Easy Modbus
  1. Home
  2. Modbus register maps
  3. Siemens
  4. Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)

Protection relay · Modbus register map

Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The 7SR10 is a compact non-directional overcurrent and earth-fault protection relay with an RS-485 port that can run IEC 60870-5-103, Modbus RTU or DNP3. Under Modbus, commands are coils, protection and status indications are discrete inputs, and measurands are input registers. This map covers the default point list: binary outputs, control commands, protection elements, voltages, currents, frequency, power factor, maximum demand, fault values, counters and status bit strings.

This page lists 426 Modbus registers for the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) — 51 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Equipment type
Protection relay
Registers
426 (51 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004
Source document
Reyrolle 7SR10 Communication Protocols Manual (IEC 60870-5-103, Modbus RTU, DNP3) · C53000-L7040-C002-7 · rev. 2025-11 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)

Integration in brief

Set COM1-RS485 Protocol to Modbus RTU and give the relay a station address, then read input registers (FC 04) from 30010 for voltages and 30064 for currents; values are 32-bit integers with 3 decimals, high word first. Protection pickups and trips are discrete inputs (FC 02); commands are coils (FC 05).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 63I Primary aINT32 ABCDPrimary current phase aRead
IR 65I Primary bINT32 ABCDPrimary current phase bRead
IR 67I Primary cINT32 ABCDPrimary current phase cRead
IR 59FrequencyINT32 ABCDFrequencyRead
DI 109General TripBITGeneral tripRead
CO 108CB 1BITCB 1 control pointRead/write

Enable Modbus control & writes

In the Communications menu set COM1-RS485 Protocol = Modbus RTU (factory default is IEC 60870-5-103), then the station address (1-247), baud rate (default 19200) and parity (default even). Remote control needs the port mode to be Remote (default).

Byte order & addressing

Network setup

Watch out for

Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

426 of 426 shown
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Binary output 1BITRead/write
CO1doc 00002Binary output 2BITRead/write
CO2doc 00003Binary output 3BITRead/write
CO3doc 00004Binary output 4BITRead/write
CO4doc 00005Binary output 5BITRead/write
CO5doc 00006Binary output 6BITRead/write
CO99doc 00100LED resetBITWrite
CO100doc 00101Setting G1 selectedBITRead/write
CO101doc 00102Setting G2 selectedBITRead/write
CO102doc 00103Setting G3 selectedBITRead/write
CO103doc 00104Setting G4 selectedBITRead/write
CO108doc 00109CB 1BITRead/write
CO109doc 00110CB 1 Trip and RecloseBITRead/write
CO110doc 00111CB 1 Trip and LockoutBITRead/write
CO111doc 00112Auto-reclose activeBITRead/write
CO112doc 00113HotLine WorkingBITRead/write
CO113doc 00114E/F OutBITRead/write
CO114doc 00115SEF OutBITRead/write
CO115doc 00116Inst Protection OutBITRead/write
CO117doc 00118Reset CB Total Trip CountBITRead/write
CO118doc 00119Reset CB Delta Trip CountBITRead/write
CO119doc 00120Reset CB Count To AR BlockBITRead/write
CO120doc 00121Reset CB Frequent Ops CountBITRead/write
CO122doc 00123Reset I^2t CB WearBITRead/write
CO125doc 00126Demand metering resetBITRead/write
CO153doc 00154Reset Energy MetersBITRead/write
CO154doc 00155Remote modeBITRead/write
CO155doc 00156Out of Service ModeBITRead/write
CO156doc 00157Local modeBITRead/write
CO157doc 00158Local and RemoteBITRead/write
CO164doc 00165Reset Start CountBITRead/write
CO179doc 00180CB 1 OpenedBITRead/write
CO180doc 00181CB 1 ClosedBITRead/write
CO199doc 00200User SP Command 1BITRead/write
CO200doc 00201User SP Command 2BITRead/write
CO201doc 00202User SP Command 3BITRead/write
CO202doc 00203User SP Command 4BITRead/write
CO203doc 00204User SP Command 5BITRead/write
CO204doc 00205User SP Command 6BITRead/write
CO205doc 00206User SP Command 7BITRead/write
CO206doc 00207User SP Command 8BITRead/write
CO207doc 00208User DP Command 1BITRead/write
CO208doc 00209User DP Command 2BITRead/write
CO209doc 00210User DP Command 3BITRead/write
CO210doc 00211User DP Command 4BITRead/write
CO211doc 00212User DP Command 5BITRead/write
CO212doc 00213User DP Command 6BITRead/write
CO213doc 00214User DP Command 7BITRead/write
CO214doc 00215User DP Command 8BITRead/write
CO225doc 00226Block 27/59BITRead/write
CO226doc 00227Cmd TripBITRead/write
DI0doc 10001Binary Input 1BITRead
DI1doc 10002Binary Input 2BITRead
DI2doc 10003Binary Input 3BITRead
DI3doc 10004Binary Input 4BITRead
DI4doc 10005Binary Input 5BITRead
DI5doc 10006Binary Input 6BITRead
DI6doc 10007Binary Input 7BITRead
DI7doc 10008Binary Input 8BITRead
DI8doc 10009Binary Input 9BITRead
DI101doc 10102Remote ModeBITRead
DI102doc 10103Out Of Service ModeBITRead
DI103doc 10104Local ModeBITRead
DI104doc 10105Local & RemoteBITRead
DI109doc 10110General TripBITRead
DI110doc 10111Trip Circuit FailBITRead
DI111doc 10112Start/Pick-up L1BITRead
DI112doc 10113Start/Pick-up L2BITRead
DI113doc 10114Start/Pick-up L3BITRead
DI114doc 10115General Start/Pick-upBITRead
DI115doc 10116VT Fuse FailureBITRead
DI116doc 10117Earth Fault Forward/LineBITRead
DI117doc 10118Earth Fault Reverse/BusbarBITRead
DI118doc 10119Start/Pick-up NBITRead
DI119doc 10120Fault Forward/LineBITRead
DI120doc 10121Fault Reverse/BusbarBITRead
DI121doc 1012251-1BITRead
DI122doc 1012350-1BITRead
DI123doc 1012451N-1BITRead
DI124doc 1012550N-1BITRead
DI125doc 1012651G-1BITRead
DI126doc 1012750G-1BITRead
DI127doc 1012851-2BITRead
DI128doc 1012950-2BITRead
DI129doc 1013051N-2BITRead
DI130doc 1013150N-2BITRead
DI131doc 1013251G-2BITRead
DI132doc 1013350G-2BITRead
DI133doc 1013451-3BITRead
DI134doc 1013550-3BITRead
DI135doc 1013651N-3BITRead
DI136doc 1013750N-3BITRead
DI137doc 1013851G-3BITRead
DI138doc 1013950G-3BITRead
DI139doc 1014051-4BITRead
DI140doc 1014150-4BITRead
DI141doc 1014251N-4BITRead
DI142doc 1014350N-4BITRead
DI143doc 1014451G-4BITRead
DI144doc 1014550G-4BITRead
DI145doc 1014650BF Stage 2BITRead
DI146doc 1014749-AlarmBITRead
DI147doc 1014849-TripBITRead
DI148doc 1014960 CTSBITRead
DI149doc 1015046ITBITRead
DI150doc 1015146DTBITRead
DI151doc 1015247-1BITRead
DI152doc 1015347-2BITRead
DI153doc 1015446BCBITRead
DI154doc 1015527/59-1BITRead
DI155doc 1015627/59-2BITRead
DI156doc 1015727/59-3BITRead
DI157doc 1015827/59-4BITRead
DI158doc 1015959NITBITRead
DI159doc 1016059NDTBITRead
DI160doc 1016181-1BITRead
DI161doc 1016281-2BITRead
DI162doc 1016381-3BITRead
DI163doc 1016481-4BITRead
DI166doc 1016764HBITRead
DI167doc 1016837-1BITRead
DI168doc 1016937-2BITRead
DI170doc 10171Auto-reclose activeBITRead
DI171doc 10172CB on by auto recloseBITRead
DI172doc 10173ReclaimBITRead
DI173doc 10174LockoutBITRead
DI174doc 10175HotLine WorkingBITRead
DI175doc 10176Inst Protection OutBITRead
DI176doc 10177CB Total Trip CountBITRead
DI177doc 10178CB Delta Trip CountBITRead
DI178doc 10179CB Count To AR BlockBITRead
DI179doc 10180I^2t CB WearBITRead
DI180doc 1018179 AR In progressBITRead
DI181doc 10182Cold Load ActiveBITRead
DI182doc 10183E/F OutBITRead
DI183doc 10184P/F Inst Protection InhibitedBITRead
DI184doc 10185E/F Inst Protection InhibitedBITRead
DI185doc 10186SEF Inst Protection InhibitedBITRead
DI186doc 10187Ext Inst Protection InhibitedBITRead
DI201doc 1020251SEF-1BITRead
DI202doc 1020350SEF-1BITRead
DI203doc 1020451SEF-2BITRead
DI204doc 1020550SEF-2BITRead
DI205doc 1020651SEF-3BITRead
DI206doc 1020750SEF-3BITRead
DI207doc 1020851SEF-4BITRead
DI208doc 1020950SEF-4BITRead
DI209doc 10210SEF OutBITRead
DI210doc 10211Trip Circuit Fail 1BITRead
DI211doc 10212Trip Circuit Fail 2BITRead
DI212doc 10213Trip Circuit Fail 3BITRead
DI213doc 10214CB Total Trip CountBITRead
DI214doc 10215CB Delta Trip CountBITRead
DI215doc 10216CB Count To AR BlockBITRead
DI216doc 10217CB Frequent Ops CountBITRead
DI217doc 10218I^2t CB WearBITRead
DI218doc 10219CB 1 OpenedBITRead
DI219doc 10220CB 1 ClosedBITRead
DI282doc 10283Close Circuit Fail 1BITRead
DI283doc 10284Close Circuit Fail 2BITRead
DI284doc 10285Close Circuit Fail 3BITRead
DI285doc 10286Close Circuit FailBITRead
DI287doc 10288SEF Forward/LineBITRead
DI288doc 10289SEF Reverse/BusbarBITRead
DI289doc 10290General Alarm 1BITRead
DI290doc 10291General Alarm 2BITRead
DI291doc 10292General Alarm 3BITRead
DI292doc 10293General Alarm 4BITRead
DI293doc 10294General Alarm 5BITRead
DI294doc 10295General Alarm 6BITRead
DI301doc 10302Quick Logic E1BITRead
DI302doc 10303Quick Logic E2BITRead
DI303doc 10304Quick Logic E3BITRead
DI304doc 10305Quick Logic E4BITRead
DI333doc 1033460 CTS-IBITRead
DI334doc 1033581HBL2BITRead
DI335doc 1033637G-1BITRead
DI336doc 1033737G-2BITRead
DI337doc 1033837SEF-1BITRead
DI338doc 1033937SEF-2BITRead
DI366doc 1036750BF Stage 1BITRead
DI367doc 10368Wattmetric Po>BITRead
DI368doc 1036937-PhABITRead
DI369doc 1037037-PhBBITRead
DI370doc 1037137-PhCBITRead
DI371doc 1037250 LC-1BITRead
DI372doc 1037350 LC-2BITRead
DI373doc 1037450G LC-1BITRead
DI374doc 1037550G LC-2BITRead
DI375doc 1037650SEF LC-1BITRead
DI376doc 1037750SEF LC-2BITRead
DI377doc 1037850BF-PhABITRead
DI378doc 1037950BF-PhBBITRead
DI379doc 1038050BF-PhCBITRead
DI380doc 1038150BF-EFBITRead
DI382doc 1038360 CTS-I-PhABITRead
DI383doc 1038460 CTS-I-PhBBITRead
DI384doc 1038560 CTS-I-PhCBITRead
DI389doc 10390Trip PhABITRead
DI390doc 10391Trip PhBBITRead
DI391doc 10392Trip PhCBITRead
DI400doc 1040127/59 PhABITRead
DI401doc 1040227/59 PhBBITRead
DI402doc 1040327/59 PhCBITRead
DI409doc 10410CB AlarmBITRead
DI430doc 1043167SEF-1BITRead
DI431doc 1043267SEF-2BITRead
DI500doc 10501Virtual Input 1BITRead
DI501doc 10502Virtual Input 2BITRead
DI502doc 10503Virtual Input 3BITRead
DI503doc 10504Virtual Input 4BITRead
DI504doc 10505Virtual Input 5BITRead
DI505doc 10506Virtual Input 6BITRead
DI506doc 10507Virtual Input 7BITRead
DI507doc 10508Virtual Input 8BITRead
DI600doc 10601LED 1BITRead
DI601doc 10602LED 2BITRead
DI602doc 10603LED 3BITRead
DI603doc 10604LED 4BITRead
DI604doc 10605LED 5BITRead
DI605doc 10606LED 6BITRead
DI606doc 10607LED 7BITRead
DI607doc 10608LED 8BITRead
DI608doc 10609LED 9BITRead
DI700doc 10701LED PU 1BITRead
DI701doc 10702LED PU 2BITRead
DI702doc 10703LED PU 3BITRead
DI703doc 10704LED PU 4BITRead
DI704doc 10705LED PU 5BITRead
DI705doc 10706LED PU 6BITRead
DI706doc 10707LED PU 7BITRead
DI707doc 10708LED PU 8BITRead
DI708doc 10709LED PU 9BITRead
DI799doc 10800Cold StartBITRead
DI801doc 10802Re-StartBITRead
DI802doc 10803Power OnBITRead
DI803doc 10804Expected RestartBITRead
DI804doc 10805Unexpected RestartBITRead
DI805doc 10806Reset Start CountBITRead
DI899doc 10900User SP Command 1BITRead
DI900doc 10901User SP Command 2BITRead
DI901doc 10902User SP Command 3BITRead
DI902doc 10903User SP Command 4BITRead
DI903doc 10904User SP Command 5BITRead
DI904doc 10905User SP Command 6BITRead
DI905doc 10906User SP Command 7BITRead
DI906doc 10907User SP Command 8BITRead
DI907doc 10908User DP Command 1BITRead
DI908doc 10909User DP Command 2BITRead
DI909doc 10910User DP Command 3BITRead
DI910doc 10911User DP Command 4BITRead
DI911doc 10912User DP Command 5BITRead
DI912doc 10913User DP Command 6BITRead
DI913doc 10914User DP Command 7BITRead
DI914doc 10915User DP Command 8BITRead
DI915doc 1091632-1BITRead
DI916doc 1091732-2BITRead
DI917doc 1091832S-1BITRead
DI918doc 1091932S-2BITRead
DI919doc 1092055-1BITRead
DI920doc 1092155-2BITRead
DI1072doc 11073CB DBIBITRead
DI1073doc 11074CB TravellingBITRead
DI1074doc 11075Close CB FailedBITRead
DI1075doc 11076Open CB FailedBITRead
DI1076doc 11077Start Count AlarmBITRead
DI1077doc 1107850AFD PhABITRead
DI1078doc 1107950AFD PhBBITRead
DI1079doc 1108050AFD PhCBITRead
DI1080doc 1108150AFDBITRead
DI1081doc 11082AFD Zone 1 FlashBITRead
DI1082doc 11083AFD Zone 1BITRead
DI1083doc 11084AFD Zone 2 FlashBITRead
DI1084doc 11085AFD Zone 2BITRead
DI1085doc 11086AFD Zone 3 FlashBITRead
DI1086doc 11087AFD Zone 3BITRead
DI1087doc 11088AFD Zone 4 FlashBITRead
DI1088doc 11089AFD Zone 4BITRead
DI1089doc 11090AFD Zone 5 FlashBITRead
DI1090doc 11091AFD Zone 5BITRead
DI1091doc 11092AFD Zone 6 FlashBITRead
DI1092doc 11093AFD Zone 6BITRead
DI1117doc 1111881I-THDBITRead
DI1119doc 1112059.S1BITRead
DI1120doc 1112159.S2BITRead
DI1121doc 1112227.S1BITRead
DI1122doc 1112327.S2BITRead
DI1123doc 1112459V0BITRead
DI1124doc 1112559 PhABBITRead
DI1125doc 1112659 PhBCBITRead
DI1126doc 1112759 PhCABITRead
DI1127doc 1112827 PhABBITRead
DI1128doc 1112927 PhBCBITRead
DI1129doc 1113027 PhCABITRead
DI1130doc 1113159V0 PickupBITRead
DI1131doc 1113281V 59V2 PickupBITRead
DI1132doc 1113381V 27V1 PickupBITRead
DI1133doc 1113481.S1 O/FBITRead
DI1134doc 1113581.S1 U/FBITRead
DI1135doc 1113681.S2 O/FBITRead
DI1136doc 1113781.S2 U/FBITRead
DI1137doc 1113881V UnblockBITRead
DI1138doc 11139PI TripBITRead
DI1139doc 11140Loc 81V EnBITRead
DI1140doc 11141DDI OpenBITRead
IR0doc 30001Event countNumber of events in the relay's event buffer.INT16Read
IR9doc 30010V Primary abFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR11doc 30012V Primary bcFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR13doc 30014V Primary caFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR15doc 30016V Primary aFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR17doc 30018V Primary bFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR19doc 30020V Primary cFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR21doc 30022V Secondary aFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR23doc 30024V Secondary bFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR25doc 30026V Secondary cFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR33doc 30034V Nominal ab angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR35doc 30036V Nominal bc angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR37doc 30038V Nominal ca angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR39doc 30040V Nominal a angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR41doc 30042V Nominal b angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR43doc 30044V Nominal c angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR47doc 30048V zpsFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR49doc 30050V ppsFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR51doc 30052V npsFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR53doc 30054V zps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR55doc 30056V pps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR57doc 30058V nps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR59doc 30060FrequencyFixed point, 3 decimals.INT32ABCD× 0.001HzRead
IR63doc 30064I Primary aFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR65doc 30066I Primary bFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR67doc 30068I Primary cFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR69doc 30070I Secondary aFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR71doc 30072I Secondary bFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR73doc 30074I Secondary cFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR75doc 30076I Nominal a (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR77doc 30078I Nominal b (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR79doc 30080I Nominal c (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR81doc 30082I Nominal a angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR83doc 30084I Nominal b angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR85doc 30086I Nominal c angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR87doc 30088I Primary nFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR89doc 30090I Secondary nFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR91doc 30092I Nominal n (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInomRead
IR93doc 30094I Primary gFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR95doc 30096I Secondary gFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR97doc 30098I Nominal g (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInomRead
IR99doc 30100I Nominal zps (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR101doc 30102I Nominal pps (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR103doc 30104I Nominal nps (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInRead
IR105doc 30106I Nominal zps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR107doc 30108I Nominal pps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR109doc 30110I Nominal nps angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR135doc 30136Power Factor AFixed point, 3 decimals.INT32ABCD× 0.001Read
IR137doc 30138Power Factor BFixed point, 3 decimals.INT32ABCD× 0.001Read
IR139doc 30140Power Factor CFixed point, 3 decimals.INT32ABCD× 0.001Read
IR141doc 30142Power Factor(3P)Fixed point, 3 decimals.INT32ABCD× 0.001Read
IR151doc 30152Thermal Status Ph AINT16%Read
IR152doc 30153Thermal Status Ph BINT16%Read
IR153doc 30154Thermal Status Ph CINT16%Read
IR166doc 30167Fault RecordsINT16Read
IR167doc 30168Event RecordsINT16Read
IR168doc 30169Waveform RecordsINT16Read
IR169doc 30170V Secondary abFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR171doc 30172V Secondary bcFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR173doc 30174V Secondary caFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR175doc 30176V Primary nFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR177doc 30178V Secondary nFixed point, 3 decimals.INT32ABCD× 0.001VRead
IR179doc 30180V Secondary n angleFixed point, 3 decimals.INT32ABCD× 0.001°Read
IR192doc 30193I Phase A MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR194doc 30195I Phase B MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR196doc 30197I Phase C MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR206doc 30207I Primary sefFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR208doc 30209I Secondary sefFixed point, 3 decimals.INT32ABCD× 0.001ARead
IR210doc 30211I Nominal sef (multiple of rated current)Fixed point, 3 decimals.INT32ABCD× 0.001xInomRead
IR240doc 30241CB Total Trip Count32-bit integer.INT32ABCDRead
IR242doc 30243CB Delta Trip Count32-bit integer.INT32ABCDRead
IR244doc 30245CB Count To AR Block32-bit integer.INT32ABCDRead
IR246doc 30247CB Frequent Ops Count32-bit integer.INT32ABCDRead
IR300doc 30301I Last Trip aFixed point, 3 decimals.INT32ABCD× 0.001Read
IR302doc 30303I Last Trip bFixed point, 3 decimals.INT32ABCD× 0.001Read
IR304doc 30305I Last Trip cFixed point, 3 decimals.INT32ABCD× 0.001Read
IR306doc 30307V Last Trip aFixed point, 3 decimals.INT32ABCD× 0.001Read
IR308doc 30309V Last Trip bFixed point, 3 decimals.INT32ABCD× 0.001Read
IR310doc 30311V Last Trip cFixed point, 3 decimals.INT32ABCD× 0.001Read
IR312doc 30313I Last Trip nFixed point, 3 decimals.INT32ABCD× 0.001Read
IR314doc 30315I Last Trip gFixed point, 3 decimals.INT32ABCD× 0.001Read
IR316doc 30317I Last Trip sefFixed point, 3 decimals.INT32ABCD× 0.001Read
IR318doc 30319V Phase A MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR320doc 30321V Phase B MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR322doc 30323V Phase C MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR324doc 30325V Phase AB MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR326doc 30327V Phase BC MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR328doc 30329V Phase CA MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR340doc 30341Led 1-16 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Led 1; bit 1 = Led 2; bit 2 = Led 3; bit 3 = Led 4; bit 4 = Led 5; bit 5 = Led 6; bit 6 = Led 7; bit 7 = Led 8; bit 8 = Led 9; bit 9 = Led 10; bit 10 = Led 11; bit 11 = Led 12; bit 12 = Led 13; bit 13 = Led 14; bit 14 = Led 15; bit 15 = Led 16
IR341doc 30342Led 17-32 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Led 17; bit 1 = Led 18; bit 2 = Led 19; bit 3 = Led 20; bit 4 = Led 21; bit 5 = Led 22; bit 6 = Led 23; bit 7 = Led 24; bit 8 = Led 25; bit 9 = Led 26; bit 10 = Led 27; bit 11 = Led 28; bit 12 = Led 29; bit 13 = Led 30; bit 14 = Led 31; bit 15 = Led 32
IR342doc 30343Input 1-16 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16
IR343doc 30344Input 17-32 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Input 17; bit 1 = Input 18; bit 2 = Input 19; bit 3 = Input 20; bit 4 = Input 21; bit 5 = Input 22; bit 6 = Input 23; bit 7 = Input 24; bit 8 = Input 25; bit 9 = Input 26; bit 10 = Input 27; bit 11 = Input 28; bit 12 = Input 29; bit 13 = Input 30; bit 14 = Input 31; bit 15 = Input 32
IR344doc 30345Output 1-16 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8; bit 8 = Output 9; bit 9 = Output 10; bit 10 = Output 11; bit 11 = Output 12; bit 12 = Output 13; bit 13 = Output 14; bit 14 = Output 15; bit 15 = Output 16
IR345doc 30346Output 17-32 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Output 17; bit 1 = Output 18; bit 2 = Output 19; bit 3 = Output 20; bit 4 = Output 21; bit 5 = Output 22; bit 6 = Output 23; bit 7 = Output 24; bit 8 = Output 25; bit 9 = Output 26; bit 10 = Output 27; bit 11 = Output 28; bit 12 = Output 29; bit 13 = Output 30; bit 14 = Output 31; bit 15 = Output 32
IR346doc 30347Virtual 1-16 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Virtual 1; bit 1 = Virtual 2; bit 2 = Virtual 3; bit 3 = Virtual 4; bit 4 = Virtual 5; bit 5 = Virtual 6; bit 6 = Virtual 7; bit 7 = Virtual 8; bit 8 = Virtual 9; bit 9 = Virtual 10; bit 10 = Virtual 11; bit 11 = Virtual 12; bit 12 = Virtual 13; bit 13 = Virtual 14; bit 14 = Virtual 15; bit 15 = Virtual 16
IR347doc 30348Virtual 17-32 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Virtual 17; bit 1 = Virtual 18; bit 2 = Virtual 19; bit 3 = Virtual 20; bit 4 = Virtual 21; bit 5 = Virtual 22; bit 6 = Virtual 23; bit 7 = Virtual 24; bit 8 = Virtual 25; bit 9 = Virtual 26; bit 10 = Virtual 27; bit 11 = Virtual 28; bit 12 = Virtual 29; bit 13 = Virtual 30; bit 14 = Virtual 31; bit 15 = Virtual 32
IR348doc 30349Equation 1-16 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Equation 1; bit 1 = Equation 2; bit 2 = Equation 3; bit 3 = Equation 4; bit 4 = Equation 5; bit 5 = Equation 6; bit 6 = Equation 7; bit 7 = Equation 8; bit 8 = Equation 9; bit 9 = Equation 10; bit 10 = Equation 11; bit 11 = Equation 12; bit 12 = Equation 13; bit 13 = Equation 14; bit 14 = Equation 15; bit 15 = Equation 16
IR349doc 30350Equation 17-32 statusFirst item in bit 0 (LSB).BITMAP16Readbit 0 = Equation 17; bit 1 = Equation 18; bit 2 = Equation 19; bit 3 = Equation 20; bit 4 = Equation 21; bit 5 = Equation 22; bit 6 = Equation 23; bit 7 = Equation 24; bit 8 = Equation 25; bit 9 = Equation 26; bit 10 = Equation 27; bit 11 = Equation 28; bit 12 = Equation 29; bit 13 = Equation 30; bit 14 = Equation 31; bit 15 = Equation 32
IR359doc 30360CB Wear A RemainingFixed point, 3 decimals.INT32ABCD× 0.001Read
IR361doc 30362CB Wear B RemainingFixed point, 3 decimals.INT32ABCD× 0.001Read
IR363doc 30364CB Wear C RemainingFixed point, 3 decimals.INT32ABCD× 0.001Read
IR365doc 30366CB Wear MinimumFixed point, 3 decimals.INT32ABCD× 0.001Read
IR379doc 30380StartCountFixed point, 3 decimals.INT32ABCD× 0.001Read
IR381doc 30382Start Count TargetFixed point, 3 decimals.INT32ABCD× 0.001Read
IR389doc 30390Freq Last TripFixed point, 3 decimals.INT32ABCD× 0.001Read
IR391doc 30392Active Setting GroupINT16Read
IR399doc 30400Frequency MaxFixed point, 3 decimals.INT32ABCD× 0.001Read
IR467doc 30468CB Trip Time MeterFixed point, 3 decimals.INT32ABCD× 0.001Read
IR483doc 30484AFDZone1Count32-bit integer.INT32ABCDRead
IR485doc 30486AFDZone2Count32-bit integer.INT32ABCDRead
IR487doc 30488AFDZone3Count32-bit integer.INT32ABCDRead
IR489doc 30490AFDZone4Count32-bit integer.INT32ABCDRead
IR491doc 30492AFDZone5Count32-bit integer.INT32ABCDRead
IR493doc 30494AFDZone6Count32-bit integer.INT32ABCDRead
IR495doc 30496V Last Trip abFixed point, 3 decimals.INT32ABCD× 0.001Read
IR497doc 30498V Last Trip bcFixed point, 3 decimals.INT32ABCD× 0.001Read
IR499doc 30500V Last Trip caFixed point, 3 decimals.INT32ABCD× 0.001Read
IR501doc 30502V Last Trip nFixed point, 3 decimals.INT32ABCD× 0.001Read
IR577doc 30578I THD aFixed point, 3 decimals.INT32ABCD× 0.001%Read
IR579doc 30580I THD bFixed point, 3 decimals.INT32ABCD× 0.001%Read
IR581doc 30582I THD cFixed point, 3 decimals.INT32ABCD× 0.001%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)

What Modbus registers does the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) have?

This map lists 426 registers: 51 coils, 254 discrete inputs, 121 input registers. 51 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The point list uses Modicon numbers: coils 00001+, inputs 10001+, input registers 30001+. Subtract the block base for the wire address: coil 00001 = address 0, input 10001 = address 0, input register 30010 = address 9. The data-type section uses the same numbering (a float 'stored in registers 30001 and 30002').

What byte order does the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)?

Start with IR 63 I Primary a (Primary current phase a); IR 65 I Primary b (Primary current phase b); IR 67 I Primary c (Primary current phase c); IR 59 Frequency (Frequency); DI 109 General Trip (General trip); CO 108 CB 1 (CB 1 control point).

How do I enable Modbus control of the Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)?

In the Communications menu set COM1-RS485 Protocol = Modbus RTU (factory default is IEC 60870-5-103), then the station address (1-247), baud rate (default 19200) and parity (default even). Remote control needs the port mode to be Remote (default).

Where is the official Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU) Modbus documentation?

The source is Reyrolle 7SR10 Communication Protocols Manual (IEC 60870-5-103, Modbus RTU, DNP3) (C53000-L7040-C002-7), revision 2025-11. Siemens doesn't publish it on its own website, so this map was re-typed from a free copy at https://docs.rs-online.com/a9fe/A700000016195318.pdf. It may be an older revision, so check it against the live unit.

More Siemens Modbus register maps

Other soft starters & protection relays register maps

All soft starters & protection relays Modbus register maps →

Source: Reyrolle 7SR10 Communication Protocols Manual (IEC 60870-5-103, Modbus RTU, DNP3) · C53000-L7040-C002-7 · rev. 2025-11 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.