- RM60 PRECICAP radar precipitation sensor (Modbus RTU)
Sensor (precipitation) · Modbus register map
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus register map
Updated 19 November 2026
The Vaisala RM60 is a compact radar precipitation sensor that reports rain intensity, accumulation, snow and precipitation type, plus air pressure when that measurement option is ordered. On RS-485 it serves Modbus RTU (or a text data message). This map covers the measurement floats, drop-size distribution, reset and interval settings, serial settings, status and diagnostic registers, device monitoring and the test registers.
This page lists 37 Modbus registers for the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- RM60 PRECICAP radar precipitation sensor (Modbus RTU)
- Equipment type
- Sensor (precipitation)
- Registers
- 37 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- RM60, PRECICAP RM60, Vaisala RM60
- Source document
- RM60 User Guide · M213218EN-B · rev. 2026-08
Integration notes: Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
Read holding registers 0x0022-0x0027 for intensity and accumulation as low-word-first floats, 0x002A for precipitation type, and check the status words at 0x0200 and 0x0218.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 34 | Precipitation intensity | FLOAT32 CDAB | Precipitation intensity | Read |
| HR 36 | Precipitation accumulation | FLOAT32 CDAB | Precipitation accumulation | Read |
| HR 42 | Precipitation type | FLOAT32 CDAB | Precipitation type (SYNOP) | Read |
| HR 512 | Device status | BITMAP16 | Device status | Read |
| HR 536 | Precipitation measurement status | BITMAP16 | Measurement status | Read |
Enable Modbus control & writes
Order communication option 1 (Modbus RTU), or set Interface mode to Modbus RTU in Insight PC software (Configure device > Communication), save, and power-cycle the sensor.
Byte order & addressing
- Floats and int32 are low word first (CDAB).
- Reading a differential accumulation register resets it.
Network setup
- Option 1 default: RS-485 Modbus RTU, 19200 baud, 8 data bits, even parity, 1 stop bit, address 240.
- After changing settings in Insight, the guide has you power-cycle the sensor (cable off for 5 s) before connecting the Modbus client.
Watch out for
- Read the test registers at 0x1F00-0x1F06 first to confirm addressing and word order.
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 32doc 0x0020 (32) | Air pressure | Only with the air pressure ordering option. | FLOAT32 | CDAB | hPa | Read | ||
| HR | 34doc 0x0022 (34) | Precipitation intensity | FLOAT32 | CDAB | mm/h | Read | |||
| HR | 36doc 0x0024 (36) | Precipitation accumulation | Accumulates until reset. | FLOAT32 | CDAB | mm | Read | ||
| HR | 38doc 0x0026 (38) | Precipitation accumulation (differential) | Accumulates until read or reset. | FLOAT32 | CDAB | mm | Read | ||
| HR | 42doc 0x002a (42) | Precipitation type | SYNOP present-weather code. | FLOAT32 | CDAB | Read | |||
| HR | 44doc 0x002c (44) | Snow accumulation | Accumulates until reset. | FLOAT32 | CDAB | mm | Read | ||
| HR | 46doc 0x002e (46) | Snow accumulation (differential) | Accumulates until read or reset. | FLOAT32 | CDAB | mm | Read | ||
| HR | 512doc 0x0200 (512) | Device status | 0 = device OK. | BITMAP16 | Read | bit 2 = Warning (W) | |||
| HR | 513doc 0x0201 (513) | Device diagnostic code | INT32 | CDAB | Read | ||||
| HR | 515doc 0x0203 (515) | Operating voltage status | 0 = operating voltage OK. | BITMAP16 | Read | bit 2 = Operating voltage too low (U); bit 3 = Operating voltage too high (O) | |||
| HR | 516doc 0x0204 (516) | Operating voltage diagnostic code | INT32 | CDAB | Read | ||||
| HR | 536doc 0x0218 (536) | Precipitation measurement status | 0 = measurement OK. | BITMAP16 | Read | bit 0 = Unavailable (S); bit 1 = Unreliable (R); bit 6 = Calibration expired (C) | |||
| HR | 537doc 0x0219 (537) | Precipitation measurement diagnostic code | INT32 | CDAB | Read | ||||
| HR | 790doc 0x0316 (790) | Measurement interval | 12-600 s, default 12. | FLOAT32 | CDAB | s | Read/write | ||
| HR | 1536doc 0x0600 (1536) | Restart device | Write 1 to restart. | INT16 | Read/write | ||||
| HR | 1538doc 0x0602 (1538) | Bit rate | INT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200 | ||||
| HR | 1539doc 0x0603 (1539) | Parity, data, stop bits | INT16 | Read/write | 0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82; 6 = N71; 7 = N72; 8 = E71; 9 = E72; 10 = O71; 11 = O72 | ||||
| HR | 1541doc 0x0605 (1541) | Interface mode | INT16 | Read/write | 0 = Modbus RTU; 1 = Data messaging | ||||
| HR | 1542doc 0x0606 (1542) | Modbus address | 1-247, default 240. | INT16 | Read/write | ||||
| HR | 7424doc 0x1d00 (7424) | Vendor name | STRING[16] | Read | |||||
| HR | 7432doc 0x1d08 (7432) | Product code | STRING[16] | Read | |||||
| HR | 7440doc 0x1d10 (7440) | Product serial number | STRING[16] | Read | |||||
| HR | 7680doc 0x1e00 (7680) | Restore factory default settings | Write 1 to start. | INT16 | Read/write | ||||
| HR | 7936doc 0x1f00 (7936) | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 0x1f01 (7937) | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read | |||
| HR | 7939doc 0x1f03 (7939) | Text string test | Reads the text "-123.45". | STRING[8] | Read | ||||
| HR | 9472doc 0x2500 (9472) | Reset accumulation counter | Write 1 to zero the four accumulation registers. | INT16 | Read/write | ||||
| HR | 9473doc 0x2501 (9473) | Accumulation counter reset value | Accumulations roll to 0 at this value; 0-1000, default 1000. | INT16 | mm | Read/write | |||
| HR | 32768doc 0x8000 (32768) | Uptime | INT32 | CDAB | s | Read | |||
| HR | 32770doc 0x8002 (32770) | Operating voltage | FLOAT32 | CDAB | V | Read | |||
| HR | 32772doc 0x8004 (32772) | Digital 3.3 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 32774doc 0x8006 (32774) | Digital 5 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 32780doc 0x800c (32780) | Device tilt angle | FLOAT32 | CDAB | deg | Read | |||
| HR | 34816doc 0x8800 (34816) | Autocalibration | INT16 | Read | 0 = Up to date; 1 = In progress | ||||
| HR | 34817doc 0x8801 (34817) | Reflectivity factor | FLOAT32 | CDAB | dBZ | Read | |||
| HR | 34819doc 0x8803 (34819) | DSD bin 1 | Drop size distribution; bins 2-22 follow every 2 registers. | FLOAT32 | CDAB | m-3 mm-1 | Read | ||
| HR | 34861doc 0x882d (34861) | DSD bin 22 | FLOAT32 | CDAB | m-3 mm-1 | Read |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16; function 43/14 reads device identification.
- int32 and float values are two registers in little-endian word order (least significant word first, CDAB), as the guide's data-type table states and its -123.45 test example shows. Bytes inside each register are big-endian.
- The 'differential' accumulation registers restart from zero each time they are read (or reset).
- Left out: DSD bins 2-21 (same pattern), the messaging address, autosend message and interval (data-messaging mode only), configuration code, manufacturing date, product name and the module identification strings.
- Air pressure (0x0020) is an additional measurement ordering option in the guide.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
What Modbus registers does the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) have?
This map lists 37 registers: 37 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints each register as a hex address with its decimal value (sent on the wire as-is) plus a 'register number' that is the address + 1. The test registers start at 0x1F00, which the guide reads directly.
What byte order does the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)?
Start with HR 34 Precipitation intensity (Precipitation intensity); HR 36 Precipitation accumulation (Precipitation accumulation); HR 42 Precipitation type (Precipitation type (SYNOP)); HR 512 Device status (Device status); HR 536 Precipitation measurement status (Measurement status).
How do I enable Modbus control of the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)?
Order communication option 1 (Modbus RTU), or set Interface mode to Modbus RTU in Insight PC software (Configure device > Communication), save, and power-cycle the sensor.
Where is the official Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus documentation?
The source is RM60 User Guide (M213218EN-B), revision 2026-08, published free by Vaisala at https://docs.vaisala.com/r/M213218EN-B/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series - Sensor (room temperature / humidity)
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor
ACI Wall Plate Series stainless wall-plate temperature, RH and temperature/RH sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000931).
Also known as: A/RH-BM wall plate, Wall Plate Series BACnet Modbus - Sensor (particulate matter)
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
DFRobot SEN0662 Gravity BMV080 module with its DIP switch set to UART, firmware V1.0.0 / register map version 4, per the DFRobot wiki register page.
Also known as: SEN0662, Gravity BMV080, BMV080 PM2.5 sensor, DFRobot BMV080 - Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT - Sensor (CO2, humidity, temperature module)
Sensirion SCD30 CO2, humidity and temperature sensor module
Sensirion SCD30 sensor module with the SEL pin pulled high at power-up (Modbus mode), per interface description version 1.0.
Also known as: SCD30
All valves, actuators & sensors Modbus register maps →
Source: RM60 User Guide · M213218EN-B · rev. 2026-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.