Variable frequency drive · Modbus register map

ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

ABB's ACS310 is a compact drive for pumps and fans with Modbus RTU built in on its I/O terminals. Every value is a 16-bit holding register: 40001-40006 carry the ABB Drives control word, two references, status word and two selectable actual values, 40031-40034 the DCU profile words, and each parameter NNNN sits at register 4NNNN. This map covers the control block, the main actual signals, fault and alarm words, fault history and the communication set-up parameters.

This page lists 57 Modbus registers for the ABB ACS310 pump and fan drive (embedded Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
ACS310 pump and fan drive (embedded Modbus RTU)
Equipment type
Variable frequency drive
Registers
57 (15 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U
Source document
ACS310 drives user's manual · 3AUA0000044201 Rev D · rev. 2016-01-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB ACS310 pump and fan drive (embedded Modbus RTU)

Integration in brief

Set 9802 = STD MODBUS and the group 53 link settings, then 5305 = ABB DRV FULL, point 1001 EXT1 COMMANDS and 1103 REF1 SELECT at COMM, write the control word and REF1 at 40001/40002 and poll the status word plus 0103/0104 at 40103/40104.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Control word (ABB Drives)BITMAP16Control word: start/stop/resetRead/write
HR 1Reference 1 (REF1)INT16REF1 frequency setpoint (20000 = 1105)Read/write
HR 3Status word (ABB Drives)BITMAP16Status word: ready/running/fault/remoteRead
HR 1020103 Output freqUINT160103 Output frequency, 0.1 HzRead
HR 1030104 CurrentUINT160104 Motor current, 0.1 ARead
HR 1060107 DC bus voltageUINT160107 DC bus voltageRead
HR 4000401 Last faultUINT160401 Last fault codeRead
HR 3040305 Fault word 1BITMAP160305 Fault word 1Read

Enable Modbus control & writes

Set 1611 PARAMETER VIEW = LONG VIEW, then 9802 COMM PROT SEL = STD MODBUS (EIA-485 on terminals 23-26) or MODBUS RS232 (panel connector). Set 5302 station ID, 5303 baud, 5304 parity and 5305 profile. For control set 1001 EXT1 COMMANDS = COMM (1002 for EXT2), 1103 REF1 SELECT = COMM, and optionally 1102, 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Save fieldbus parameter writes with 1607 PARAM SAVE.

Communication loss & watchdog

3018 COMM FAULT FUNC (NOT SEL default / FAULT / CONST SP 7 / LAST SPEED) after the delay in 3019 COMM FAULT TIME (default 3.0 s, 0.1 s steps). FAULT trips SERIAL 1 ERR and coasts; the other two raise alarm IO COMM and keep running.

Byte order & addressing

Network setup

Watch out for

ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

57 of 57 shown
ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Control word (ABB Drives)ABB DRV LIM/FULL only (5305).BITMAP16Read/writebit 0 = OFF1 CONTROL: 1 = ready to operate, 0 = ramp stop; bit 1 = OFF2 CONTROL: 0 = emergency OFF, coast to stop; bit 2 = OFF3 CONTROL: 0 = emergency stop (2208 time); bit 3 = INHIBIT OPERATION: 1 = operation enabled (run), 0 = inhibit; bit 4 = RAMP_OUT_ZERO (ABB DRV FULL only): 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 0 = halt ramping; bit 6 = RAMP_IN_ZERO: 0 = force ramp input to zero; bit 7 = RESET: 0->1 = fault reset (1604 = COMM); bit 8 = Not in use; bit 9 = Not in use; bit 10 = REMOTE_CMD (ABB DRV FULL only): 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = EXT2, 0 = EXT1 (1102 = COMM); bit 12 = MOTOR_HEAT: 1 = start motor heating; bit 13 = Reserved; bit 14 = Reserved; bit 15 = Reserved
HR1doc 40002Reference 1 (REF1)Signed; 20000 = 1105 REF1 MAX (frequency).INT16Read/write
HR2doc 40003Reference 2 (REF2)Signed; 10000 = 1108 REF2 MAX.INT16Read/write
HR3doc 40004Status word (ABB Drives)ABB DRV LIM/FULL only (5305).BITMAP16Readbit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate; bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibited; bit 7 = ALARM; bit 8 = AT_SETPOINT: output frequency at reference; bit 9 = REMOTE: 1 = EXT1/EXT2, 0 = local; bit 10 = ABOVE_LIMIT: supervised value above limit (group 32); bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE: run enable received; bit 13 = MOTOR_HEAT: motor heating on; bit 14 = Reserved; bit 15 = Reserved
HR4doc 40005Actual value 1Signal chosen by 5310; scaling is that of the chosen signal.INT16Read
HR5doc 40006Actual value 2Signal chosen by 5311.INT16Read
HR30doc 40031DCU control word LSW (0301)DCU profile only.BITMAP16Read/write
HR31doc 40032DCU control word MSW (0302)DCU profile only.BITMAP16Read/write
HR32doc 40033DCU status word LSW (0303)DCU profile only.BITMAP16Read
HR33doc 40034DCU status word MSW (0304)DCU profile only.BITMAP16Read
HR100doc 401010101 Speed & dirCalculated motor speed; negative = reverse.INT16rpmRead
HR101doc 401020102 SpeedCalculated motor speed.UINT16rpmRead
HR102doc 401030103 Output freqUINT16× 0.1HzRead
HR103doc 401040104 CurrentMeasured motor current.UINT16× 0.1ARead
HR104doc 401050105 TorquePercent of nominal motor torque.INT16× 0.1%Read
HR105doc 401060106 PowerMeasured motor power.INT16× 0.1kWRead
HR106doc 401070107 DC bus voltageUINT16VRead
HR108doc 401090109 Output voltageUINT16VRead
HR109doc 401100110 Drive tempIGBT temperature.INT16× 0.1°CRead
HR110doc 401110111 External ref 1REF1 in Hz.INT16× 0.1HzRead
HR111doc 401120112 External ref 2REF2 in percent.INT16× 0.1%Read
HR112doc 401130113 Ctrl locationUINT16Read0 = LOCAL; 1 = EXT1; 2 = EXT2
HR113doc 401140114 Run time (R)Resettable run hours.UINT16hRead
HR114doc 401150115 kWh counter (R)Rolls over at 65535; resettable.UINT16kWhRead
HR139doc 401400140 Run timeRun time in thousands of hours.UINT16× 0.01khRead
HR140doc 401410141 MWh counterRolls over at 65535.UINT16MWhRead
HR142doc 401430143 Drive on time hiControl board power-on time in days.UINT16daysRead
HR143doc 401440144 Drive on time loPower-on time in 2 s ticks within the day.UINT16× 2sRead
HR161doc 401620162 RO statusRelay output 1: 1 = energized.UINT16Read
HR304doc 403050305 Fault word 1BITMAP16Readbit 0 = OVERCURRENT; bit 1 = DC OVERVOLT; bit 2 = DEV OVERTEMP; bit 3 = SHORT CIRC; bit 4 = Reserved; bit 5 = DC UNDERVOLT; bit 6 = AI1 LOSS; bit 7 = AI2 LOSS; bit 8 = MOT OVERTEMP; bit 9 = PANEL LOSS; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = Reserved; bit 13 = EXT FAULT 1; bit 14 = EXT FAULT 2; bit 15 = EARTH FAULT
HR305doc 403060306 Fault word 2BITMAP16Readbit 0 = Reserved; bit 1 = THERM FAIL; bit 2 = Reserved; bit 3 = Reserved; bit 4 = CURR MEAS; bit 5 = SUPPLY PHASE; bit 6 = Reserved; bit 7 = OVERSPEED; bit 8 = Reserved; bit 9 = DRIVE ID; bit 10 = CONFIG FILE; bit 11 = SERIAL 1 ERR; bit 12 = EFB CON FILE; bit 13 = FORCE TRIP; bit 14 = MOTOR PHASE; bit 15 = OUTP WIRING
HR306doc 403070307 Fault word 3BITMAP16Readbit 0 = EFB 1; bit 1 = EFB 2; bit 2 = EFB 3; bit 3 = INCOMPATIBLE SW; bit 4 = USER LOAD CURVE; bit 5 = UNKNOWN EXTENSION; bit 6 = INLET VERY LOW; bit 7 = OUTLET VERY HIGH; bit 8 = INLET LOW; bit 9 = OUTLET HIGH; bit 10 = System error; bit 11 = System error; bit 12 = System error; bit 13 = System error; bit 14 = System error; bit 15 = Parameter setting fault
HR307doc 403080308 Alarm word 1BITMAP16Readbit 0 = OVERCURRENT; bit 1 = OVERVOLTAGE; bit 2 = UNDERVOLTAGE; bit 3 = DIR LOCK; bit 4 = IO COMM; bit 5 = AI1 LOSS; bit 6 = AI2 LOSS; bit 7 = PANEL LOSS; bit 8 = DEVICE OVERTEMP; bit 9 = MOTOR TEMP; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = AUTORESET; bit 13 = AUTOCHANGE; bit 14 = PFC I LOCK; bit 15 = Reserved
HR308doc 403090309 Alarm word 2BITMAP16Readbit 0 = Reserved; bit 1 = PID SLEEP; bit 2 = Reserved; bit 3 = Reserved; bit 4 = START ENABLE 1 MISSING; bit 5 = START ENABLE 2 MISSING; bit 6 = EMERGENCY STOP; bit 7 = Reserved; bit 8 = FIRST START; bit 9 = Reserved; bit 10 = USER LOAD CURVE; bit 11 = START DELAY; bit 12 = Reserved; bit 13 = INLET LOW; bit 14 = OUTLET HIGH; bit 15 = PIPE FILL
HR309doc 403100310 Alarm word 3Bits 2-15 reserved.BITMAP16Readbit 0 = INLET VERY LOW; bit 1 = OUTLET VERY HIGH
HR400doc 404010401 Last faultLatest fault code; 0 = history clear.UINT16Read
HR403doc 404040404 Speed at fltINT16rpmRead
HR404doc 404050405 Freq at fltINT16× 0.1HzRead
HR405doc 404060406 Voltage at fltDC voltage at the fault.UINT16× 0.1VRead
HR406doc 404070407 Current at fltUINT16× 0.1ARead
HR407doc 404080408 Torque at fltINT16× 0.1%Read
HR411doc 404120412 Previous fault 1Second latest fault code.UINT16Read
HR412doc 404130413 Previous fault 2Third latest fault code.UINT16Read
HR1606doc 416071607 Param saveWrite 1 to save parameters to permanent memory.UINT16Read/write0 = DONE; 1 = SAVE...
HR3017doc 430183018 Comm fault funcReaction to fieldbus communication loss.UINT16Read/write0 = NOT SEL; 1 = FAULT; 2 = CONST SP 7; 3 = LAST SPEED
HR3018doc 430193019 Comm fault timeDelay before 3018 acts (0.0-600.0 s).UINT16× 0.1sRead/write
HR5301doc 453025302 EFB station IDUINT16Read/write
HR5302doc 453035303 EFB baud rate1.2-76.8 kbit/s.UINT16× 0.1kbit/sRead/write
HR5303doc 453045304 EFB parityUINT16Read/write0 = 8 NONE 1; 1 = 8 NONE 2; 2 = 8 EVEN 1; 3 = 8 ODD 1
HR5304doc 453055305 EFB ctrl profileUINT16Read/write0 = ABB DRV LIM; 1 = DCU PROFILE; 2 = ABB DRV FULL
HR5305doc 453065306 EFB OK messagesCount of valid messages.UINT16Read
HR5306doc 453075307 EFB CRC errorsCount of messages with CRC errors.UINT16Read
HR5307doc 453085308 EFB UART errorsCount of character errors.UINT16Read
HR5308doc 453095309 EFB statusUINT16Read0 = IDLE; 1 = EXECUT INIT; 2 = TIME OUT; 3 = CONFIG ERROR; 4 = OFF-LINE; 5 = ON-LINE; 6 = RESET; 7 = LISTEN ONLY
HR5309doc 453105310 EFB par 10Parameter index mapped to 40005.UINT16Read/write
HR5310doc 453115311 EFB par 11Parameter index mapped to 40006.UINT16Read/write
HR9801doc 498029802 Comm prot selUINT16Read/write0 = NOT SEL; 1 = STD MODBUS; 10 = MODBUS RS232

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB ACS310 pump and fan drive (embedded Modbus RTU)

What Modbus registers does the ABB ACS310 pump and fan drive (embedded Modbus RTU) have?

This map lists 57 registers: 57 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists 4xxxx holding registers and states that register 4xxxx is sent as xxxx - 1 in the Modbus message (its example: 40002 is addressed as 0001), so 40001 = wire address 0. Parameter NNNN sits at register 4NNNN (e.g. 0103 -> 40103, wire 102; 3018 -> 43018, wire 3017).

What are the minimum Modbus registers to integrate the ABB ACS310 pump and fan drive (embedded Modbus RTU)?

Start with HR 0 Control word (ABB Drives) (Control word: start/stop/reset); HR 1 Reference 1 (REF1) (REF1 frequency setpoint (20000 = 1105)); HR 3 Status word (ABB Drives) (Status word: ready/running/fault/remote); HR 102 0103 Output freq (0103 Output frequency, 0.1 Hz); HR 103 0104 Current (0104 Motor current, 0.1 A); HR 106 0107 DC bus voltage (0107 DC bus voltage); HR 400 0401 Last fault (0401 Last fault code); HR 304 0305 Fault word 1 (0305 Fault word 1).

How do I enable Modbus control of the ABB ACS310 pump and fan drive (embedded Modbus RTU)?

Set 1611 PARAMETER VIEW = LONG VIEW, then 9802 COMM PROT SEL = STD MODBUS (EIA-485 on terminals 23-26) or MODBUS RS232 (panel connector). Set 5302 station ID, 5303 baud, 5304 parity and 5305 profile. For control set 1001 EXT1 COMMANDS = COMM (1002 for EXT2), 1103 REF1 SELECT = COMM, and optionally 1102, 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Save fieldbus parameter writes with 1607 PARAM SAVE.

What happens when the ABB ACS310 pump and fan drive (embedded Modbus RTU) loses Modbus communication?

3018 COMM FAULT FUNC (NOT SEL default / FAULT / CONST SP 7 / LAST SPEED) after the delay in 3019 COMM FAULT TIME (default 3.0 s, 0.1 s steps). FAULT trips SERIAL 1 ERR and coasts; the other two raise alarm IO COMM and keep running.

Where is the official ABB ACS310 pump and fan drive (embedded Modbus RTU) Modbus documentation?

The source is ACS310 drives user's manual (3AUA0000044201 Rev D), revision 2016-01-11, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AUA0000044201&LanguageCode=en&DocumentPartId=1&Action=Launch.

More ABB Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: ACS310 drives user's manual · 3AUA0000044201 Rev D · rev. 2016-01-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.