- Home
- Modbus register maps
- Siemens
- Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Protection relay · Modbus register map
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) Modbus register map
Updated 17 November 2026
The 7SR11 and 7SR12 Argus are overcurrent and earth-fault protection relays (7SR12 adds directional and voltage elements) whose RS-485, USB and optional fibre ports can run IEC 60870-5-103, Modbus RTU or DNP3. Under Modbus, commands are coils, indications are discrete inputs and measurands are input registers. This map covers the default point list: binary outputs and commands, protection element states, voltages, currents, frequency, power factor, maximum demand, fault values, counters and status bit strings.
This page lists 370 Modbus registers for the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
- Equipment type
- Protection relay
- Registers
- 370 (41 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120
Integration notes: Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Set COM1-RS485 Protocol to Modbus RTU and give the relay a station address, then read input registers (FC 04) from 30010 for voltages and 30064 for currents; values are 32-bit integers with 3 decimals, high word first. Protection pickups and trips are discrete inputs (FC 02); commands are coils (FC 05).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 63 | Ia Primary | INT32 ABCD | Primary current phase a | Read |
| IR 65 | Ib Primary | INT32 ABCD | Primary current phase b | Read |
| IR 67 | Ic Primary | INT32 ABCD | Primary current phase c | Read |
| IR 59 | Frequency | INT32 ABCD | Frequency | Read |
| DI 109 | General Trip | BIT | General trip | Read |
| CO 108 | CB 1 | BIT | CB 1 control point | Read/write |
Enable Modbus control & writes
In the Communications menu set COM1-RS485 Protocol = MODBUS-RTU (factory default is IEC 60870-5-103), then the station address (1-247), baud rate (default 19200) and parity (default even). Remote control needs the port mode Remote.
Byte order & addressing
- Measurands are input registers (FC 04), not holding registers.
- FP_32BITS_3DP values are integers: divide by 1000.
- Bit strings put the first item in the least significant bit.
Network setup
- RS-485 rear terminals 14 (A) and 18 (B); the internal 120 ohm terminator is connected by linking terminals 18 and 20.
- Up to 64 relays per RS-485 bus; the master must support Auto Device Enable (ADE).
- USB and fibre ports can run a protocol at the same time as RS-485.
Watch out for
- The 'Mult' column is not explained in the manual; check power readings against the relay display before using them.
- Event records must be read as exactly 8 registers or the relay answers exception 2.
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Binary Output 1 | BIT | Read/write | |||||
| CO | 1doc 00002 | Binary Output 2 | BIT | Read/write | |||||
| CO | 2doc 00003 | Binary Output 3 | BIT | Read/write | |||||
| CO | 3doc 00004 | Binary Output 4 | BIT | Read/write | |||||
| CO | 4doc 00005 | Binary Output 5 | BIT | Read/write | |||||
| CO | 5doc 00006 | Binary Output 6 | BIT | Read/write | |||||
| CO | 6doc 00007 | Binary Output 7 | BIT | Read/write | |||||
| CO | 7doc 00008 | Binary Output 8 | BIT | Read/write | |||||
| CO | 100doc 00101 | Setting G1 selected | BIT | Read/write | |||||
| CO | 101doc 00102 | Setting G2 selected | BIT | Read/write | |||||
| CO | 102doc 00103 | Setting G3 selected | BIT | Read/write | |||||
| CO | 103doc 00104 | Setting G4 selected | BIT | Read/write | |||||
| CO | 108doc 00109 | CB 1 | BIT | Read/write | |||||
| CO | 111doc 00112 | Auto-reclose active | BIT | Read/write | |||||
| CO | 112doc 00113 | HotLine Working | BIT | Read/write | |||||
| CO | 113doc 00114 | E/F Out | BIT | Read/write | |||||
| CO | 114doc 00115 | SEF Out | BIT | Read/write | |||||
| CO | 115doc 00116 | Inst Protection Out | BIT | Read/write | |||||
| CO | 154doc 00155 | Remote Mode | BIT | Read/write | |||||
| CO | 155doc 00156 | Out Of Service Mode | BIT | Read/write | |||||
| CO | 156doc 00157 | Local Mode | BIT | Read/write | |||||
| CO | 157doc 00158 | Local & Remote | BIT | Read/write | |||||
| CO | 164doc 00165 | Reset Start Count | BIT | Read/write | |||||
| CO | 179doc 00180 | CB 1 Opened | BIT | Read/write | |||||
| CO | 180doc 00181 | CB 1 Closed | BIT | Read/write | |||||
| CO | 199doc 00200 | User SP Command 1 | BIT | Read/write | |||||
| CO | 200doc 00201 | User SP Command 2 | BIT | Read/write | |||||
| CO | 201doc 00202 | User SP Command 3 | BIT | Read/write | |||||
| CO | 202doc 00203 | User SP Command 4 | BIT | Read/write | |||||
| CO | 203doc 00204 | User SP Command 5 | BIT | Read/write | |||||
| CO | 204doc 00205 | User SP Command 6 | BIT | Read/write | |||||
| CO | 205doc 00206 | User SP Command 7 | BIT | Read/write | |||||
| CO | 206doc 00207 | User SP Command 8 | BIT | Read/write | |||||
| CO | 207doc 00208 | User DP Command 1 | BIT | Read/write | |||||
| CO | 208doc 00209 | User DP Command 2 | BIT | Read/write | |||||
| CO | 209doc 00210 | User DP Command 3 | BIT | Read/write | |||||
| CO | 210doc 00211 | User DP Command 4 | BIT | Read/write | |||||
| CO | 211doc 00212 | User DP Command 5 | BIT | Read/write | |||||
| CO | 212doc 00213 | User DP Command 6 | BIT | Read/write | |||||
| CO | 213doc 00214 | User DP Command 7 | BIT | Read/write | |||||
| CO | 214doc 00215 | User DP Command 8 | BIT | Read/write | |||||
| DI | 0doc 10001 | Binary Input 1 | BIT | Read | |||||
| DI | 1doc 10002 | Binary Input 2 | BIT | Read | |||||
| DI | 2doc 10003 | Binary Input 3 | BIT | Read | |||||
| DI | 3doc 10004 | Binary Input 4 | BIT | Read | |||||
| DI | 4doc 10005 | Binary Input 5 | BIT | Read | |||||
| DI | 5doc 10006 | Binary Input 6 | BIT | Read | |||||
| DI | 101doc 10102 | Remote Mode | BIT | Read | |||||
| DI | 102doc 10103 | Out Of Service Mode | BIT | Read | |||||
| DI | 103doc 10104 | Local Mode | BIT | Read | |||||
| DI | 104doc 10105 | Local & Remote | BIT | Read | |||||
| DI | 109doc 10110 | General Trip | BIT | Read | |||||
| DI | 110doc 10111 | Trip Circuit Fail | BIT | Read | |||||
| DI | 111doc 10112 | Start/Pick-up L1 | BIT | Read | |||||
| DI | 112doc 10113 | Start/Pick-up L2 | BIT | Read | |||||
| DI | 113doc 10114 | Start/Pick-up L3 | BIT | Read | |||||
| DI | 114doc 10115 | General Start/Pick-up | BIT | Read | |||||
| DI | 115doc 10116 | VT Fuse Failure | BIT | Read | |||||
| DI | 116doc 10117 | Earth Fault Forward/Line | BIT | Read | |||||
| DI | 117doc 10118 | Earth Fault Reverse/Busbar | BIT | Read | |||||
| DI | 118doc 10119 | Start/Pick-up N | BIT | Read | |||||
| DI | 119doc 10120 | Fault Forward/Line | BIT | Read | |||||
| DI | 120doc 10121 | Fault Reverse/Busbar | BIT | Read | |||||
| DI | 121doc 10122 | 51-1 | BIT | Read | |||||
| DI | 122doc 10123 | 50-1 | BIT | Read | |||||
| DI | 123doc 10124 | 51N-1 | BIT | Read | |||||
| DI | 124doc 10125 | 50N-1 | BIT | Read | |||||
| DI | 125doc 10126 | 51G-1 | BIT | Read | |||||
| DI | 126doc 10127 | 50G-1 | BIT | Read | |||||
| DI | 127doc 10128 | 51-2 | BIT | Read | |||||
| DI | 128doc 10129 | 50-2 | BIT | Read | |||||
| DI | 129doc 10130 | 51N-2 | BIT | Read | |||||
| DI | 130doc 10131 | 50N-2 | BIT | Read | |||||
| DI | 131doc 10132 | 51G-2 | BIT | Read | |||||
| DI | 132doc 10133 | 50G-2 | BIT | Read | |||||
| DI | 133doc 10134 | 51-3 | BIT | Read | |||||
| DI | 134doc 10135 | 50-3 | BIT | Read | |||||
| DI | 135doc 10136 | 51N-3 | BIT | Read | |||||
| DI | 136doc 10137 | 50N-3 | BIT | Read | |||||
| DI | 137doc 10138 | 51G-3 | BIT | Read | |||||
| DI | 138doc 10139 | 50G-3 | BIT | Read | |||||
| DI | 139doc 10140 | 51-4 | BIT | Read | |||||
| DI | 140doc 10141 | 50-4 | BIT | Read | |||||
| DI | 141doc 10142 | 51N-4 | BIT | Read | |||||
| DI | 142doc 10143 | 50N-4 | BIT | Read | |||||
| DI | 143doc 10144 | 51G-4 | BIT | Read | |||||
| DI | 144doc 10145 | 50G-4 | BIT | Read | |||||
| DI | 145doc 10146 | 50BF Stage 2 | BIT | Read | |||||
| DI | 146doc 10147 | 49-Alarm | BIT | Read | |||||
| DI | 147doc 10148 | 49-Trip | BIT | Read | |||||
| DI | 148doc 10149 | 60 CTS | BIT | Read | |||||
| DI | 149doc 10150 | 46IT | BIT | Read | |||||
| DI | 150doc 10151 | 46DT | BIT | Read | |||||
| DI | 151doc 10152 | 47-1 | BIT | Read | |||||
| DI | 152doc 10153 | 47-2 | BIT | Read | |||||
| DI | 153doc 10154 | 46BC | BIT | Read | |||||
| DI | 154doc 10155 | 27/59-1 | BIT | Read | |||||
| DI | 155doc 10156 | 27/59-2 | BIT | Read | |||||
| DI | 156doc 10157 | 27/59-3 | BIT | Read | |||||
| DI | 157doc 10158 | 27/59-4 | BIT | Read | |||||
| DI | 158doc 10159 | 59NIT | BIT | Read | |||||
| DI | 159doc 10160 | 59NDT | BIT | Read | |||||
| DI | 160doc 10161 | 81-1 | BIT | Read | |||||
| DI | 161doc 10162 | 81-2 | BIT | Read | |||||
| DI | 162doc 10163 | 81-3 | BIT | Read | |||||
| DI | 163doc 10164 | 81-4 | BIT | Read | |||||
| DI | 166doc 10167 | 64H | BIT | Read | |||||
| DI | 167doc 10168 | 37-1 | BIT | Read | |||||
| DI | 168doc 10169 | 37-2 | BIT | Read | |||||
| DI | 170doc 10171 | Auto-reclose active | BIT | Read | |||||
| DI | 171doc 10172 | CB on by auto reclose | BIT | Read | |||||
| DI | 172doc 10173 | Reclaim | BIT | Read | |||||
| DI | 173doc 10174 | Lockout | BIT | Read | |||||
| DI | 174doc 10175 | HotLine Working | BIT | Read | |||||
| DI | 175doc 10176 | Inst Protection Out | BIT | Read | |||||
| DI | 176doc 10177 | CB Total Trip Count | BIT | Read | |||||
| DI | 177doc 10178 | CB Delta Trip Count | BIT | Read | |||||
| DI | 178doc 10179 | CB Count To AR Block | BIT | Read | |||||
| DI | 179doc 10180 | I^2t CB Wear | BIT | Read | |||||
| DI | 180doc 10181 | 79 AR In progress | BIT | Read | |||||
| DI | 181doc 10182 | Cold Load Active | BIT | Read | |||||
| DI | 182doc 10183 | E/F Out | BIT | Read | |||||
| DI | 183doc 10184 | P/F Inst Protection Inhibited | BIT | Read | |||||
| DI | 184doc 10185 | E/F Inst Protection Inhibited | BIT | Read | |||||
| DI | 185doc 10186 | SEF Inst Protection Inhibited | BIT | Read | |||||
| DI | 186doc 10187 | Ext Inst Protection Inhibited | BIT | Read | |||||
| DI | 201doc 10202 | 51SEF-1 | BIT | Read | |||||
| DI | 202doc 10203 | 50SEF-1 | BIT | Read | |||||
| DI | 203doc 10204 | 51SEF-2 | BIT | Read | |||||
| DI | 204doc 10205 | 50SEF-2 | BIT | Read | |||||
| DI | 205doc 10206 | 51SEF-3 | BIT | Read | |||||
| DI | 206doc 10207 | 50SEF-3 | BIT | Read | |||||
| DI | 207doc 10208 | 51SEF-4 | BIT | Read | |||||
| DI | 208doc 10209 | 50SEF-4 | BIT | Read | |||||
| DI | 209doc 10210 | SEF Out | BIT | Read | |||||
| DI | 210doc 10211 | Trip Circuit Fail 1 | BIT | Read | |||||
| DI | 211doc 10212 | Trip Circuit Fail 2 | BIT | Read | |||||
| DI | 212doc 10213 | Trip Circuit Fail 3 | BIT | Read | |||||
| DI | 213doc 10214 | CB Total Trip Count | BIT | Read | |||||
| DI | 214doc 10215 | CB Delta Trip Count | BIT | Read | |||||
| DI | 215doc 10216 | CB Count To AR Block | BIT | Read | |||||
| DI | 216doc 10217 | CB Frequent Ops Count | BIT | Read | |||||
| DI | 217doc 10218 | I^2t CB Wear | BIT | Read | |||||
| DI | 218doc 10219 | CB 1 Opened | BIT | Read | |||||
| DI | 219doc 10220 | CB 1 Closed | BIT | Read | |||||
| DI | 282doc 10283 | Close Circuit Fail 1 | BIT | Read | |||||
| DI | 283doc 10284 | Close Circuit Fail 2 | BIT | Read | |||||
| DI | 284doc 10285 | Close Circuit Fail 3 | BIT | Read | |||||
| DI | 285doc 10286 | Close Circuit Fail | BIT | Read | |||||
| DI | 287doc 10288 | SEF Forward/Line | BIT | Read | |||||
| DI | 288doc 10289 | SEF Reverse/Busbar | BIT | Read | |||||
| DI | 289doc 10290 | General Alarm 1 | BIT | Read | |||||
| DI | 290doc 10291 | General Alarm 2 | BIT | Read | |||||
| DI | 291doc 10292 | General Alarm 3 | BIT | Read | |||||
| DI | 292doc 10293 | General Alarm 4 | BIT | Read | |||||
| DI | 293doc 10294 | General Alarm 5 | BIT | Read | |||||
| DI | 294doc 10295 | General Alarm 6 | BIT | Read | |||||
| DI | 301doc 10302 | Quick Logic E1 | BIT | Read | |||||
| DI | 302doc 10303 | Quick Logic E2 | BIT | Read | |||||
| DI | 303doc 10304 | Quick Logic E3 | BIT | Read | |||||
| DI | 304doc 10305 | Quick Logic E4 | BIT | Read | |||||
| DI | 333doc 10334 | 60 CTS-I | BIT | Read | |||||
| DI | 334doc 10335 | 81HBL2 | BIT | Read | |||||
| DI | 335doc 10336 | 37G-1 | BIT | Read | |||||
| DI | 336doc 10337 | 37G-2 | BIT | Read | |||||
| DI | 337doc 10338 | 37SEF-1 | BIT | Read | |||||
| DI | 338doc 10339 | 37SEF-2 | BIT | Read | |||||
| DI | 366doc 10367 | 50BF Stage 1 | BIT | Read | |||||
| DI | 367doc 10368 | Wattmetric Po> | BIT | Read | |||||
| DI | 368doc 10369 | 37-PhA | BIT | Read | |||||
| DI | 369doc 10370 | 37-PhB | BIT | Read | |||||
| DI | 370doc 10371 | 37-PhC | BIT | Read | |||||
| DI | 377doc 10378 | 50BF-PhA | BIT | Read | |||||
| DI | 378doc 10379 | 50BF-PhB | BIT | Read | |||||
| DI | 379doc 10380 | 50BF-PhC | BIT | Read | |||||
| DI | 380doc 10381 | 50BF-EF | BIT | Read | |||||
| DI | 382doc 10383 | 60 CTS-I-PhA | BIT | Read | |||||
| DI | 383doc 10384 | 60 CTS-I-PhB | BIT | Read | |||||
| DI | 384doc 10385 | 60 CTS-I-PhC | BIT | Read | |||||
| DI | 389doc 10390 | Trip PhA | BIT | Read | |||||
| DI | 390doc 10391 | Trip PhB | BIT | Read | |||||
| DI | 391doc 10392 | Trip PhC | BIT | Read | |||||
| DI | 400doc 10401 | 27/59 PhA | BIT | Read | |||||
| DI | 401doc 10402 | 27/59 PhB | BIT | Read | |||||
| DI | 402doc 10403 | 27/59 PhC | BIT | Read | |||||
| DI | 409doc 10410 | CB Alarm | BIT | Read | |||||
| DI | 500doc 10501 | Virtual Input 1 | BIT | Read | |||||
| DI | 501doc 10502 | Virtual Input 2 | BIT | Read | |||||
| DI | 502doc 10503 | Virtual Input 3 | BIT | Read | |||||
| DI | 503doc 10504 | Virtual Input 4 | BIT | Read | |||||
| DI | 504doc 10505 | Virtual Input 5 | BIT | Read | |||||
| DI | 505doc 10506 | Virtual Input 6 | BIT | Read | |||||
| DI | 506doc 10507 | Virtual Input 7 | BIT | Read | |||||
| DI | 507doc 10508 | Virtual Input 8 | BIT | Read | |||||
| DI | 600doc 10601 | LED 1 | BIT | Read | |||||
| DI | 601doc 10602 | LED 2 | BIT | Read | |||||
| DI | 602doc 10603 | LED 3 | BIT | Read | |||||
| DI | 603doc 10604 | LED 4 | BIT | Read | |||||
| DI | 604doc 10605 | LED 5 | BIT | Read | |||||
| DI | 605doc 10606 | LED 6 | BIT | Read | |||||
| DI | 606doc 10607 | LED 7 | BIT | Read | |||||
| DI | 607doc 10608 | LED 8 | BIT | Read | |||||
| DI | 608doc 10609 | LED 9 | BIT | Read | |||||
| DI | 700doc 10701 | LED PU 1 | BIT | Read | |||||
| DI | 701doc 10702 | LED PU 2 | BIT | Read | |||||
| DI | 702doc 10703 | LED PU 3 | BIT | Read | |||||
| DI | 703doc 10704 | LED PU 4 | BIT | Read | |||||
| DI | 704doc 10705 | LED PU 5 | BIT | Read | |||||
| DI | 705doc 10706 | LED PU 6 | BIT | Read | |||||
| DI | 706doc 10707 | LED PU 7 | BIT | Read | |||||
| DI | 707doc 10708 | LED PU 8 | BIT | Read | |||||
| DI | 708doc 10709 | LED PU 9 | BIT | Read | |||||
| DI | 799doc 10800 | Cold Start | BIT | Read | |||||
| DI | 800doc 10801 | Warm Start | BIT | Read | |||||
| DI | 801doc 10802 | Re-Start | BIT | Read | |||||
| DI | 802doc 10803 | Power On | BIT | Read | |||||
| DI | 803doc 10804 | Expected Restart | BIT | Read | |||||
| DI | 804doc 10805 | Unexpected Restart | BIT | Read | |||||
| DI | 805doc 10806 | Reset Start Count | BIT | Read | |||||
| DI | 899doc 10900 | User SP Command 1 | BIT | Read | |||||
| DI | 900doc 10901 | User SP Command 2 | BIT | Read | |||||
| DI | 901doc 10902 | User SP Command 3 | BIT | Read | |||||
| DI | 902doc 10903 | User SP Command 4 | BIT | Read | |||||
| DI | 903doc 10904 | User SP Command 5 | BIT | Read | |||||
| DI | 904doc 10905 | User SP Command 6 | BIT | Read | |||||
| DI | 905doc 10906 | User SP Command 7 | BIT | Read | |||||
| DI | 906doc 10907 | User SP Command 8 | BIT | Read | |||||
| DI | 907doc 10908 | User DP Command 1 | BIT | Read | |||||
| DI | 908doc 10909 | User DP Command 2 | BIT | Read | |||||
| DI | 909doc 10910 | User DP Command 3 | BIT | Read | |||||
| DI | 910doc 10911 | User DP Command 4 | BIT | Read | |||||
| DI | 911doc 10912 | User DP Command 5 | BIT | Read | |||||
| DI | 912doc 10913 | User DP Command 6 | BIT | Read | |||||
| DI | 913doc 10914 | User DP Command 7 | BIT | Read | |||||
| DI | 914doc 10915 | User DP Command 8 | BIT | Read | |||||
| DI | 915doc 10916 | 32-1 | BIT | Read | |||||
| DI | 916doc 10917 | 32-2 | BIT | Read | |||||
| DI | 917doc 10918 | 32S-1 | BIT | Read | |||||
| DI | 918doc 10919 | 32S-2 | BIT | Read | |||||
| DI | 919doc 10920 | 55-1 | BIT | Read | |||||
| DI | 920doc 10921 | 55-2 | BIT | Read | |||||
| DI | 1072doc 11073 | CB DBI | BIT | Read | |||||
| DI | 1073doc 11074 | CB Travelling | BIT | Read | |||||
| DI | 1074doc 11075 | Close CB Failed | BIT | Read | |||||
| DI | 1075doc 11076 | Open CB Failed | BIT | Read | |||||
| DI | 1076doc 11077 | Start Count Alarm | BIT | Read | |||||
| DI | 1077doc 11078 | 50AFD PhA | BIT | Read | |||||
| DI | 1078doc 11079 | 50AFD PhB | BIT | Read | |||||
| DI | 1079doc 11080 | 50AFD PhC | BIT | Read | |||||
| DI | 1080doc 11081 | 50AFD | BIT | Read | |||||
| DI | 1081doc 11082 | AFD Zone 1 Flash | BIT | Read | |||||
| DI | 1082doc 11083 | AFD Zone 1 | BIT | Read | |||||
| DI | 1083doc 11084 | AFD Zone 2 Flash | BIT | Read | |||||
| DI | 1084doc 11085 | AFD Zone 2 | BIT | Read | |||||
| DI | 1085doc 11086 | AFD Zone 3 Flash | BIT | Read | |||||
| DI | 1086doc 11087 | AFD Zone 3 | BIT | Read | |||||
| DI | 1087doc 11088 | AFD Zone 4 Flash | BIT | Read | |||||
| DI | 1088doc 11089 | AFD Zone 4 | BIT | Read | |||||
| DI | 1089doc 11090 | AFD Zone 5 Flash | BIT | Read | |||||
| DI | 1090doc 11091 | AFD Zone 5 | BIT | Read | |||||
| DI | 1091doc 11092 | AFD Zone 6 Flash | BIT | Read | |||||
| DI | 1092doc 11093 | AFD Zone 6 | BIT | Read | |||||
| IR | 0doc 30001 | Event count | Number of events in the relay's event buffer. | INT16 | Read | ||||
| IR | 9doc 30010 | Vab Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 11doc 30012 | Vbc Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 13doc 30014 | Vca Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 15doc 30016 | Va Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 17doc 30018 | Vb Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 19doc 30020 | Vc Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 21doc 30022 | Va Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 23doc 30024 | Vb Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 25doc 30026 | Vc Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 33doc 30034 | Vab Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 35doc 30036 | Vbc Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 37doc 30038 | Vca Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 39doc 30040 | Va Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 41doc 30042 | Vb Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 43doc 30044 | Vc Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 47doc 30048 | Vzps | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 49doc 30050 | Vpps | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 51doc 30052 | Vnps | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 53doc 30054 | Vzps angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 55doc 30056 | Vpps angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 57doc 30058 | Vnps angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 59doc 30060 | Frequency | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Hz | Read | |
| IR | 63doc 30064 | Ia Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 65doc 30066 | Ib Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 67doc 30068 | Ic Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 69doc 30070 | Ia Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 71doc 30072 | Ib Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 73doc 30074 | Ic Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 75doc 30076 | Ia Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 77doc 30078 | Ib Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 79doc 30080 | Ic Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 81doc 30082 | Ia Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 83doc 30084 | Ib Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 85doc 30086 | Ic Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 87doc 30088 | In Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 89doc 30090 | In Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 91doc 30092 | In Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xInom | Read | |
| IR | 93doc 30094 | Ig Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 95doc 30096 | Ig Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 97doc 30098 | Ig Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xInom | Read | |
| IR | 99doc 30100 | Izps Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 101doc 30102 | Ipps Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 103doc 30104 | Inps Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xIn | Read | |
| IR | 105doc 30106 | Izps Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 107doc 30108 | Ipps Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 109doc 30110 | Inps Nominal angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 135doc 30136 | Power Factor A | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 137doc 30138 | Power Factor B | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 139doc 30140 | Power Factor C | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 141doc 30142 | Power Factor(3P) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 151doc 30152 | Thermal Status Ph A | INT16 | % | Read | ||||
| IR | 152doc 30153 | Thermal Status Ph B | INT16 | % | Read | ||||
| IR | 153doc 30154 | Thermal Status Ph C | INT16 | % | Read | ||||
| IR | 166doc 30167 | Fault Records | INT16 | Read | |||||
| IR | 167doc 30168 | Event Records | INT16 | Read | |||||
| IR | 168doc 30169 | Waveform Records | INT16 | Read | |||||
| IR | 169doc 30170 | Vab Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 171doc 30172 | Vbc Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 173doc 30174 | Vca Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 175doc 30176 | Vn Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 177doc 30178 | Vn Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | V | Read | |
| IR | 179doc 30180 | Vn Secondary angle | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | ° | Read | |
| IR | 192doc 30193 | I Phase A Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 194doc 30195 | I Phase B Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 196doc 30197 | I Phase C Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 206doc 30207 | Isef Primary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 208doc 30209 | Isef Secondary | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | A | Read | |
| IR | 210doc 30211 | Isef Nominal (multiple of rated current) | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | xInom | Read | |
| IR | 240doc 30241 | CB Total Trip Count | 32-bit integer. | INT32 | ABCD | Read | |||
| IR | 242doc 30243 | CB Delta Trip Count | 32-bit integer. | INT32 | ABCD | Read | |||
| IR | 244doc 30245 | CB Count To AR Block | 32-bit integer. | INT32 | ABCD | Read | |||
| IR | 246doc 30247 | CB Frequent Ops Count | 32-bit integer. | INT32 | ABCD | Read | |||
| IR | 300doc 30301 | Ia Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 302doc 30303 | Ib Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 304doc 30305 | Ic Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 306doc 30307 | Va Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 308doc 30309 | Vb Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 310doc 30311 | Vc Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 312doc 30313 | In Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 314doc 30315 | Ig Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 316doc 30317 | Isef Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 318doc 30319 | V Phase A Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 320doc 30321 | V Phase B Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 322doc 30323 | V Phase C Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 324doc 30325 | V Phase AB Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 326doc 30327 | V Phase BC Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 328doc 30329 | V Phase CA Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 340doc 30341 | Led 1-16 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Led 1; bit 1 = Led 2; bit 2 = Led 3; bit 3 = Led 4; bit 4 = Led 5; bit 5 = Led 6; bit 6 = Led 7; bit 7 = Led 8; bit 8 = Led 9; bit 9 = Led 10; bit 10 = Led 11; bit 11 = Led 12; bit 12 = Led 13; bit 13 = Led 14; bit 14 = Led 15; bit 15 = Led 16 | |||
| IR | 341doc 30342 | Led 17-32 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Led 17; bit 1 = Led 18; bit 2 = Led 19; bit 3 = Led 20; bit 4 = Led 21; bit 5 = Led 22; bit 6 = Led 23; bit 7 = Led 24; bit 8 = Led 25; bit 9 = Led 26; bit 10 = Led 27; bit 11 = Led 28; bit 12 = Led 29; bit 13 = Led 30; bit 14 = Led 31; bit 15 = Led 32 | |||
| IR | 342doc 30343 | Input 1-16 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16 | |||
| IR | 343doc 30344 | Input 17-32 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Input 17; bit 1 = Input 18; bit 2 = Input 19; bit 3 = Input 20; bit 4 = Input 21; bit 5 = Input 22; bit 6 = Input 23; bit 7 = Input 24; bit 8 = Input 25; bit 9 = Input 26; bit 10 = Input 27; bit 11 = Input 28; bit 12 = Input 29; bit 13 = Input 30; bit 14 = Input 31; bit 15 = Input 32 | |||
| IR | 344doc 30345 | Output 1-16 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8; bit 8 = Output 9; bit 9 = Output 10; bit 10 = Output 11; bit 11 = Output 12; bit 12 = Output 13; bit 13 = Output 14; bit 14 = Output 15; bit 15 = Output 16 | |||
| IR | 345doc 30346 | Output 17-32 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Output 17; bit 1 = Output 18; bit 2 = Output 19; bit 3 = Output 20; bit 4 = Output 21; bit 5 = Output 22; bit 6 = Output 23; bit 7 = Output 24; bit 8 = Output 25; bit 9 = Output 26; bit 10 = Output 27; bit 11 = Output 28; bit 12 = Output 29; bit 13 = Output 30; bit 14 = Output 31; bit 15 = Output 32 | |||
| IR | 346doc 30347 | Virtual 1-16 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Virtual 1; bit 1 = Virtual 2; bit 2 = Virtual 3; bit 3 = Virtual 4; bit 4 = Virtual 5; bit 5 = Virtual 6; bit 6 = Virtual 7; bit 7 = Virtual 8; bit 8 = Virtual 9; bit 9 = Virtual 10; bit 10 = Virtual 11; bit 11 = Virtual 12; bit 12 = Virtual 13; bit 13 = Virtual 14; bit 14 = Virtual 15; bit 15 = Virtual 16 | |||
| IR | 347doc 30348 | Virtual 17-32 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Virtual 17; bit 1 = Virtual 18; bit 2 = Virtual 19; bit 3 = Virtual 20; bit 4 = Virtual 21; bit 5 = Virtual 22; bit 6 = Virtual 23; bit 7 = Virtual 24; bit 8 = Virtual 25; bit 9 = Virtual 26; bit 10 = Virtual 27; bit 11 = Virtual 28; bit 12 = Virtual 29; bit 13 = Virtual 30; bit 14 = Virtual 31; bit 15 = Virtual 32 | |||
| IR | 348doc 30349 | Equation 1-16 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Equation 1; bit 1 = Equation 2; bit 2 = Equation 3; bit 3 = Equation 4; bit 4 = Equation 5; bit 5 = Equation 6; bit 6 = Equation 7; bit 7 = Equation 8; bit 8 = Equation 9; bit 9 = Equation 10; bit 10 = Equation 11; bit 11 = Equation 12; bit 12 = Equation 13; bit 13 = Equation 14; bit 14 = Equation 15; bit 15 = Equation 16 | |||
| IR | 349doc 30350 | Equation 17-32 status | First item in bit 0 (LSB). | BITMAP16 | Read | bit 0 = Equation 17; bit 1 = Equation 18; bit 2 = Equation 19; bit 3 = Equation 20; bit 4 = Equation 21; bit 5 = Equation 22; bit 6 = Equation 23; bit 7 = Equation 24; bit 8 = Equation 25; bit 9 = Equation 26; bit 10 = Equation 27; bit 11 = Equation 28; bit 12 = Equation 29; bit 13 = Equation 30; bit 14 = Equation 31; bit 15 = Equation 32 | |||
| IR | 359doc 30360 | CB Wear A Remaining | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 361doc 30362 | CB Wear B Remaining | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 363doc 30364 | CB Wear C Remaining | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 365doc 30366 | CB Wear Minimum | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 379doc 30380 | StartCount | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 381doc 30382 | Start Count Target | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 389doc 30390 | Freq Last Trip | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 391doc 30392 | Active Setting Group | INT16 | Read | |||||
| IR | 399doc 30400 | Frequency Max | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read | ||
| IR | 467doc 30468 | CB Trip Time Meter | Fixed point, 3 decimals. | INT32 | ABCD | × 0.001 | Read |
Notes on this map
- Word order: the manual states that 32-bit values are stored in two registers in big-endian format and shows FP_32BITS_3DP 123456 as 30001 = 0001h, 30002 = E240h, so high word first (ABCD).
- FP_32BITS_3DP is a signed 32-bit integer carrying 3 decimal places (123.456 sent as 123456), so scale is 0.001. The manual's 'UINT32' and 'UINT16' are described as signed (two's complement), so they are listed as INT32 / INT16.
- The point list is the factory default; it can be changed with the Communications Configuration Editor, and some points do not exist on every model.
- Each point list row has a 'Mult' column that the manual does not explain. Numeric rows with Mult 1.000000 are listed (bit strings and the event counter, printed with Mult 0.000000, are also kept); rows with other Mult values (active/reactive/apparent power, max demand power, CB wear, S 3P max) are left out because their engineering scale cannot be settled from the manual.
- Left out: the energy meter registers 30144-30150 (no unit printed), the 8-register event record at 30002 the TIME_METER holding register 40001 (byte-packed structures) and the holding-register copy of the measurands from 40010, which repeats the 300xx layout.
- Units come from the point list description: 'xIn' / 'xInom' values are multiples of rated current, 'Degrees' values are phase angles.
- Shaded rows in the manual are not available on every model (for example voltage-based values need a 7SR12 with VT inputs); the shading is not reproduced here.
- Units are given only where the point list prints one; fault, maximum-demand and last-trip values have no unit in the list.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
What Modbus registers does the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) have?
This map lists 370 registers: 41 coils, 221 discrete inputs, 108 input registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The point list uses Modicon numbers: coils 00001+, inputs 10001+, input registers 30001+. Subtract the block base for the wire address: coil 00001 = address 0, input 10001 = address 0, input register 30010 = address 9. The data-type section uses the same numbering (a float 'stored in registers 30001 and 30002').
What byte order does the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)?
Start with IR 63 Ia Primary (Primary current phase a); IR 65 Ib Primary (Primary current phase b); IR 67 Ic Primary (Primary current phase c); IR 59 Frequency (Frequency); DI 109 General Trip (General trip); CO 108 CB 1 (CB 1 control point).
How do I enable Modbus control of the Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)?
In the Communications menu set COM1-RS485 Protocol = MODBUS-RTU (factory default is IEC 60870-5-103), then the station address (1-247), baud rate (default 19200) and parity (default even). Remote control needs the port mode Remote.
Where is the official Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU) Modbus documentation?
The source is 7SR11 & 7SR12 Argus Overcurrent Relay Complete Technical Manual (Chapter 4 - Data Communications Definitions, section 4 MODBUS Definitions) (Siemens industry support entry 109747284 (att_918664)), revision 2015, published free by Siemens at https://cache.industry.siemens.com/dl/files/284/109747284/att_918664/v1/7SR12_Argus_Complete_Technical_Manual.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other soft starters & protection relays register maps
- Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042
All soft starters & protection relays Modbus register maps →
Source: 7SR11 & 7SR12 Argus Overcurrent Relay Complete Technical Manual (Chapter 4 - Data Communications Definitions, section 4 MODBUS Definitions) · Siemens industry support entry 109747284 (att_918664) · rev. 2015. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.