Sensor (room temperature / humidity) · Modbus register map

ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus register map

Updated 17 November 2026

Short answer

ACI's stainless wall-plate room sensor for temperature, humidity or both, with a DIP-switch selectable BACnet MS/TP or Modbus RTU RS-485 interface and no analog output. Readings are signed tenths in input registers; a few holding registers set units, offsets and user labels.

This page lists 21 Modbus registers for the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ACI (Automation Components Inc.)’s own free documentation (linked below) and checked against it.

Manufacturer
ACI (Automation Components Inc.)
Model
Wall Plate Series BACnet/Modbus temperature/RH sensor
Equipment type
Sensor (room temperature / humidity)
Registers
21 (9 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
A/RH-BM wall plate, Wall Plate Series BACnet Modbus
Source document
Wall Plate Series BACnet / Modbus User's Guide · I0000931
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor

Integration in brief

Switch the sensor to Modbus with SW4 DIP 4, give it a non-zero address and a fixed baud rate, then read input registers 2 (temperature, tenths) and 3 (RH) with function 04. Check input registers 9000/9001 once to confirm your master decodes unsigned and signed values correctly.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2Temperature sensor valueINT16Temperature valueRead
IR 3RH sensor valueUINT16Relative humidityRead
HR 0Temperature unitsUINT16Temperature unitRead/write
IR 0Sensors presentBITMAP16Which sensors are fittedRead
IR 9000Unsigned test valueUINT16Decoding check 12345Read
IR 9001Signed test valueINT16Signed decoding check -12345Read

Enable Modbus control & writes

SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.

Byte order & addressing

Network setup

Watch out for

ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

21 of 21 shown
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1000doc 1001Test mode enable1 = IR3/IR4 return the test values in HR1001/HR1002; not kept after reset.BITRead/write0 = Disabled (live values); 1 = Enabled (test values)
IR0doc 1Sensors presentWhich sensing elements are fitted.BITMAP16Readbit 0 = Temperature sensor present; bit 1 = RH sensor present
IR2doc 3Temperature sensor valueTenths, in the unit chosen in HR1 (address 0).INT16× 0.1Read
IR3doc 4RH sensor valueUINT16× 0.1%RHRead
IR2000doc 2001Temperature range minLowest reportable temperature, tenths.INT16× 0.1Read
IR2001doc 2002Temperature range maxHighest reportable temperature, tenths.INT16× 0.1Read
IR2002doc 2003RH range minUINT16× 0.1%RHRead
IR2003doc 2004RH range maxUINT16× 0.1%RHRead
IR9000doc 9001Unsigned test valueAlways 12345; checks decoding.UINT16Read
IR9001doc 9002Signed test valueAlways -12345; checks signed decoding.INT16Read
IR9002doc 9003-9006Test stringAlways "-123.45", null terminated.STRING[8]Read
IR9006doc 9007-9010Serial numberASCII, not null terminated.STRING[8]Read
IR9010doc 9011-9016Firmware versionASCII, not null terminated, e.g. 02.00.000.90.STRING[12]Read
HR0doc 1Temperature unitsUnit used for the temperature value and ranges.UINT16Read/write62 = °C; 63 = K; 64 = °F
HR1doc 2Temperature offsetAdded to the reading; -5.0 to 5.0 °C/K (-9.0 to 9.0 °F).INT16× 0.1Read/write
HR2doc 3RH offsetAdded to the RH reading; -10.0 to 10.0 %RH.INT16× 0.1%RHRead/write
HR1000doc 1001Test mode temperature valueReturned by IR3 while test mode is on.INT16× 0.1Read/write
HR1001doc 1002Test mode RH valueReturned by IR4 while test mode is on.UINT16× 0.1%RHRead/write
HR9000doc 9001-9016Device nameUser text, null terminated.STRING[32]Read/write
HR9016doc 9017-9048Device locationUser text, null terminated.STRING[64]Read/write
HR9048doc 9049-9080Device descriptionUser text, null terminated.STRING[64]Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor

What Modbus registers does the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor have?

This map lists 21 registers: 1 coil, 12 input registers, 8 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a Reference (1-based, e.g. 3) and an Address (0-based, e.g. 2). The documented field here holds the Reference; the address field holds the Address column, which is what goes on the wire.

What are the minimum Modbus registers to integrate the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor?

Start with IR 2 Temperature sensor value (Temperature value); IR 3 RH sensor value (Relative humidity); HR 0 Temperature units (Temperature unit); IR 0 Sensors present (Which sensors are fitted); IR 9000 Unsigned test value (Decoding check 12345); IR 9001 Signed test value (Signed decoding check -12345).

How do I enable Modbus control of the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor?

SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.

Where is the official ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus documentation?

The source is Wall Plate Series BACnet / Modbus User's Guide (I0000931), published free by ACI (Automation Components Inc.) at https://www.workaci.com/media/791/download.

More ACI (Automation Components Inc.) Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Wall Plate Series BACnet / Modbus User's Guide · I0000931. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.