Power meter (circuit breaker trip unit) · Modbus register map
ABB SACE Tmax PR223DS trip unit (Modbus RTU) Modbus register map
Updated 19 November 2026
The PR223DS trip unit on Tmax moulded-case breakers has a built-in Modbus RTU interface. Measurements, status, alarms and trip data are input registers; open, close and reset commands are single holding registers set to 1. 32-bit power and energy values are sent low word first.
This page lists 47 Modbus registers for the ABB SACE Tmax PR223DS trip unit (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- SACE Tmax PR223DS trip unit (Modbus RTU)
- Equipment type
- Power meter (circuit breaker trip unit)
- Registers
- 47 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 247
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- SW 02.02
- Also known as
- PR223DS, Tmax PR223DS, SACE PR223DS
Integration notes: ABB SACE Tmax PR223DS trip unit (Modbus RTU)
Read input registers 30101-30156 with function 4 for currents, voltages, power and energy, and 30034-30036 for status, alarms and trips. Write 1 to 40001 / 40003 to open or close.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 33 | Status | BITMAP16 | CB open/closed/tripped, local/remote | Read |
| IR 35 | Trips | BITMAP16 | Which protection tripped | Read |
| IR 100 | RMS current phase 1 | UINT16 | Phase 1 current | Read |
| IR 119 | Total active power | INT32 CDAB | Total active power | Read |
| IR 145 | Positive active energy | INT32 CDAB | Active energy | Read |
| HR 0 | CB open command | UINT16 | Open command | Write |
Enable Modbus control & writes
Modbus is built into the trip unit; address, baud, parity and addressing type are set locally with the ABB Test Unit. Remote commands need the trip unit in Remote mode (LOCAL/REMOTE button); CB open/close also fails if the motor operator selector is on MANUAL or the motor command is faulty.
Byte order & addressing
- 32-bit values are low word first.
- Measurements use function 4 (input registers).
- Event bits in 30033 clear after reading.
Network setup
- Defaults: address 247, 19200 baud, even parity; 9600 baud and odd/no parity also allowed.
Watch out for
- Factory address is 247.
- Only one command is processed at a time; a second pending command is refused.
ABB SACE Tmax PR223DS trip unit (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 6doc 30007 | CB number of operations | Transitions to open, any cause. | UINT16 | Read | ||||
| IR | 8doc 30009 | CB number of protection trips | UINT16 | Read | |||||
| IR | 33doc 30034 | Status | Breaker and trip unit status. | BITMAP16 | Read | bit 0 = Any alarm; bit 1 = Any trip; bit 2 = CB tripped; bit 3 = CB closed (0 = open); bit 4 = Trip command fail; bit 5 = Other trip (test, UVR, SOR); bit 6 = Local mode (0 = remote); bit 7 = Programming OK; bit 8 = Programming fail; bit 11 = EEPROM parameters error; bit 12 = AUX-E unknown; bit 13 = Nominal current unknown; bit 14 = Serial parameters unknown; bit 15 = Trip data available | |||
| IR | 34doc 30035 | Alarms | BITMAP16 | Read | bit 0 = L pre-alarm; bit 1 = L alarm (timing/tripping); bit 2 = S alarm (timing/tripping); bit 3 = G alarm (timing/tripping); bit 4 = Motor command overheated; bit 11 = DSP fault; bit 13 = TC error; bit 14 = Frequency out of range; bit 15 = Clock oscillator fault | ||||
| IR | 35doc 30036 | Trips | Held until trip reset. | BITMAP16 | Read | bit 0 = L tripped; bit 1 = S tripped; bit 2 = I tripped; bit 3 = G tripped | |||
| IR | 36doc 30037 | DO status | BITMAP16 | Read | bit 0 = DO1; bit 1 = DO2; bit 2 = DO3; bit 3 = DO4; bit 4 = DO5; bit 5 = DO6; bit 6 = DO7; bit 7 = DO8 | ||||
| IR | 100doc 30101 | RMS current phase 1 | Percent x 100 of In if nominal current is unknown. | UINT16 | A | Read | |||
| IR | 101doc 30102 | RMS current phase 2 | UINT16 | A | Read | ||||
| IR | 102doc 30103 | RMS current phase 3 | UINT16 | A | Read | ||||
| IR | 103doc 30104 | RMS current neutral | UINT16 | A | Read | ||||
| IR | 104doc 30105 | RMS current ground | UINT16 | A | Read | ||||
| IR | 106doc 30107 | Voltage V1-N | 0xFFFF = not available; needs VM210. | UINT16 | × 0.1 | V | Read | ||
| IR | 107doc 30108 | Voltage V2-N | UINT16 | × 0.1 | V | Read | |||
| IR | 108doc 30109 | Voltage V3-N | UINT16 | × 0.1 | V | Read | |||
| IR | 109doc 30110 | Voltage V12 | UINT16 | × 0.1 | V | Read | |||
| IR | 110doc 30111 | Voltage V23 | UINT16 | × 0.1 | V | Read | |||
| IR | 111doc 30112 | Voltage V31 | UINT16 | × 0.1 | V | Read | |||
| IR | 113doc 30114 | Active power phase 1 | 0x7FFFFFFF = not available. | INT32 | CDAB | × 0.1 | kW | Read | |
| IR | 115doc 30116 | Active power phase 2 | INT32 | CDAB | × 0.1 | kW | Read | ||
| IR | 117doc 30118 | Active power phase 3 | INT32 | CDAB | × 0.1 | kW | Read | ||
| IR | 119doc 30120 | Total active power | INT32 | CDAB | × 0.1 | kW | Read | ||
| IR | 121doc 30122 | Reactive power phase 1 | INT32 | CDAB | × 0.1 | kVAR | Read | ||
| IR | 123doc 30124 | Reactive power phase 2 | INT32 | CDAB | × 0.1 | kVAR | Read | ||
| IR | 125doc 30126 | Reactive power phase 3 | INT32 | CDAB | × 0.1 | kVAR | Read | ||
| IR | 127doc 30128 | Total reactive power | INT32 | CDAB | × 0.1 | kVAR | Read | ||
| IR | 129doc 30130 | Apparent power phase 1 | INT32 | CDAB | × 0.1 | kVA | Read | ||
| IR | 131doc 30132 | Apparent power phase 2 | INT32 | CDAB | × 0.1 | kVA | Read | ||
| IR | 133doc 30134 | Apparent power phase 3 | INT32 | CDAB | × 0.1 | kVA | Read | ||
| IR | 135doc 30136 | Total apparent power | INT32 | CDAB | × 0.1 | kVA | Read | ||
| IR | 138doc 30139 | Peak factor phase 1 | UINT16 | × 0.01 | Read | ||||
| IR | 142doc 30143 | Total power factor | Signed. | INT16 | × 0.01 | Read | |||
| IR | 143doc 30144 | Frequency | 0xFFFF when all voltages are below 80 V. | UINT16 | × 0.1 | Hz | Read | ||
| IR | 145doc 30146 | Positive active energy | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 147doc 30148 | Positive reactive energy | INT32 | CDAB | × 0.1 | kVARh | Read | ||
| IR | 149doc 30150 | Apparent energy | INT32 | CDAB | × 0.1 | kVAh | Read | ||
| IR | 151doc 30152 | Negative active energy | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 153doc 30154 | Negative reactive energy | INT32 | CDAB | × 0.1 | kVARh | Read | ||
| IR | 155doc 30156 | Max active power in 15 minutes | Highest 15-minute mean, stored. | INT32 | CDAB | × 0.1 | kW | Read | |
| IR | 200doc 30201 | Trip current phase 1 | Measured at the last trip. | UINT16 | A | Read | |||
| IR | 201doc 30202 | Trip current phase 2 | UINT16 | A | Read | ||||
| IR | 202doc 30203 | Trip current phase 3 | UINT16 | A | Read | ||||
| HR | 0doc 40001 | CB open command | Write 1 to open; remote mode only. | UINT16 | Write | 0 = No execution; 1 = Execute | |||
| HR | 2doc 40003 | CB close command | Write 1 to close; remote mode only. | UINT16 | Write | 0 = No execution; 1 = Execute | |||
| HR | 4doc 40005 | CB reset command | UINT16 | Write | 0 = No execution; 1 = Execute | ||||
| HR | 12doc 40013 | Trip reset command | UINT16 | Write | 0 = No execution; 1 = Execute | ||||
| HR | 22doc 40023 | Wink command | Flashes the trip unit LED. | UINT16 | Write | 0 = No execution; 1 = Execute | |||
| HR | 26doc 40027 | Reset communication statistics | UINT16 | Write | 0 = No execution; 1 = Execute |
Notes on this map
- The manual says double words are little-endian by word (least significant word first) and big-endian within each word, so 32-bit registers here are CDAB.
- Default communication parameters (address 247, 19200 baud, even parity, Standard addressing) apply until set with the Test Unit; they can only be changed locally.
- Currents read in amps once the nominal current is set; if 'Nominal current unknown' (status bit 13) is set they read as a percentage of In (150 = 1.5 In).
- Voltages, power, energy and frequency need the VM210 voltage module; without it they read 0.
- Commands run only in remote operating mode and one at a time. The remote signalling contact commands are left out because their hex addresses (0029h, 002Ah) do not match the absolute addresses 40041/40043.
- Read the currents as a 5-register block, not one at a time, as the manual asks.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB SACE Tmax PR223DS trip unit (Modbus RTU)
What Modbus registers does the ABB SACE Tmax PR223DS trip unit (Modbus RTU) have?
This map lists 47 registers: 41 input registers, 6 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB SACE Tmax PR223DS trip unit (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each register row gives the absolute address (30001/40001 style) and a 'Relative Address - 1 (HEX)' column that goes in the Modbus message (30101 = 0064h, 40001 = 0000h). This applies with the default 'Standard' addressing type.
What byte order does the ABB SACE Tmax PR223DS trip unit (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB SACE Tmax PR223DS trip unit (Modbus RTU)?
Start with IR 33 Status (CB open/closed/tripped, local/remote); IR 35 Trips (Which protection tripped); IR 100 RMS current phase 1 (Phase 1 current); IR 119 Total active power (Total active power); IR 145 Positive active energy (Active energy); HR 0 CB open command (Open command).
How do I enable Modbus control of the ABB SACE Tmax PR223DS trip unit (Modbus RTU)?
Modbus is built into the trip unit; address, baud, parity and addressing type are set locally with the ABB Test Unit. Remote commands need the trip unit in Remote mode (LOCAL/REMOTE button); CB open/close also fails if the motor operator selector is on MANUAL or the motor command is faulty.
Where is the official ABB SACE Tmax PR223DS trip unit (Modbus RTU) Modbus documentation?
The source is PR223DS Modbus System Interface - Instruction manual (1SDH000658R0001), published free by ABB at https://library.e.abb.com/public/dfe9aa822695b773c125780800716f6c/1SDH000658R0001.pdf.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332
Other power & energy meters register maps
- Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Energy meter (heat / cooling meter)
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Modbus RTU plug-in communication module (Sylop M/N 11024, firmware 1.0) in a Diehl SHARKY 775 compact heat meter or SCYLAR INT 8 calculator.
Also known as: SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI
All power & energy meters Modbus register maps →
Source: PR223DS Modbus System Interface - Instruction manual · 1SDH000658R0001. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.