bit 15 = Reserved | |||
| HR | 1doc 40002 | Reference 1 (REF1) | Signed; 20000 = 1105 REF1 MAX (frequency). | INT16 | Read/write | ||||
| HR | 2doc 40003 | Reference 2 (REF2) | Signed; 10000 = 1108 REF2 MAX. | INT16 | Read/write | ||||
| HR | 3doc 40004 | Status word (ABB Drives) | ABB DRV LIM/FULL only (5305). | BITMAP16 | Read | bit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate; bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibited; bit 7 = ALARM; bit 8 = AT_SETPOINT: output frequency at reference; bit 9 = REMOTE: 1 = EXT1/EXT2, 0 = local; bit 10 = ABOVE_LIMIT: supervised value above limit (group 32); bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE: run enable received; bit 13 = MOTOR_HEAT: motor heating on; bit 14 = Reserved; bit 15 = Reserved | |||
| HR | 4doc 40005 | Actual value 1 | Signal chosen by 5310; scaling is that of the chosen signal. | INT16 | Read | ||||
| HR | 5doc 40006 | Actual value 2 | Signal chosen by 5311. | INT16 | Read | ||||
| HR | 30doc 40031 | DCU control word LSW (0301) | DCU profile only. | BITMAP16 | Read/write | ||||
| HR | 31doc 40032 | DCU control word MSW (0302) | DCU profile only. | BITMAP16 | Read/write | ||||
| HR | 32doc 40033 | DCU status word LSW (0303) | DCU profile only. | BITMAP16 | Read | ||||
| HR | 33doc 40034 | DCU status word MSW (0304) | DCU profile only. | BITMAP16 | Read | ||||
| HR | 100doc 40101 | 0101 Speed & dir | Calculated motor speed; negative = reverse. | INT16 | rpm | Read | |||
| HR | 101doc 40102 | 0102 Speed | Calculated motor speed. | UINT16 | rpm | Read | |||
| HR | 102doc 40103 | 0103 Output freq | UINT16 | × 0.1 | Hz | Read | |||
| HR | 103doc 40104 | 0104 Current | Measured motor current. | UINT16 | × 0.1 | A | Read | ||
| HR | 104doc 40105 | 0105 Torque | Percent of nominal motor torque. | INT16 | × 0.1 | % | Read | ||
| HR | 105doc 40106 | 0106 Power | Measured motor power. | INT16 | × 0.1 | kW | Read | ||
| HR | 106doc 40107 | 0107 DC bus voltage | UINT16 | V | Read | ||||
| HR | 108doc 40109 | 0109 Output voltage | UINT16 | V | Read | ||||
| HR | 109doc 40110 | 0110 Drive temp | IGBT temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 110doc 40111 | 0111 External ref 1 | REF1 in Hz. | INT16 | × 0.1 | Hz | Read | ||
| HR | 111doc 40112 | 0112 External ref 2 | REF2 in percent. | INT16 | × 0.1 | % | Read | ||
| HR | 112doc 40113 | 0113 Ctrl location | UINT16 | Read | 0 = LOCAL; 1 = EXT1; 2 = EXT2 | ||||
| HR | 113doc 40114 | 0114 Run time (R) | Resettable run hours. | UINT16 | h | Read | |||
| HR | 114doc 40115 | 0115 kWh counter (R) | Rolls over at 65535; resettable. | UINT16 | kWh | Read | |||
| HR | 139doc 40140 | 0140 Run time | Run time in thousands of hours. | UINT16 | × 0.01 | kh | Read | ||
| HR | 140doc 40141 | 0141 MWh counter | Rolls over at 65535. | UINT16 | MWh | Read | |||
| HR | 142doc 40143 | 0143 Drive on time hi | Control board power-on time in days. | UINT16 | days | Read | |||
| HR | 143doc 40144 | 0144 Drive on time lo | Power-on time in 2 s ticks within the day. | UINT16 | × 2 | s | Read | ||
| HR | 161doc 40162 | 0162 RO status | Relay output 1: 1 = energized. | UINT16 | Read | ||||
| HR | 304doc 40305 | 0305 Fault word 1 | BITMAP16 | Read | bit 0 = OVERCURRENT; bit 1 = DC OVERVOLT; bit 2 = DEV OVERTEMP; bit 3 = SHORT CIRC; bit 4 = Reserved; bit 5 = DC UNDERVOLT; bit 6 = AI1 LOSS; bit 7 = AI2 LOSS; bit 8 = MOT OVERTEMP; bit 9 = PANEL LOSS; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = Reserved; bit 13 = EXT FAULT 1; bit 14 = EXT FAULT 2; bit 15 = EARTH FAULT | ||||
| HR | 305doc 40306 | 0306 Fault word 2 | BITMAP16 | Read | bit 0 = Reserved; bit 1 = THERM FAIL; bit 2 = Reserved; bit 3 = Reserved; bit 4 = CURR MEAS; bit 5 = SUPPLY PHASE; bit 6 = Reserved; bit 7 = OVERSPEED; bit 8 = Reserved; bit 9 = DRIVE ID; bit 10 = CONFIG FILE; bit 11 = SERIAL 1 ERR; bit 12 = EFB CON FILE; bit 13 = FORCE TRIP; bit 14 = MOTOR PHASE; bit 15 = OUTP WIRING | ||||
| HR | 306doc 40307 | 0307 Fault word 3 | BITMAP16 | Read | bit 0 = EFB 1; bit 1 = EFB 2; bit 2 = EFB 3; bit 3 = INCOMPATIBLE SW; bit 4 = USER LOAD CURVE; bit 5 = UNKNOWN EXTENSION; bit 6 = INLET VERY LOW; bit 7 = OUTLET VERY HIGH; bit 8 = INLET LOW; bit 9 = OUTLET HIGH; bit 10 = System error; bit 11 = System error; bit 12 = System error; bit 13 = System error; bit 14 = System error; bit 15 = Parameter setting fault | ||||
| HR | 307doc 40308 | 0308 Alarm word 1 | BITMAP16 | Read | bit 0 = OVERCURRENT; bit 1 = OVERVOLTAGE; bit 2 = UNDERVOLTAGE; bit 3 = DIR LOCK; bit 4 = IO COMM; bit 5 = AI1 LOSS; bit 6 = AI2 LOSS; bit 7 = PANEL LOSS; bit 8 = DEVICE OVERTEMP; bit 9 = MOTOR TEMP; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = AUTORESET; bit 13 = AUTOCHANGE; bit 14 = PFC I LOCK; bit 15 = Reserved | ||||
| HR | 308doc 40309 | 0309 Alarm word 2 | BITMAP16 | Read | bit 0 = Reserved; bit 1 = PID SLEEP; bit 2 = Reserved; bit 3 = Reserved; bit 4 = START ENABLE 1 MISSING; bit 5 = START ENABLE 2 MISSING; bit 6 = EMERGENCY STOP; bit 7 = Reserved; bit 8 = FIRST START; bit 9 = Reserved; bit 10 = USER LOAD CURVE; bit 11 = START DELAY; bit 12 = Reserved; bit 13 = INLET LOW; bit 14 = OUTLET HIGH; bit 15 = PIPE FILL | ||||
| HR | 309doc 40310 | 0310 Alarm word 3 | Bits 2-15 reserved. | BITMAP16 | Read | bit 0 = INLET VERY LOW; bit 1 = OUTLET VERY HIGH | |||
| HR | 400doc 40401 | 0401 Last fault | Latest fault code; 0 = history clear. | UINT16 | Read | ||||
| HR | 403doc 40404 | 0404 Speed at flt | INT16 | rpm | Read | ||||
| HR | 404doc 40405 | 0405 Freq at flt | INT16 | × 0.1 | Hz | Read | |||
| HR | 405doc 40406 | 0406 Voltage at flt | DC voltage at the fault. | UINT16 | × 0.1 | V | Read | ||
| HR | 406doc 40407 | 0407 Current at flt | UINT16 | × 0.1 | A | Read | |||
| HR | 407doc 40408 | 0408 Torque at flt | INT16 | × 0.1 | % | Read | |||
| HR | 411doc 40412 | 0412 Previous fault 1 | Second latest fault code. | UINT16 | Read | ||||
| HR | 412doc 40413 | 0413 Previous fault 2 | Third latest fault code. | UINT16 | Read | ||||
| HR | 1606doc 41607 | 1607 Param save | Write 1 to save parameters to permanent memory. | UINT16 | Read/write | 0 = DONE; 1 = SAVE... | |||
| HR | 3017doc 43018 | 3018 Comm fault func | Reaction to fieldbus communication loss. | UINT16 | Read/write | 0 = NOT SEL; 1 = FAULT; 2 = CONST SP 7; 3 = LAST SPEED | |||
| HR | 3018doc 43019 | 3019 Comm fault time | Delay before 3018 acts (0.0-600.0 s). | UINT16 | × 0.1 | s | Read/write | ||
| HR | 5301doc 45302 | 5302 EFB station ID | UINT16 | Read/write | |||||
| HR | 5302doc 45303 | 5303 EFB baud rate | 1.2-76.8 kbit/s. | UINT16 | × 0.1 | kbit/s | Read/write | ||
| HR | 5303doc 45304 | 5304 EFB parity | UINT16 | Read/write | 0 = 8 NONE 1; 1 = 8 NONE 2; 2 = 8 EVEN 1; 3 = 8 ODD 1 | ||||
| HR | 5304doc 45305 | 5305 EFB ctrl profile | UINT16 | Read/write | 0 = ABB DRV LIM; 1 = DCU PROFILE; 2 = ABB DRV FULL | ||||
| HR | 5305doc 45306 | 5306 EFB OK messages | Count of valid messages. | UINT16 | Read | ||||
| HR | 5306doc 45307 | 5307 EFB CRC errors | Count of messages with CRC errors. | UINT16 | Read | ||||
| HR | 5307doc 45308 | 5308 EFB UART errors | Count of character errors. | UINT16 | Read | ||||
| HR | 5308doc 45309 | 5309 EFB status | UINT16 | Read | 0 = IDLE; 1 = EXECUT INIT; 2 = TIME OUT; 3 = CONFIG ERROR; 4 = OFF-LINE; 5 = ON-LINE; 6 = RESET; 7 = LISTEN ONLY | ||||
| HR | 5309doc 45310 | 5310 EFB par 10 | Parameter index mapped to 40005. | UINT16 | Read/write | ||||
| HR | 5310doc 45311 | 5311 EFB par 11 | Parameter index mapped to 40006. | UINT16 | Read/write | ||||
| HR | 9801doc 49802 | 9802 Comm prot sel | UINT16 | Read/write | 0 = NOT SEL; 1 = STD MODBUS; 10 = MODBUS RS232 |
Notes on this map
- There are no 32-bit registers: the manual states all values read or written are limited to 16 bits (-32768...32767). Signals that can be negative are listed as INT16.
- Scaling is the manual's FbEq column (fieldbus integer per unit, e.g. '1 = 0.1 Hz' -> scale 0.1).
- 40001 and 40004 work only with 5305 = ABB DRV LIM or ABB DRV FULL; 40031-40034 only with 5305 = DCU PROFILE. Control word bits 4 and 10 work only with ABB DRV FULL.
- Actual values 40005-40012 follow 5310-5317 (all default 0 in the parameter list). Their scaling is that of the chosen signal, so they are left unscaled; 40007-40012 are not listed.
- Reference scaling (ABB Drives profile): REF1 20000 = 1105 REF1 MAX, REF2 10000 = 1108 REF2 MAX; final references are limited by 1104/1105 and 1107/1108.
- Group 03 fault and alarm words are listed read-only, but the manual says an alarm can be cleared by writing zero to the whole alarm word.
- Left out: analog I/O, PID and process-variable signals (0116-0139, units depend on configuration), 0402/0403 fault time stamps, 0409 status at fault, energy-saving counters, 40080-40089 Modbus data OUT, and all motor/application parameters.
- Coils (control-word bits 1-16, relay outputs from 33), discrete inputs and two input registers (analog inputs) are mentioned in the function code table but not listed here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB ACS310 pump and fan drive (embedded Modbus RTU)
What Modbus registers does the ABB ACS310 pump and fan drive (embedded Modbus RTU) have?
This map lists 57 registers: 57 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists 4xxxx holding registers and states that register 4xxxx is sent as xxxx - 1 in the Modbus message (its example: 40002 is addressed as 0001), so 40001 = wire address 0. Parameter NNNN sits at register 4NNNN (e.g. 0103 -> 40103, wire 102; 3018 -> 43018, wire 3017).
What are the minimum Modbus registers to integrate the ABB ACS310 pump and fan drive (embedded Modbus RTU)?
Start with HR 0 Control word (ABB Drives) (Control word: start/stop/reset); HR 1 Reference 1 (REF1) (REF1 frequency setpoint (20000 = 1105)); HR 3 Status word (ABB Drives) (Status word: ready/running/fault/remote); HR 102 0103 Output freq (0103 Output frequency, 0.1 Hz); HR 103 0104 Current (0104 Motor current, 0.1 A); HR 106 0107 DC bus voltage (0107 DC bus voltage); HR 400 0401 Last fault (0401 Last fault code); HR 304 0305 Fault word 1 (0305 Fault word 1).
How do I enable Modbus control of the ABB ACS310 pump and fan drive (embedded Modbus RTU)?
Set 1611 PARAMETER VIEW = LONG VIEW, then 9802 COMM PROT SEL = STD MODBUS (EIA-485 on terminals 23-26) or MODBUS RS232 (panel connector). Set 5302 station ID, 5303 baud, 5304 parity and 5305 profile. For control set 1001 EXT1 COMMANDS = COMM (1002 for EXT2), 1103 REF1 SELECT = COMM, and optionally 1102, 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Save fieldbus parameter writes with 1607 PARAM SAVE.
What happens when the ABB ACS310 pump and fan drive (embedded Modbus RTU) loses Modbus communication?
3018 COMM FAULT FUNC (NOT SEL default / FAULT / CONST SP 7 / LAST SPEED) after the delay in 3019 COMM FAULT TIME (default 3.0 s, 0.1 s steps). FAULT trips SERIAL 1 ERR and coasts; the other two raise alarm IO COMM and keep running.
Where is the official ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus documentation?
The source is ACS310 drives user's manual (3AUA0000044201 Rev D), revision 2016-01-11, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AUA0000044201&LanguageCode=en&DocumentPartId=1&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other variable frequency drives register maps
- Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD
All variable frequency drives Modbus register maps →
Source: ACS310 drives user's manual · 3AUA0000044201 Rev D · rev. 2016-01-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.