Soft starter (motor control) · Modbus register map
ABB PSE softstarter (internal Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's compact PSE softstarters can be controlled over Modbus RTU through a small adaptor on their fieldbus port. Status comes as discrete inputs or one status word, measurements (currents, frequency, power factor, starts, run time) as 16-bit registers, and the motor is started and stopped through coils or a control word. Start/stop and protection settings are directly readable and writable as one register each. This map covers the full published register set.
This page lists 67 Modbus registers for the ABB PSE softstarter (internal Modbus RTU) — 29 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- PSE softstarter (internal Modbus RTU)
- Equipment type
- Soft starter (motor control)
- Registers
- 67 (29 writable)
- Transport
- Modbus RTU
- Default unit ID
- 255
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370
Integration notes: ABB PSE softstarter (internal Modbus RTU)
Set Fieldbus interface type = Modbus RTU and Fieldbus control = On on the softstarter, then write the control word 0400h with bit 5 (auto mode) and bit 2 (start), and poll 0300h status, 0202h-0204h phase currents and 2000h diagnostics.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1024 | Control word | BITMAP16 | Control word: start/stop/auto mode/reset | Read/write |
| IR 768 | Status word | BITMAP16 | Status word: running, fault, ready | Read |
| IR 514 | Phase current L1 | UINT16 | Phase current L1 | Read |
| IR 512 | Motor current in % of Ie | UINT16 | Motor current in % of Ie | Read |
| IR 513 | Thermal load | UINT16 | Thermal load | Read |
| IR 8192 | Diagnostic word 1 | BITMAP16 | Diagnostic word (faults/protections) | Read |
Enable Modbus control & writes
On the softstarter set Fieldbus interface type = internal Modbus RTU, Fieldbus control = On (Off for monitoring only), the internal Modbus RTU baud rate (9.6-76.8 kbaud) and frame format (8O1, 8E1, 8N2, 8N1), and the Fieldbus address (1-247).
Communication loss & watchdog
301Ch Internal Modbus RTU timeout (0.5-60.0 s, default 0.5 s) with 3019h Fieldbus fault reaction (Trip or Switch to local). A loss shows as fault EF40 and diagnostic bit 'Fieldbus fault'.
Byte order & addressing
- Addresses are hex protocol addresses sent as-is.
- Stop has priority over start, and both are ignored unless auto mode is set in exactly one place (coil 0105h or control word bit 5).
- The default comm timeout is only 0.5 s, so the master must poll continuously.
Network setup
- The Modbus RTU adaptor plugs into the PSE fieldbus connector; fit termination at both line ends.
- After writing 4064h (baud) the master must switch to the new rate to keep talking.
Watch out for
- Parameter writes fail while the motor is ramping; read 2003h for the reason and the parameter number.
- The motor may start unexpectedly when switching between fieldbus and hardwired control if a start signal is present.
ABB PSE softstarter (internal Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 257doc 0101h | Stop | Stops when set (priority over start); needs Auto mode coil. | BIT | Read/write | ||||
| CO | 258doc 0102h | Start | Starts when set; needs Auto mode coil. | BIT | Read/write | ||||
| CO | 261doc 0105h | Auto mode | Must be set for controlling the motor. | BIT | Read/write | ||||
| CO | 262doc 0106h | Fault reset | Resets an active fault or protection. | BIT | Read/write | ||||
| CO | 268doc 010Ch | Clear active diagnostics | Clears 2000h and 2003h. | BIT | Read/write | ||||
| DI | 1doc 0001h | Motor stopped status | 1 = motor stopped. | BIT | Read | ||||
| DI | 2doc 0002h | Run status | 1 = motor running. | BIT | Read | ||||
| DI | 5doc 0005h | Auto mode status | 1 = Modbus master control, 0 = local. | BIT | Read | ||||
| DI | 6doc 0006h | Fault status | 1 = one or more active faults. | BIT | Read | ||||
| DI | 11doc 000Bh | Start status | Hardwired DI Start input state. | BIT | Read | ||||
| DI | 12doc 000Ch | Stop status | Hardwired DI Stop input state. | BIT | Read | ||||
| DI | 13doc 000Dh | Reset status | Hardwired DI Reset input state. | BIT | Read | ||||
| DI | 14doc 000Eh | TOR status | 1 = top of ramp (bypass closed). | BIT | Read | ||||
| DI | 15doc 000Fh | Ready to start status | 1 = no fault and stable supply; a start will be accepted. | BIT | Read | ||||
| IR | 512doc 0200h | Motor current in % of Ie | 0-800 %. | UINT16 | % | Read | |||
| IR | 513doc 0201h | Thermal load | Percent of trip temperature (0-100 %). | UINT16 | % | Read | |||
| IR | 514doc 0202h | Phase current L1 | UINT16 | A | Read | ||||
| IR | 515doc 0203h | Phase current L2 | UINT16 | A | Read | ||||
| IR | 516doc 0204h | Phase current L3 | UINT16 | A | Read | ||||
| IR | 517doc 0205h | Max phase current | UINT16 | A | Read | ||||
| IR | 518doc 0206h | Measured frequency | UINT16 | Hz | Read | ||||
| IR | 519doc 0207h | Measured power factor | 100 = 1.00. | UINT16 | × 0.01 | Read | |||
| IR | 520doc 0208h | Output voltage | Percent of line voltage. | UINT16 | % | Read | |||
| IR | 521doc 0209h | Counted number of starts | 1 = 100 starts. | UINT16 | × 100 | starts | Read | ||
| IR | 522doc 020Ah | Run time | 1 = 10 hours. | UINT16 | × 10 | h | Read | ||
| IR | 523doc 020Bh | Modbus failure register | Last address that could not be read or written. | UINT16 | Read | ||||
| IR | 524doc 020Ch | Modbus toggle bit | Toggles on every read. | UINT16 | Read | ||||
| IR | 768doc 0300h | Status word | Same bits as the digital input telegram. | BITMAP16 | Read | bit 0 = Reserved; bit 1 = Motor stopped; bit 2 = Run status (running); bit 3 = Reserved; bit 4 = Reserved; bit 5 = Auto mode status (Modbus control); bit 6 = Fault status; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = DI Start active; bit 12 = DI Stop active; bit 13 = DI Reset active; bit 14 = TOR status (bypass closed); bit 15 = Ready to start | |||
| IR | 8192doc 2000h | Diagnostic word 1 | Active faults and protections. | BITMAP16 | Read | bit 0 = Reset possible on active event; bit 1 = Software fault; bit 2 = Shunt fault; bit 3 = By-pass open (does not close); bit 4 = Softstarter overload; bit 5 = Phase loss; bit 6 = Bad network quality; bit 7 = Current loss; bit 8 = Fieldbus fault; bit 9 = Low supply voltage; bit 10 = High current; bit 11 = Motor overload; bit 12 = Locked rotor protection; bit 13 = Underload protection; bit 14 = Reserved; bit 15 = Reserved | |||
| IR | 8195doc 2003h | Diagnostic word 4 | Parameter-write errors; bits 8-15 fault code (line number or parameter number). | BITMAP16 | Read | bit 4 = Parameter is read-only (last write failed); bit 5 = Parameter not settable now (e.g. during ramp); bit 6 = Parameter value out of range; bit 7 = Extended diagnostic available; bit 8 = Fault code bit 0; bit 9 = Fault code bit 1; bit 10 = Fault code bit 2; bit 11 = Fault code bit 3; bit 12 = Fault code bit 4; bit 13 = Fault code bit 5; bit 14 = Fault code bit 6; bit 15 = Fault code bit 7 | |||
| IR | 16431doc 402Fh | Modbus CRC error count | Resets at power cycle. | UINT16 | Read | ||||
| IR | 16432doc 4030h | Modbus slave exception count | Resets at power cycle. | UINT16 | Read | ||||
| IR | 16433doc 4031h | Modbus slave address | UINT16 | Read | |||||
| IR | 16434doc 4032h | Modbus baud rate (read) | Baud / 100, e.g. 192 = 19200. | UINT16 | × 100 | baud | Read | ||
| HR | 1024doc 0400h | Control word | Alternative to the coils; FC 06/16. | BITMAP16 | Read/write | bit 0 = Reserved; bit 1 = Stop (higher priority than start; needs auto mode); bit 2 = Start (needs auto mode); bit 3 = Reserved; bit 4 = Reserved; bit 5 = Auto mode (must be set to control the motor); bit 6 = Fault reset; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = Reserved; bit 12 = Clear active diagnostics (2000h, 2003h); bit 13 = Reserved; bit 14 = Reserved; bit 15 = Reserved | |||
| HR | 12288doc 3000h | Motor rated current (Ie) | Accepted range depends on unit size. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 12289doc 3001h | Start ramp time | 1-30 s, default 10. | UINT16 | s | Read/write | |||
| HR | 12290doc 3002h | Stop ramp on | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12291doc 3003h | Stop ramp time | 1-30 s, default 1. | UINT16 | s | Read/write | |||
| HR | 12292doc 3004h | Initial voltage | 30-70 %, default 40. | UINT16 | % | Read/write | |||
| HR | 12293doc 3005h | End voltage | 30-70 %, default 30. | UINT16 | % | Read/write | |||
| HR | 12294doc 3006h | Current limit | 1.5-7.0 x Ie, default 7.0. | UINT16 | × 0.1 | xIe | Read/write | ||
| HR | 12295doc 3007h | Torque control start | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12296doc 3008h | Torque control stop | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12297doc 3009h | Kick start on | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12298doc 300Ah | Kick start time | 0.1-1.0 s, default 0.2. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 12299doc 300Bh | Kick start voltage | 30-100 %, default 50. | UINT16 | % | Read/write | |||
| HR | 12300doc 300Ch | EOL protection on | Electronic overload; default 1. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12301doc 300Dh | EOL trip class | Default 1 (class 10). | UINT16 | Read/write | 0 = 10A; 1 = 10; 2 = 20; 3 = 30 | |||
| HR | 12302doc 300Eh | EOL protection reset type | Default 0. | UINT16 | Read/write | 0 = Hand; 1 = Auto | |||
| HR | 12303doc 300Fh | Underload protection on | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12304doc 3010h | Underload protection level | 0.2-1.0 x Ie, default 0.5. | UINT16 | × 0.1 | xIe | Read/write | ||
| HR | 12305doc 3011h | Underload protection reset type | Default 0. | UINT16 | Read/write | 0 = Hand; 1 = Auto | |||
| HR | 12306doc 3012h | Locked rotor protection on | Default 0. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 12307doc 3013h | Locked rotor protection level | 0.5-7.0 x Ie, default 1.2. | UINT16 | × 0.1 | xIe | Read/write | ||
| HR | 12308doc 3014h | Locked rotor protection reset type | Default 0. | UINT16 | Read/write | 0 = Hand; 1 = Auto | |||
| HR | 12309doc 3015h | Bad network fault reset type | Default 0. | UINT16 | Read/write | 0 = Hand; 1 = Auto | |||
| HR | 12310doc 3016h | Fieldbus control enabled | Read only over Modbus. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 12311doc 3017h | Fieldbus address | 0-255, default 255; read only over Modbus. | UINT16 | Read | ||||
| HR | 12312doc 3018h | Fieldbus download parameter | Read only over Modbus. | UINT16 | Read | 0 = dPOff; 1 = dPOn | |||
| HR | 12313doc 3019h | Fieldbus fault reaction | Read only over Modbus. | UINT16 | Read | 0 = Trip; 1 = Switch to local | |||
| HR | 12314doc 301Ah | Fieldbus fault reset type | Read only over Modbus. | UINT16 | Read | 0 = Hand; 1 = Auto | |||
| HR | 12315doc 301Bh | Fieldbus interface type | Read only over Modbus. | UINT16 | Read | 0 = Fieldbus plug; 1 = Modbus RTU | |||
| HR | 12316doc 301Ch | Internal Modbus RTU timeout | 0.5-60.0 s, default 0.5; read only over Modbus. | UINT16 | × 0.1 | s | Read | ||
| HR | 12317doc 301Dh | Internal Modbus RTU baud rate | Read only over Modbus; default 1. | UINT16 | Read | 0 = 9600; 1 = 19200; 2 = 38400; 3 = 57600; 4 = 76800 | |||
| HR | 12318doc 301Eh | Internal Modbus RTU frame format | Read only over Modbus; default 1. | UINT16 | Read | 0 = 8O1; 1 = 8E1; 2 = 8N2; 3 = 8N1 | |||
| HR | 16484doc 4064h | Fieldbus baud rate (write) | Baud / 100; master must follow after a change. | UINT16 | × 100 | baud | Read/write |
Notes on this map
- This copy is hosted by the US distributor Precision Electric; it is the unaltered ABB document (ABB footer, document ID 1SFC132367M0201 Rev B). ABB's online library did not return a copy for this document ID.
- All values are 16-bit. Read-only data blocks (status word, analog inputs, diagnostics, Modbus diagnostics) answer both function 03 and 04; they are listed as input registers here. The digital input telegram answers function 01 or 02 and is listed as discrete inputs; the output coils can be read back with 01/02.
- Scaling follows the manual's 'Value = 1 => ...' column: power factor 100 = 1, number of starts 1 = 100 starts, run time 1 = 10 h.
- Defaults: unit_id 255 is the parameter-list default of 3017h Fieldbus address (the manual's examples use 47); baud 19200 and 8E1 are the defaults of 301Dh/301Eh.
- Parameters 3016h-301Eh are read-only over Modbus; set them on the softstarter. 4064h lets the master change the baud rate.
- Left out: 2001h and 2002h (all bits reserved), the identification strings at 4000h-4017h (vendor, product code, revision, URL, product name; byte order of the text is not stated) and the reserved blocks. Function 43 (2Bh) Read Device Identification is also supported.
- Start/stop can come from coils 0101h/0102h (with auto mode on coil 0105h) or from bits 1/2 of the control word (with auto mode in bit 5). Setting auto mode in both places makes the device ignore start/stop.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB PSE softstarter (internal Modbus RTU)
What Modbus registers does the ABB PSE softstarter (internal Modbus RTU) have?
This map lists 67 registers: 5 coils, 9 discrete inputs, 20 input registers, 33 holding registers. 29 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB PSE softstarter (internal Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses are printed as hex protocol addresses and go on the wire unchanged; the manual's example frames send 0000h (coils), 0100h, 0202h, 2000h and 3007h exactly as listed. So 0202h is requested as 514 decimal.
What are the minimum Modbus registers to integrate the ABB PSE softstarter (internal Modbus RTU)?
Start with HR 1024 Control word (Control word: start/stop/auto mode/reset); IR 768 Status word (Status word: running, fault, ready); IR 514 Phase current L1 (Phase current L1); IR 512 Motor current in % of Ie (Motor current in % of Ie); IR 513 Thermal load (Thermal load); IR 8192 Diagnostic word 1 (Diagnostic word (faults/protections)).
How do I enable Modbus control of the ABB PSE softstarter (internal Modbus RTU)?
On the softstarter set Fieldbus interface type = internal Modbus RTU, Fieldbus control = On (Off for monitoring only), the internal Modbus RTU baud rate (9.6-76.8 kbaud) and frame format (8O1, 8E1, 8N2, 8N1), and the Fieldbus address (1-247).
What happens when the ABB PSE softstarter (internal Modbus RTU) loses Modbus communication?
301Ch Internal Modbus RTU timeout (0.5-60.0 s, default 0.5 s) with 3019h Fieldbus fault reaction (Trip or Switch to local). A loss shows as fault EF40 and diagnostic bit 'Fieldbus fault'.
Where is the official ABB PSE softstarter (internal Modbus RTU) Modbus documentation?
The source is Softstarter type PSE - Fieldbus Communication, Internal Modbus RTU (1SFC132367M0201 Rev B), revision 2019-12-18. ABB doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/11/PSE18-370-Fieldbus-Communication-Internal-Modbus-RTU-PSE.pdf. It may be an older revision, so check it against the live unit.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other soft starters & protection relays register maps
- Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042
All soft starters & protection relays Modbus register maps →
Source: Softstarter type PSE - Fieldbus Communication, Internal Modbus RTU · 1SFC132367M0201 Rev B · rev. 2019-12-18 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.