- Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
Process controller (sensor / PID controller) · Modbus register map
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's Protronic and Digitric panel controllers expose their internal variables to a Modbus RTU master through an interface module. Global variables (analog inputs and outputs and the per-loop controller values) are 32-bit IEEE floats in pairs of holding registers starting at register 0; online parameters and binary I/O have their own ranges. This map covers the basic and slot-1 analog I/O plus the main setpoint, process value, deviation and output values of control loops 1-4.
This page lists 38 Modbus registers for the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
- Equipment type
- Process controller (sensor / PID controller)
- Registers
- 38 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Protronic 100, Protronic 500, Protronic 550, Digitric 500
Integration notes: ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
Read the loop values with function 03 as CDAB floats: process value at 164 (loop 1), active setpoint at 238, controller output at 184; add 150 per further loop. Analog inputs start at register 0.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 164 | Loop 1 process value (digital display) (.L1_XDIGI) | FLOAT32 CDAB | Loop 1 process value | Read |
| HR 238 | Loop 1 active setpoint (.L1_WW) | FLOAT32 CDAB | Loop 1 active setpoint | Read |
| HR 184 | Loop 1 PID output (.L1_PID_Y_OUT) | FLOAT32 CDAB | Loop 1 PID output | Read |
| HR 170 | Loop 1 control deviation (.L1_XW) | FLOAT32 CDAB | Loop 1 control deviation | Read |
| HR 0 | Basic device analog input 1 (.AE01) | FLOAT32 CDAB | Analog input 1 | Read |
Enable Modbus control & writes
Fit the RS-485 (or RS-232) interface module and set the station address and line settings on the controller; addresses 1-255 are allowed, 0 is broadcast.
Byte order & addressing
- REAL values are low word first (even register = low word).
- Always read or write both registers of a REAL together.
- Function 04 behaves like 03 and 02 like 01.
Network setup
- RS-485: up to 32 stations, cable under 1200 m, stubs under 0.3 m, electrically isolated; RS-232 for a single PC up to 10 m.
Watch out for
- Gaps in the register table (e.g. 60-69, 78-79) are unassigned.
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Basic device analog input 1 (.AE01) | FLOAT32 | CDAB | Read | ||||
| HR | 2 | Basic device analog input 2 (.AE02) | FLOAT32 | CDAB | Read | ||||
| HR | 4 | Slot 1 analog input 1 (.AE11) | FLOAT32 | CDAB | Read | ||||
| HR | 6 | Slot 1 analog input 2 (.AE12) | FLOAT32 | CDAB | Read | ||||
| HR | 8 | Slot 1 analog input 3 (.AE13) | FLOAT32 | CDAB | Read | ||||
| HR | 10 | Slot 1 analog input 4 (.AE14) | FLOAT32 | CDAB | Read | ||||
| HR | 70 | Basic device analog output 1 (.AA01) | FLOAT32 | CDAB | Read | ||||
| HR | 72 | Slot 1 analog output 1 (.AA11) | FLOAT32 | CDAB | Read | ||||
| HR | 74 | Slot 1 analog output 2 (.AA12) | FLOAT32 | CDAB | Read | ||||
| HR | 76 | Slot 1 analog output 3 (.AA13) | FLOAT32 | CDAB | Read | ||||
| HR | 160 | Loop 1 current setpoint (.L1_WAKT) | FLOAT32 | CDAB | Read | ||||
| HR | 164 | Loop 1 process value (digital display) (.L1_XDIGI) | FLOAT32 | CDAB | Read | ||||
| HR | 170 | Loop 1 control deviation (.L1_XW) | FLOAT32 | CDAB | Read | ||||
| HR | 184 | Loop 1 PID output (.L1_PID_Y_OUT) | FLOAT32 | CDAB | Read | ||||
| HR | 188 | Loop 1 control deviation in % (.L1_XW_PRZ) | FLOAT32 | CDAB | Read | ||||
| HR | 228 | Loop 1 computer setpoint (.L1_WCOMPUTER) | Setpoint given by a host computer. | FLOAT32 | CDAB | Read | |||
| HR | 238 | Loop 1 active setpoint (.L1_WW) | FLOAT32 | CDAB | Read | ||||
| HR | 310 | Loop 2 current setpoint (.L2_WAKT) | FLOAT32 | CDAB | Read | ||||
| HR | 314 | Loop 2 process value (digital display) (.L2_XDIGI) | FLOAT32 | CDAB | Read | ||||
| HR | 320 | Loop 2 control deviation (.L2_XW) | FLOAT32 | CDAB | Read | ||||
| HR | 334 | Loop 2 PID output (.L2_PID_Y_OUT) | FLOAT32 | CDAB | Read | ||||
| HR | 338 | Loop 2 control deviation in % (.L2_XW_PRZ) | FLOAT32 | CDAB | Read | ||||
| HR | 378 | Loop 2 computer setpoint (.L2_WCOMPUTER) | Setpoint given by a host computer. | FLOAT32 | CDAB | Read | |||
| HR | 388 | Loop 2 active setpoint (.L2_WW) | FLOAT32 | CDAB | Read | ||||
| HR | 460 | Loop 3 current setpoint (.L3_WAKT) | FLOAT32 | CDAB | Read | ||||
| HR | 464 | Loop 3 process value (digital display) (.L3_XDIGI) | FLOAT32 | CDAB | Read | ||||
| HR | 470 | Loop 3 control deviation (.L3_XW) | FLOAT32 | CDAB | Read | ||||
| HR | 484 | Loop 3 PID output (.L3_PID_Y_OUT) | FLOAT32 | CDAB | Read | ||||
| HR | 488 | Loop 3 control deviation in % (.L3_XW_PRZ) | FLOAT32 | CDAB | Read | ||||
| HR | 528 | Loop 3 computer setpoint (.L3_WCOMPUTER) | Setpoint given by a host computer. | FLOAT32 | CDAB | Read | |||
| HR | 538 | Loop 3 active setpoint (.L3_WW) | FLOAT32 | CDAB | Read | ||||
| HR | 610 | Loop 4 current setpoint (.L4_WAKT) | FLOAT32 | CDAB | Read | ||||
| HR | 614 | Loop 4 process value (digital display) (.L4_XDIGI) | FLOAT32 | CDAB | Read | ||||
| HR | 620 | Loop 4 control deviation (.L4_XW) | FLOAT32 | CDAB | Read | ||||
| HR | 634 | Loop 4 PID output (.L4_PID_Y_OUT) | FLOAT32 | CDAB | Read | ||||
| HR | 638 | Loop 4 control deviation in % (.L4_XW_PRZ) | FLOAT32 | CDAB | Read | ||||
| HR | 678 | Loop 4 computer setpoint (.L4_WCOMPUTER) | Setpoint given by a host computer. | FLOAT32 | CDAB | Read | |||
| HR | 688 | Loop 4 active setpoint (.L4_WW) | FLOAT32 | CDAB | Read |
Notes on this map
- Word order: with the pair-of-registers method the even register carries the low word and the next (odd) register the high word of the IEEE-754 REAL, so floats are CDAB.
- The same variables can also be read in a mantissa/exponent format by adding 2000 to the register number (FW 1.149 and later); that format is not listed.
- Values are in the engineering units configured in the controller, so no units are given.
- Loop variables repeat every 150 registers (loop 1 from 150, loop 2 from 300, loop 3 from 450, loop 4 from 600). Many more loop variables (constants, limits, PID parts, free variables) and analog I/O of slots 2-7 follow the same table and are not all listed.
- Online parameters sit at 10000-20000 (10000 + loop x 1000 + 2 x parameter number, e.g. loop 1 Kp = 11002). Register 900 accepts key-press codes for remote keyboard operation. Binary inputs/outputs are read as coils (e.g. BE01 from 151). These are not listed.
- The table does not mark which global variables are writable; all are listed read-only here. Writes use function 06 (two telegrams for a REAL) or 16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
What Modbus registers does the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) have?
This map lists 38 registers: 38 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed in decimal starting at 0 and go on the wire unchanged: the manual's example reads analog input AE01 from registers 0 and 1 with start address 00 00. Function 03 is preferred; function 04 returns the same data.
What byte order does the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)?
Start with HR 164 Loop 1 process value (digital display) (.L1_XDIGI) (Loop 1 process value); HR 238 Loop 1 active setpoint (.L1_WW) (Loop 1 active setpoint); HR 184 Loop 1 PID output (.L1_PID_Y_OUT) (Loop 1 PID output); HR 170 Loop 1 control deviation (.L1_XW) (Loop 1 control deviation); HR 0 Basic device analog input 1 (.AE01) (Analog input 1).
How do I enable Modbus control of the ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)?
Fit the RS-485 (or RS-232) interface module and set the station address and line settings on the controller; addresses 1-255 are allowed, 0 is broadcast.
Where is the official ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU) Modbus documentation?
The source is Protronic 100/500/550, Digitric 500 - MODBUS interface description (42/62-50040 EN Rev. 04), revision 2001-11, published free by ABB at https://library.e.abb.com/public/c125698f006840e9c1256b21003c16bd/42-62-50040-EN-04-11_01.pdf.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other temperature & process controllers register maps
- Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2
All temperature & process controllers Modbus register maps →
Source: Protronic 100/500/550, Digitric 500 - MODBUS interface description · 42/62-50040 EN Rev. 04 · rev. 2001-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.