Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The Vaisala RM60 is a compact radar precipitation sensor that reports rain intensity, accumulation, snow and precipitation type, plus air pressure when that measurement option is ordered. On RS-485 it serves Modbus RTU (or a text data message). This map covers the measurement floats, drop-size distribution, reset and interval settings, serial settings, status and diagnostic registers, device monitoring and the test registers.

This page lists 37 Modbus registers for the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
RM60 PRECICAP radar precipitation sensor (Modbus RTU)
Equipment type
Sensor (precipitation)
Registers
37 (9 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
RM60, PRECICAP RM60, Vaisala RM60
Source document
RM60 User Guide · M213218EN-B · rev. 2026-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)

Integration in brief

Read holding registers 0x0022-0x0027 for intensity and accumulation as low-word-first floats, 0x002A for precipitation type, and check the status words at 0x0200 and 0x0218.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 34Precipitation intensityFLOAT32 CDABPrecipitation intensityRead
HR 36Precipitation accumulationFLOAT32 CDABPrecipitation accumulationRead
HR 42Precipitation typeFLOAT32 CDABPrecipitation type (SYNOP)Read
HR 512Device statusBITMAP16Device statusRead
HR 536Precipitation measurement statusBITMAP16Measurement statusRead

Enable Modbus control & writes

Order communication option 1 (Modbus RTU), or set Interface mode to Modbus RTU in Insight PC software (Configure device > Communication), save, and power-cycle the sensor.

Byte order & addressing

Network setup

Watch out for

Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

37 of 37 shown
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR32doc 0x0020 (32)Air pressureOnly with the air pressure ordering option.FLOAT32CDABhPaRead
HR34doc 0x0022 (34)Precipitation intensityFLOAT32CDABmm/hRead
HR36doc 0x0024 (36)Precipitation accumulationAccumulates until reset.FLOAT32CDABmmRead
HR38doc 0x0026 (38)Precipitation accumulation (differential)Accumulates until read or reset.FLOAT32CDABmmRead
HR42doc 0x002a (42)Precipitation typeSYNOP present-weather code.FLOAT32CDABRead
HR44doc 0x002c (44)Snow accumulationAccumulates until reset.FLOAT32CDABmmRead
HR46doc 0x002e (46)Snow accumulation (differential)Accumulates until read or reset.FLOAT32CDABmmRead
HR512doc 0x0200 (512)Device status0 = device OK.BITMAP16Readbit 2 = Warning (W)
HR513doc 0x0201 (513)Device diagnostic codeINT32CDABRead
HR515doc 0x0203 (515)Operating voltage status0 = operating voltage OK.BITMAP16Readbit 2 = Operating voltage too low (U); bit 3 = Operating voltage too high (O)
HR516doc 0x0204 (516)Operating voltage diagnostic codeINT32CDABRead
HR536doc 0x0218 (536)Precipitation measurement status0 = measurement OK.BITMAP16Readbit 0 = Unavailable (S); bit 1 = Unreliable (R); bit 6 = Calibration expired (C)
HR537doc 0x0219 (537)Precipitation measurement diagnostic codeINT32CDABRead
HR790doc 0x0316 (790)Measurement interval12-600 s, default 12.FLOAT32CDABsRead/write
HR1536doc 0x0600 (1536)Restart deviceWrite 1 to restart.INT16Read/write
HR1538doc 0x0602 (1538)Bit rateINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200
HR1539doc 0x0603 (1539)Parity, data, stop bitsINT16Read/write0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82; 6 = N71; 7 = N72; 8 = E71; 9 = E72; 10 = O71; 11 = O72
HR1541doc 0x0605 (1541)Interface modeINT16Read/write0 = Modbus RTU; 1 = Data messaging
HR1542doc 0x0606 (1542)Modbus address1-247, default 240.INT16Read/write
HR7424doc 0x1d00 (7424)Vendor nameSTRING[16]Read
HR7432doc 0x1d08 (7432)Product codeSTRING[16]Read
HR7440doc 0x1d10 (7440)Product serial numberSTRING[16]Read
HR7680doc 0x1e00 (7680)Restore factory default settingsWrite 1 to start.INT16Read/write
HR7936doc 0x1f00 (7936)Signed integer testAlways reads -12345.INT16Read
HR7937doc 0x1f01 (7937)Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 0x1f03 (7939)Text string testReads the text "-123.45".STRING[8]Read
HR9472doc 0x2500 (9472)Reset accumulation counterWrite 1 to zero the four accumulation registers.INT16Read/write
HR9473doc 0x2501 (9473)Accumulation counter reset valueAccumulations roll to 0 at this value; 0-1000, default 1000.INT16mmRead/write
HR32768doc 0x8000 (32768)UptimeINT32CDABsRead
HR32770doc 0x8002 (32770)Operating voltageFLOAT32CDABVRead
HR32772doc 0x8004 (32772)Digital 3.3 V supplyFLOAT32CDABVRead
HR32774doc 0x8006 (32774)Digital 5 V supplyFLOAT32CDABVRead
HR32780doc 0x800c (32780)Device tilt angleFLOAT32CDABdegRead
HR34816doc 0x8800 (34816)AutocalibrationINT16Read0 = Up to date; 1 = In progress
HR34817doc 0x8801 (34817)Reflectivity factorFLOAT32CDABdBZRead
HR34819doc 0x8803 (34819)DSD bin 1Drop size distribution; bins 2-22 follow every 2 registers.FLOAT32CDABm-3 mm-1Read
HR34861doc 0x882d (34861)DSD bin 22FLOAT32CDABm-3 mm-1Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)

What Modbus registers does the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) have?

This map lists 37 registers: 37 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints each register as a hex address with its decimal value (sent on the wire as-is) plus a 'register number' that is the address + 1. The test registers start at 0x1F00, which the guide reads directly.

What byte order does the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)?

Start with HR 34 Precipitation intensity (Precipitation intensity); HR 36 Precipitation accumulation (Precipitation accumulation); HR 42 Precipitation type (Precipitation type (SYNOP)); HR 512 Device status (Device status); HR 536 Precipitation measurement status (Measurement status).

How do I enable Modbus control of the Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)?

Order communication option 1 (Modbus RTU), or set Interface mode to Modbus RTU in Insight PC software (Configure device > Communication), save, and power-cycle the sensor.

Where is the official Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU) Modbus documentation?

The source is RM60 User Guide (M213218EN-B), revision 2026-08, published free by Vaisala at https://docs.vaisala.com/r/M213218EN-B/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: RM60 User Guide · M213218EN-B · rev. 2026-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.