Sensor (duct humidity / temperature / CO2 / VOC) · Modbus register map

Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

These Siemens duct sensors talk Modbus RTU over RS-485 and share one holding-register map. The QFM9150/MO measures temperature and relative humidity; the QPM9152/MO adds CO2, an IAQ index and a VOC value. Each reading has a reliability register next to it. The map covers all published measurement, offset, unit, communication and version registers.

This page lists 23 Modbus registers for the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Equipment type
Sensor (duct humidity / temperature / CO2 / VOC)
Registers
23 (11 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
8E1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585
Source document
Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation · A6V13841469_en--_a · rev. 2022-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)

Integration in brief

Leave DIP2 switch 7 OFF, wire A/B to the RS-485 bus, set the address over Modbus (default 1, 8E1, auto baud) and poll holding registers 0-15 with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Temperature valueINT16TemperatureRead
HR 2Relative humidity valueUINT16Relative humidityRead
HR 4CO2 valueUINT16CO2 (QPM9152/MO)Read
HR 14VOC valueUINT16VOC (QPM9152/MO)Read
HR 1Temperature reliabilityUINT16Temperature reliabilityRead
HR 400System unitUINT16Temperature unitRead/write

Enable Modbus control & writes

DIP2 switch 7 OFF (default) lets the master configure address, baud and format via registers 764-768; ON uses the DIP switches (DIP1 = address, DIP2 = baud/parity/stop).

Byte order & addressing

Network setup

Watch out for

Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

23 of 23 shown
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Temperature valueSigned, hundredths of a degree in the selected unit.INT16× 0.01°C / °FRead
HR1doc 2Temperature reliabilityUINT16Read0 = No error; 1 = Bad reliability / unavailable
HR2doc 3Relative humidity valueUINT16× 0.01%Read
HR3doc 4Humidity reliabilityUINT16Read0 = No error; 1 = Bad reliability / unavailable
HR4doc 5CO2 valueQPM9152/MO only.UINT16ppmRead
HR5doc 6CO2 reliabilityQPM9152/MO only.UINT16Read0 = No error; 1 = Bad reliability / unavailable
HR6doc 7IAQ valueIndoor air quality index, QPM9152/MO only.UINT16× 0.01%Read
HR7doc 8IAQ reliabilityQPM9152/MO only.UINT16Read0 = No error; 1 = Bad reliability / unavailable
HR14doc 15VOC valueQPM9152/MO only.UINT16× 0.01%Read
HR15doc 16VOC reliabilityQPM9152/MO only.UINT16Read0 = No error; 1 = Bad reliability / unavailable
HR211doc 212VOC sensitivityQPM9152/MO only.UINT16Read/write0 = Slow; 1 = Medium; 2 = Fast
HR222doc 223Temperature offsetRange -100 to 100.INT16× 0.1°C / °FRead/write
HR223doc 224Relative humidity offsetRange -100 to 100.INT16× 0.1%Read/write
HR224doc 225CO2 offsetRange -2000 to 2000, QPM9152/MO only.INT16ppmRead/write
HR225doc 226IAQ offsetRange -100 to 100, QPM9152/MO only.INT16%Read/write
HR226doc 227VOC pure offsetRange -100 to 100, QPM9152/MO only.INT16%Read/write
HR400doc 401System unitTemperature unit for values and offsets.UINT16Read/write0 = Celsius; 1 = Fahrenheit
HR763doc 764Modbus address1-247; 246 is reserved for on-event addressing.UINT16Read/write
HR764doc 765Baud rateUINT16Read/write0 = Auto; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 76800; 6 = 115200
HR765doc 766Transmission formatStart-data-parity-stop bits.UINT16Read/write0 = 1-8-E-1; 1 = 1-8-O-1; 2 = 1-8-N-1; 3 = 1-8-N-2
HR767doc 768Bus configuration commandUsed for on-event addressing (Climatix).UINT16Read/write0 = Ready; 1 = Load; 2 = Discard
HR1285doc 1286SW version major/minorMajor in high byte, minor in low byte.UINT16Read
HR1286doc 1287SW version buildUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)

What Modbus registers does the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) have?

This map lists 23 registers: 23 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints register numbers and states that numbering starts at 1, so register 1 (temperature) is wire address 0 and register 764 (Modbus address) is wire address 763.

What are the minimum Modbus registers to integrate the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)?

Start with HR 0 Temperature value (Temperature); HR 2 Relative humidity value (Relative humidity); HR 4 CO2 value (CO2 (QPM9152/MO)); HR 14 VOC value (VOC (QPM9152/MO)); HR 1 Temperature reliability (Temperature reliability); HR 400 System unit (Temperature unit).

How do I enable Modbus control of the Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)?

DIP2 switch 7 OFF (default) lets the master configure address, baud and format via registers 764-768; ON uses the DIP switches (DIP1 = address, DIP2 = baud/parity/stop).

Where is the official Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU) Modbus documentation?

The source is Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation (A6V13841469_en--_a), revision 2022-12, published free by Siemens at https://sid.siemens.com/r/A6V13841469.

More Siemens Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation · A6V13841469_en--_a · rev. 2022-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.