  4. HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)

Sensor (humidity and temperature transmitter) · Modbus register map

Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The HMW87 and HMW87D are the RS-485 Modbus RTU members of the Vaisala HMDW80 wall transmitter family (the D version has a display). This map covers humidity, temperature and calculated readings in float and integer form, status, filtering, serial and display settings and test registers.

This page lists 27 Modbus registers for the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
Equipment type
Sensor (humidity and temperature transmitter)
Registers
27 (9 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
HMW87, HMW87D, HMDW80 Modbus
Source document
HMDW80 Series User Guide · M211510EN-J · rev. 2026-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)

Integration in brief

Read holding registers 1-4 for RH and temperature (CDAB floats), or the integer copies 257-258 (raw x 0.1) if your controller lacks float support.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Relative humidityFLOAT32 CDABRelative humidityRead
HR 2TemperatureFLOAT32 CDABTemperatureRead
HR 8Dew/frost point temperatureFLOAT32 CDABDew pointRead
HR 512Error statusUINT16Error statusRead
HR 515Status codeINT32 CDABStatus codeRead

Enable Modbus control & writes

HMW87 and HMW87D ship as Modbus RTU transmitters on RS-485; change the serial settings with Vaisala Insight PC software, the Indigo80 indicator or registers 1537-1540.

Byte order & addressing

Network setup

Watch out for

Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Relative humidityFLOAT32CDAB%RHRead
HR2doc 3TemperatureFLOAT32CDAB°CRead
HR8doc 9Dew/frost point temperatureFLOAT32CDAB°CRead
HR18doc 19Wet-bulb temperatureFLOAT32CDAB°CRead
HR26doc 27EnthalpyFLOAT32CDABkJ/kgRead
HR256doc 257Relative humidity (integer)INT16× 0.1%RHRead
HR257doc 258Temperature (integer)INT16× 0.1°CRead
HR260doc 261Dew/frost point (integer)INT16× 0.1°CRead
HR265doc 266Wet-bulb temperature (integer)INT16× 0.1°CRead
HR269doc 270Enthalpy (integer)INT16× 0.1kJ/kgRead
HR512doc 513Error statusUINT16Read0 = One or more errors active; 1 = No errors
HR515doc 516Status codeSum of active error codes.INT32CDABReadbit 0 = Temperature measurement error; bit 1 = Humidity measurement error; bit 2 = Humidity sensor failure; bit 3 = Capacitance reference error; bit 4 = Ambient temperature out of range; bit 5 = Firmware checksum mismatch; bit 6 = Device settings corrupted; bit 7 = Additional configuration settings corrupted; bit 8 = Sensor coefficients corrupted; bit 9 = Main configuration settings corrupted; bit 11 = Supply voltage out of range; bit 13 = Non-volatile memory read/write failure
HR517doc 518Security hashChanges when settings change.INT32CDABRead
HR519doc 520RH measurement status0 = OK.BITMAP16Readbit 0 = Not available; bit 6 = Calibration expired; bit 7 = Sensor failure
HR520doc 521T measurement status0 = OK.BITMAP16Readbit 6 = Calibration expired; bit 7 = Sensor failure
HR784doc 785Filtering factor0.001 = maximum filtering, 1.000 = none.FLOAT32CDABRead/write
HR1536doc 1537Modbus address1-247, default 240; 0 = offline.INT16Read/write
HR1537doc 1538Bit rateTakes effect after restart.UINT16Read/write5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600
HR1538doc 1539Parity, data, stop bitsTakes effect after restart.UINT16Read/write0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82
HR1539doc 1540Response delay0-1020 ms.INT16msRead/write
HR1541doc 1542Restart deviceWrite 1 to restart.INT16Write
HR3072doc 3073Display parameter 1HMW87D only; address of the shown value (0x0000, 0x0002, 0x0008, 0x0012, 0x001A).UINT16Read/write
HR3073doc 3074Display parameter 2HMW87D only; as 3073, 0xFFFF disables.UINT16Read/write
HR7680doc 7681Restore settingsWrite 1 to restore factory settings.INT16Write
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 7940Text string testReads the text "-123.45".STRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)

What Modbus registers does the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) have?

This map lists 27 registers: 27 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)?

Start with HR 0 Relative humidity (Relative humidity); HR 2 Temperature (Temperature); HR 8 Dew/frost point temperature (Dew point); HR 512 Error status (Error status); HR 515 Status code (Status code).

How do I enable Modbus control of the Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)?

HMW87 and HMW87D ship as Modbus RTU transmitters on RS-485; change the serial settings with Vaisala Insight PC software, the Indigo80 indicator or registers 1537-1540.

Where is the official Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU) Modbus documentation?

The source is HMDW80 Series User Guide (M211510EN-J), revision 2026-06, published free by Vaisala at https://docs.vaisala.com/r/M211510EN-J/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: HMDW80 Series User Guide · M211510EN-J · rev. 2026-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.