Sensor (flow transmitter) · Modbus register map

Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module Modbus register map

Updated 17 November 2026

Short answer

The MASS 6000 Coriolis transmitter gets a Modbus RTU slave by fitting the USM II RS-485 add-on module. Data is held in holding registers and coils only. This map covers mass and volume flow, density, sensor temperature, fractions, totalizers, driver and identity registers, the MASS 6000 settings tables, sensor diagnostics, system status and the control coils.

This page lists 163 Modbus registers for the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module — 104 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
SITRANS F C MASS 6000 with USM II Modbus RTU module
Equipment type
Sensor (flow transmitter)
Registers
163 (104 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
MASS 6000, SITRANS FC MASS 6000
Source document
SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions · A5E00753974-AB · rev. 2021-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module

Integration in brief

Read holding registers (FC 03) from address 3000: seven floats give mass flow, volume flow, density, temperature and fractions, followed by the double totalizers at 3014 and 3018. All values are big-endian, high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3000Absolute MassflowFLOAT32 ABCDMass flowRead
HR 3002Absolute VolumeflowFLOAT32 ABCDVolume flowRead
HR 3004Absolute DensityFLOAT32 ABCDDensityRead
HR 3006Sensor temperatureFLOAT32 ABCDSensor temperatureRead
HR 3014Totalizer 1FLOAT64 ABCDTotalizer 1 (double)Read
HR 3200System statusBITMAP16System status bitsRead

Enable Modbus control & writes

Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.

Byte order & addressing

Network setup

Watch out for

Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

163 of 163 shown
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0:00001Restart MODBUS communicationWrite 1 to restart; reads 0.BITRead/write
CO8doc 0:00009Start auto zero adjustWrite 1 to start; reads 1 while busy.BITRead/write
CO9doc 0:00010Reset totalizer 1Write 1 to reset; reads 0.BITRead/write
CO10doc 0:00011Hold totalizer 11 = hold, 0 = run; reads back held state.BITRead/write
CO11doc 0:00012Reset totalizer 2Write 1 to reset; reads 0.BITRead/write
CO12doc 0:00013Hold totalizer 21 = hold, 0 = run; reads back held state.BITRead/write
CO13doc 0:00014Start batch1 = start, 0 = stop batch.BITRead/write
CO14doc 0:00015Pause batch1 = pause, 0 = resume batch.BITRead/write
HR500doc 4:00501No. of ParityErrorsUINT16Read
HR501doc 4:00502No. of FramingErrorsUINT16Read
HR503doc 4:00504No. of CRC ErrorsUINT16Read
HR504doc 4:00505No. of Ok Messages (received)UINT16Read
HR507doc 4:00508InterFrameSpaceUINT32ABCDusRead
HR511doc 4:00512Response TimeoutUINT16msRead/write
HR512doc 4:00513Response DelayUINT16msRead/write
HR513doc 4:0051410xInterFrameSpace (10 x chars)UINT16Read/write
HR514doc 4:00515Baudrate as double wordUINT32ABCDRead
HR528doc 4:00529Device address (1 - 247)UINT16Read/write
HR529doc 4:00530BaudrateUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 76800; 8 = 115200
HR530doc 4:00531Parity/framingUINT16Read/write0 = 8, E, 1; 1 = 8, O, 1; 2 = 8, N, 2; 3 = 8, N, 1
HR600doc 4:00601Slave IDUINT16Read0x2A = Siemens
HR601doc 4:00602Run indicatorUINT16Read0x00 = not running; 0xFF = running
HR602doc 4:00603Product codeUINT16Read24 = MAG 6000; 25 = MASS 6000
HR605doc 4:00606Flowmeter revisionUINT16Read
HR606doc 4:00607MODBUS revisionUINT16Read
HR607doc 4:00608Manufacturer nameSTRING[12]Read
HR613doc 4:00614Product nameSTRING[18]Read
HR622doc 4:00623MODBUS module nameSTRING[12]Read
HR640doc 4:00641TAGSTRING[18]Read/write
HR649doc 4:00650MODBUS module SW versionSTRING[20]Read
HR659doc 4:00660MODBUS module HW versionUINT16Read
HR680doc 4:00681Last Coil Error (CoilAddr)UINT16Read
HR681doc 4:00682Last Coil Error (ErrorNo)UINT16Read
HR682doc 4:00683Last HoldReg Error (HoldReg Addr)UINT16Read
HR683doc 4:00684Last HoldReg Error (ErrorNo)UINT16Read
HR2000doc 4:02001Flow directionUINT16Read/write0 = Negative; 1 = Positive
HR2001doc 4:02002Massflow max.FLOAT32ABCDkg/sRead/write
HR2003doc 4:02004Volumeflow max.FLOAT32ABCDm3/sRead/write
HR2009doc 4:02010Density min.FLOAT32ABCDkg/m3Read/write
HR2011doc 4:02012Density max.FLOAT32ABCDkg/m3Read/write
HR2013doc 4:02014Sensor temperature min.FLOAT32ABCD°CRead/write
HR2015doc 4:02016Sensor temperature max.FLOAT32ABCD°CRead/write
HR2017doc 4:02018Fraction A max.FLOAT32ABCDkg/sRead/write
HR2019doc 4:02020Fraction B max.FLOAT32ABCDkg/sRead/write
HR2021doc 4:02022% fraction A min.FLOAT32ABCDRead/write
HR2023doc 4:02024% fraction A max.FLOAT32ABCDRead/write
HR2025doc 4:02026Low flow cut offFLOAT32ABCDRead/write
HR2027doc 4:02028Empty pipe limitFLOAT32ABCDkg/m3Read/write
HR2029doc 4:02030Empty pipe on/offUINT16Read/write0 = Off; 1 = On
HR2030doc 4:02031Noise filterUINT16Read/write1 = min.; 5 = max.
HR2031doc 4:02032Error levelUINT16Read/write1 = Warning; 2 = Permanent; 3 = Fatal
HR2032doc 4:02033Zero adjust modeUINT16Read/write0 = Auto; 1 = Manual
HR2033doc 4:02034Manual zero adjustFLOAT32ABCDkg/sRead/write
HR2035doc 4:02036Zero adjust timeUINT16sRead/write
HR2036doc 4:02037Zero sigmaFLOAT32ABCDkg/sRead
HR2038doc 4:02039Zero sigma limitFLOAT32ABCDkg/sRead/write
HR2100doc 4:02101Totalizer 1 selectionUINT16Read/write1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow
HR2101doc 4:02102Totalizer 1 directionUINT16Read/write0 = Reverse; 1 = Forward; 2 = Net
HR2102doc 4:02103Totalizer 2 selectionUINT16Read/write1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow
HR2103doc 4:02104Totalizer 2 directionUINT16Read/write0 = Reverse; 1 = Forward; 2 = Net
HR2200doc 4:02201Current Output 1 selectionUINT16Read/write0 = Off; 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow; 5 = Sensor temp.; 6 = Density; 7 = % fraction A
HR2201doc 4:02202Current Output 1 directionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2202doc 4:02203Current Output 1 rangeUINT16Read/write0 = 0 - 20 mA; 1 = 4 - 20 mA; 2 = 4 - 20 mA + Alarm
HR2203doc 4:02204Current Output 1 time constantsFLOAT32ABCDRead/write
HR2205doc 4:02206Digital Output 1 functionUINT16Read/write0 = Off; 1 = Pulse; 2 = Frequency; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit; 6 = Batch
HR2206doc 4:02207Pulse 1 selectionUINT16Read/write0 = Uninitialized; 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow
HR2207doc 4:02208Pulse 1 directionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2208doc 4:02209Pulse 1 widthUINT16Read/write0 = 64 us; 1 = 130 us; 2 = 260 us; 3 = 510 us; 4 = 1.0 ms; 5 = 2.0 ms; 6 = 4.1 ms; 7 = 8.2 ms; 8 = 16 ms; 9 = 33 ms; 10 = 66 ms; 11 = 130 ms; 12 = 260 ms; 13 = 520 ms; 14 = 1.0 s; 15 = 2.1 s; 16 = 4.2 s
HR2210doc 4:02211Frequency 1 selectionUINT16Read/write0 = Off (read only); 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow; 5 = Sensor temp.; 6 = Density; 7 = % fraction A
HR2211doc 4:02212Frequency 1 DirectionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2212doc 4:02213Frequency 1 Fmax.UINT16Read/write0 = 10 kHz; 1 = 5 kHz; 2 = 1 kHz; 3 = 500 Hz
HR2213doc 4:02214Frequency 1 TimeconstantsFLOAT32ABCDRead/write
HR2215doc 4:02216Limit Digital selectionUINT16Read/write0 = Off (read only); 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow; 5 = Sensor temp.; 6 = Density; 7 = % fraction A
HR2216doc 4:02217Limit Digital modeUINT16Read/write0 = 1 setpoint; 1 = 2 setpoints
HR2217doc 4:02218Limit Digital Setpoint min.FLOAT32ABCD1/100%Read/write
HR2219doc 4:02220Limit Digital Setpoint max.FLOAT32ABCD1/100%Read/write
HR2221doc 4:02222Limit Digital HysteresisFLOAT32ABCD1/100%Read/write
HR2223doc 4:02224Relay Output 1 functionUINT16Read/write0 = Off; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit
HR2224doc 4:02225Limit Relay selectionUINT16Read/write0 = Off; 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow; 5 = Sensor temp.; 6 = Density; 7 = % fraction A
HR2225doc 4:02226Limit Relay modeUINT16Read/write0 = 1 setpoint; 1 = 2 setpoints
HR2226doc 4:02227Limit Relay Setpoint min.FLOAT32ABCD1/100%Read/write
HR2228doc 4:02229Limit Relay Setpoint max.FLOAT32ABCD1/100%Read/write
HR2230doc 4:02231Limit Relay HysteresisFLOAT32ABCD1/100%Read/write
HR2232doc 4:02233Error number (0-255)UINT16Read/write
HR2233doc 4:02234Batch selectionUINT16Read/write0 = Off (read only); 1 = Massflow; 2 = Fraction A; 3 = Fraction B; 4 = Volumeflow
HR2234doc 4:02235Batch QuantityFLOAT32ABCDkg or m3Read/write
HR2236doc 4:02237Batch CompensationFLOAT32ABCDm3Read/write
HR2238doc 4:02239Batch Lead constantFLOAT32ABCDRead/write
HR2240doc 4:02241Batch Time error on/offUINT16Read/write0 = Off; 1 = On
HR2241doc 4:02242Max. Batch timeFLOAT32ABCDsRead/write
HR2243doc 4:02244Batch overrun on/offUINT16Read/write0 = Off; 1 = On
HR2244doc 4:02245Batch overrun errorFLOAT32ABCDkg or m3Read/write
HR2246doc 4:02247Batch counter up/downUINT16Read/write0 = Down; 1 = Up
HR2249doc 4:02250Batch cycle counterUINT32ABCDRead
HR2290doc 4:02291Mass or Volume per pulseFLOAT32ABCDm3Read/write
HR2292doc 4:02293Pulse PolarityUINT16Read/write0 = Negative; 1 = Positive
HR2295doc 4:02296QuadraturUINT16Read/write0 = Off; 1 = On
HR2300doc 4:02301Input FunctionUINT16Read/write0 = Off; 1 = Start Batch; 2 = Hold/Continue; 3 = Stop Batch; 4 = Zero Adjust; 5 = Totalizer reset; 6 = Force output; 7 = Freeze output
HR2301doc 4:02302Totalizer resetUINT16Read/write0 = Totalizer 1; 1 = Totalizer 2; 2 = Totalizer 1 + 2
HR2302doc 4:02303Force outputFLOAT32ABCD1/100%Read/write
HR2400doc 4:02401Sensor sizeFLOAT32ABCDmRead/write
HR2402doc 4:02403Calibration factorFLOAT32ABCDus2/kgRead/write
HR2404doc 4:02405Correction factorFLOAT32ABCDRead/write
HR2406doc 4:02407Sensor TC (1/100%FLOAT32ABCDRead/write
HR2408doc 4:02409Density parm. AFLOAT32ABCDkg/m3Read/write
HR2410doc 4:02411Density parm. B (*10E6)FLOAT32ABCDRead/write
HR2412doc 4:02413Density TC (1/100%FLOAT32ABCDRead/write
HR2414doc 4:02415Density offsetFLOAT32ABCDkg/m3Read/write
HR2416doc 4:02417Density factorFLOAT32ABCDRead/write
HR2418doc 4:02419Table slopeFLOAT32ABCDkg/sRead/write
HR2421doc 4:02422Fraction offsetFLOAT32ABCDkg/sRead/write
HR2500doc 4:02501Converter typeSTRING[20]Read
HR2510doc 4:02511Converter code no.STRING[20]Read
HR2520doc 4:02521Converter serial no.STRING[20]Read
HR2530doc 4:02531Converter SW versionSTRING[20]Read
HR2540doc 4:02541Sensor typeSTRING[20]Read
HR2550doc 4:02551Sensor code no.STRING[20]Read
HR2560doc 4:02561Sensor serial no.STRING[20]Read
HR2570doc 4:02571Sensor sizeSTRING[20]Read
HR2580doc 4:02581Customer code no.STRING[20]Read
HR2700doc 4:02701Operating timeUINT32ABCDsRead
HR2756doc 4:02757Driver signalFLOAT32ABCDARead
HR2758doc 4:02759Pickup 1 amplitudeFLOAT32ABCDVRead
HR2760doc 4:02761Pickup 2 amplitudeFLOAT32ABCDVRead
HR2762doc 4:02763Sensor frequencyFLOAT32ABCDHzRead
HR2900doc 4:02901LanguageUINT16Read/write0 = English; 1 = Deutsch; 2 = Français; 3 = Dansk; 4 = Svenska; 5 = Suomeksi; 6 = Russian; 7 = Español; 8 = Italiano; 9 = Português
HR2904doc 4:02905Massflow unitUINT16Read/write
HR2905doc 4:02906Massflow pointUINT16Read/write
HR2906doc 4:02907Volumeflow unitUINT16Read/write
HR2907doc 4:02908Volumeflow pointUINT16Read/write
HR2908doc 4:02909Fraction A + B unitUINT16Read/write
HR2909doc 4:02910Fraction A pointUINT16Read/write
HR2911doc 4:02912Fraction B pointUINT16Read/write
HR2912doc 4:02913Totalizer 1 unitUINT16Read/write
HR2913doc 4:02914Totalizer 1 pointUINT16Read/write
HR2914doc 4:02915Totalizer 2 unitUINT16Read/write
HR2915doc 4:02916Totalizer 2 pointUINT16Read/write
HR2916doc 4:02917Density unitUINT16Read/write
HR2917doc 4:02918Density pointUINT16Read/write
HR3000doc 4:03001Absolute MassflowFLOAT32ABCDkg/sRead
HR3002doc 4:03003Absolute VolumeflowFLOAT32ABCDm3/sRead
HR3004doc 4:03005Absolute DensityFLOAT32ABCDkg/m3Read
HR3006doc 4:03007Sensor temperatureFLOAT32ABCD°CRead
HR3008doc 4:03009Fraction AFLOAT32ABCDkg/sRead
HR3010doc 4:03011Fraction BFLOAT32ABCDkg/sRead
HR3012doc 4:03013% fraction AFLOAT32ABCD%Read
HR3014doc 4:03015Totalizer 1FLOAT64ABCDkg or m3Read
HR3018doc 4:03019Totalizer 2/BatchFLOAT64ABCDkg or m3Read
HR3022doc 4:03023Totalizer 1 (float)FLOAT32ABCDkg or m3Read
HR3024doc 4:03025Totalizer 2/Batch (float)FLOAT32ABCDkg or m3Read
HR3099doc 4:03100Update rate setUINT16Read/write
HR3200doc 4:03201System statusBITMAP16Readbit 0 = RunIndicator; bit 1 = ErrorPendingOn; bit 2 = ErrPendChanged; bit 3 = Batching; bit 4 = BatchPaused; bit 5 = Zeroadjusting; bit 6 = Totalizer1Hold; bit 7 = Totalizer2Hold
HR3201doc 4:03202Error pending 1UINT16Read0xFFFF = no error
HR3202doc 4:03203Error pending 2UINT16Read
HR3203doc 4:03204Error pending 3UINT16Read
HR3204doc 4:03205Error pending 4UINT16Read
HR3205doc 4:03206Error pending 5UINT16Read
HR3206doc 4:03207Error pending 6UINT16Read
HR3207doc 4:03208Error pending 7UINT16Read
HR3208doc 4:03209Error pending 8UINT16Read
HR3209doc 4:03210Error pending 9UINT16Read
HR3210doc 4:03211Batch statusUINT16Read0 = Idle; 1 = Ready; 2 = Running; 3 = Paused
HR3211doc 4:03212Zero adjust progressProgress of the zero adjustment, 0-100 %.FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module

What Modbus registers does the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module have?

This map lists 163 registers: 8 coils, 155 holding registers. 104 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints both the Modbus register (4:0xxxx / 0:0xxxx, 1-based) and the Modbus address (0-based) sent on the wire; this map uses the address column. The manual's own example reads absolute massflow 4:03001 with query address 0x0BB8 (3000).

What byte order does the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module?

Start with HR 3000 Absolute Massflow (Mass flow); HR 3002 Absolute Volumeflow (Volume flow); HR 3004 Absolute Density (Density); HR 3006 Sensor temperature (Sensor temperature); HR 3014 Totalizer 1 (Totalizer 1 (double)); HR 3200 System status (System status bits).

How do I enable Modbus control of the Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module?

Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.

Where is the official Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module Modbus documentation?

The source is SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions (A5E00753974-AB), revision 2021-03, published free by Siemens at https://cache.industry.siemens.com/dl/files/906/44880906/att_70364/v1/A5E00753974-ABen_USMII_MODBUS_AOM_OI_en-US.pdf.

More Siemens Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions · A5E00753974-AB · rev. 2021-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.