- QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Sensor (duct humidity / temperature / CO2 / VOC) · Modbus register map
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus register map
Updated 17 November 2026
These Siemens duct sensors talk Modbus RTU over RS-485 and share one holding-register map. The QFM9150/MO measures temperature and relative humidity; the QPM9152/MO adds CO2, an IAQ index and a VOC value. Each reading has a reliability register next to it. The map covers all published measurement, offset, unit, communication and version registers.
This page lists 23 Modbus registers for the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
- Equipment type
- Sensor (duct humidity / temperature / CO2 / VOC)
- Registers
- 23 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585
Integration notes: Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Leave DIP2 switch 7 OFF, wire A/B to the RS-485 bus, set the address over Modbus (default 1, 8E1, auto baud) and poll holding registers 0-15 with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Temperature value | INT16 | Temperature | Read |
| HR 2 | Relative humidity value | UINT16 | Relative humidity | Read |
| HR 4 | CO2 value | UINT16 | CO2 (QPM9152/MO) | Read |
| HR 14 | VOC value | UINT16 | VOC (QPM9152/MO) | Read |
| HR 1 | Temperature reliability | UINT16 | Temperature reliability | Read |
| HR 400 | System unit | UINT16 | Temperature unit | Read/write |
Enable Modbus control & writes
DIP2 switch 7 OFF (default) lets the master configure address, baud and format via registers 764-768; ON uses the DIP switches (DIP1 = address, DIP2 = baud/parity/stop).
Byte order & addressing
- Register number minus 1 = wire address.
- The temperature register follows the unit chosen in register 401 (°C or °F).
- Address 246 is reserved for Climatix on-event addressing.
Network setup
- Bus termination is a jumper (OFF by default).
- A push-button hold of 10-13 s resets address, baud and format to factory defaults.
Watch out for
- If an invalid address is set by DIP switch, new values for registers 764-768 are not applied.
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Temperature value | Signed, hundredths of a degree in the selected unit. | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 1doc 2 | Temperature reliability | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | ||||
| HR | 2doc 3 | Relative humidity value | UINT16 | × 0.01 | % | Read | |||
| HR | 3doc 4 | Humidity reliability | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | ||||
| HR | 4doc 5 | CO2 value | QPM9152/MO only. | UINT16 | ppm | Read | |||
| HR | 5doc 6 | CO2 reliability | QPM9152/MO only. | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | |||
| HR | 6doc 7 | IAQ value | Indoor air quality index, QPM9152/MO only. | UINT16 | × 0.01 | % | Read | ||
| HR | 7doc 8 | IAQ reliability | QPM9152/MO only. | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | |||
| HR | 14doc 15 | VOC value | QPM9152/MO only. | UINT16 | × 0.01 | % | Read | ||
| HR | 15doc 16 | VOC reliability | QPM9152/MO only. | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | |||
| HR | 211doc 212 | VOC sensitivity | QPM9152/MO only. | UINT16 | Read/write | 0 = Slow; 1 = Medium; 2 = Fast | |||
| HR | 222doc 223 | Temperature offset | Range -100 to 100. | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 223doc 224 | Relative humidity offset | Range -100 to 100. | INT16 | × 0.1 | % | Read/write | ||
| HR | 224doc 225 | CO2 offset | Range -2000 to 2000, QPM9152/MO only. | INT16 | ppm | Read/write | |||
| HR | 225doc 226 | IAQ offset | Range -100 to 100, QPM9152/MO only. | INT16 | % | Read/write | |||
| HR | 226doc 227 | VOC pure offset | Range -100 to 100, QPM9152/MO only. | INT16 | % | Read/write | |||
| HR | 400doc 401 | System unit | Temperature unit for values and offsets. | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 763doc 764 | Modbus address | 1-247; 246 is reserved for on-event addressing. | UINT16 | Read/write | ||||
| HR | 764doc 765 | Baud rate | UINT16 | Read/write | 0 = Auto; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 76800; 6 = 115200 | ||||
| HR | 765doc 766 | Transmission format | Start-data-parity-stop bits. | UINT16 | Read/write | 0 = 1-8-E-1; 1 = 1-8-O-1; 2 = 1-8-N-1; 3 = 1-8-N-2 | |||
| HR | 767doc 768 | Bus configuration command | Used for on-event addressing (Climatix). | UINT16 | Read/write | 0 = Ready; 1 = Load; 2 = Discard | |||
| HR | 1285doc 1286 | SW version major/minor | Major in high byte, minor in low byte. | UINT16 | Read | ||||
| HR | 1286doc 1287 | SW version build | UINT16 | Read |
Notes on this map
- All registers are single 16-bit holding registers; no 32-bit values are published.
- CO2, IAQ and VOC registers (5-8, 15-16, 212, 225-227) only carry data on the QPM9152/MO.
- Baud rate default is 0 = Auto (the sensor takes the master baud rate). Default format 1-8-E-1.
- Registers 764-768 cannot be written by the master while DIP2 switch 7 is ON (DIP-switch configuration mode). Address 246 cannot be set from the master.
- Temperature and offset registers are treated as signed because the published ranges go below zero.
- Software version example from the source: [2.01.33] = 0x02010021 (major byte, minor byte, then a 16-bit build).
- Register 767 is marked reserve and is left out.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
What Modbus registers does the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) have?
This map lists 23 registers: 23 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints register numbers and states that numbering starts at 1, so register 1 (temperature) is wire address 0 and register 764 (Modbus address) is wire address 763.
What are the minimum Modbus registers to integrate the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)?
Start with HR 0 Temperature value (Temperature); HR 2 Relative humidity value (Relative humidity); HR 4 CO2 value (CO2 (QPM9152/MO)); HR 14 VOC value (VOC (QPM9152/MO)); HR 1 Temperature reliability (Temperature reliability); HR 400 System unit (Temperature unit).
How do I enable Modbus control of the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)?
DIP2 switch 7 OFF (default) lets the master configure address, baud and format via registers 764-768; ON uses the DIP switches (DIP1 = address, DIP2 = baud/parity/stop).
Where is the official Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus documentation?
The source is Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation (A6V13841469_en--_a), revision 2022-12, published free by Siemens at https://sid.siemens.com/r/A6V13841469.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other valves, actuators & sensors register maps
- Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Water treatment controller (Sensor / controller)
Walchem W900 water treatment controller (Modbus/TCP)
Walchem W900 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W600, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W900 series
All valves, actuators & sensors Modbus register maps →
Source: Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation · A6V13841469_en--_a · rev. 2022-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.