- Wall Plate Series BACnet/Modbus temperature/RH sensor
Sensor (room temperature / humidity) · Modbus register map
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus register map
Updated 17 November 2026
ACI's stainless wall-plate room sensor for temperature, humidity or both, with a DIP-switch selectable BACnet MS/TP or Modbus RTU RS-485 interface and no analog output. Readings are signed tenths in input registers; a few holding registers set units, offsets and user labels.
This page lists 21 Modbus registers for the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ACI (Automation Components Inc.)’s own free documentation (linked below) and checked against it.
- Manufacturer
- ACI (Automation Components Inc.)
- Model
- Wall Plate Series BACnet/Modbus temperature/RH sensor
- Equipment type
- Sensor (room temperature / humidity)
- Registers
- 21 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- A/RH-BM wall plate, Wall Plate Series BACnet Modbus
- Source document
- Wall Plate Series BACnet / Modbus User's Guide · I0000931
Integration notes: ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor
Switch the sensor to Modbus with SW4 DIP 4, give it a non-zero address and a fixed baud rate, then read input registers 2 (temperature, tenths) and 3 (RH) with function 04. Check input registers 9000/9001 once to confirm your master decodes unsigned and signed values correctly.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2 | Temperature sensor value | INT16 | Temperature value | Read |
| IR 3 | RH sensor value | UINT16 | Relative humidity | Read |
| HR 0 | Temperature units | UINT16 | Temperature unit | Read/write |
| IR 0 | Sensors present | BITMAP16 | Which sensors are fitted | Read |
| IR 9000 | Unsigned test value | UINT16 | Decoding check 12345 | Read |
| IR 9001 | Signed test value | INT16 | Signed decoding check -12345 | Read |
Enable Modbus control & writes
SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.
Byte order & addressing
- Temperature unit is set by holding register 0, not fixed; values are tenths of that unit.
- Test mode (coil 1000) substitutes HR1000/HR1001 values into the live registers and is cleared by reset or power cycle.
- String registers: test string and user text are null terminated, serial number and firmware are not.
Network setup
- Set SW4 DIP 4 ON to select Modbus (factory default is BACnet MS/TP), then power-cycle or press reset.
- Set the address on switches 1-7 (binary, 1-127). Address 0 is the factory default and cannot be used with Modbus.
- Set the baud rate on switches 8-10 (9600-115200); auto-baud does not work in Modbus mode.
- SW4 PAR 2 / PAR 1 DIP switches (1 = ON) set framing: 0/0 8-E-1, 0/1 8-O-1, 1/0 8-N-2, 1/1 8-N-1.
- Move the EOL jumper to EN on the last device of the RS-485 trunk (default DIS).
Watch out for
- The factory default is BACnet MS/TP with auto-baud; a sensor left at defaults will not answer Modbus.
- Address 0 is invalid for Modbus.
- 8-None-1 framing is labelled non-standard by ACI.
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000doc 1001 | Test mode enable | 1 = IR3/IR4 return the test values in HR1001/HR1002; not kept after reset. | BIT | Read/write | 0 = Disabled (live values); 1 = Enabled (test values) | |||
| IR | 0doc 1 | Sensors present | Which sensing elements are fitted. | BITMAP16 | Read | bit 0 = Temperature sensor present; bit 1 = RH sensor present | |||
| IR | 2doc 3 | Temperature sensor value | Tenths, in the unit chosen in HR1 (address 0). | INT16 | × 0.1 | Read | |||
| IR | 3doc 4 | RH sensor value | UINT16 | × 0.1 | %RH | Read | |||
| IR | 2000doc 2001 | Temperature range min | Lowest reportable temperature, tenths. | INT16 | × 0.1 | Read | |||
| IR | 2001doc 2002 | Temperature range max | Highest reportable temperature, tenths. | INT16 | × 0.1 | Read | |||
| IR | 2002doc 2003 | RH range min | UINT16 | × 0.1 | %RH | Read | |||
| IR | 2003doc 2004 | RH range max | UINT16 | × 0.1 | %RH | Read | |||
| IR | 9000doc 9001 | Unsigned test value | Always 12345; checks decoding. | UINT16 | Read | ||||
| IR | 9001doc 9002 | Signed test value | Always -12345; checks signed decoding. | INT16 | Read | ||||
| IR | 9002doc 9003-9006 | Test string | Always "-123.45", null terminated. | STRING[8] | Read | ||||
| IR | 9006doc 9007-9010 | Serial number | ASCII, not null terminated. | STRING[8] | Read | ||||
| IR | 9010doc 9011-9016 | Firmware version | ASCII, not null terminated, e.g. 02.00.000.90. | STRING[12] | Read | ||||
| HR | 0doc 1 | Temperature units | Unit used for the temperature value and ranges. | UINT16 | Read/write | 62 = °C; 63 = K; 64 = °F | |||
| HR | 1doc 2 | Temperature offset | Added to the reading; -5.0 to 5.0 °C/K (-9.0 to 9.0 °F). | INT16 | × 0.1 | Read/write | |||
| HR | 2doc 3 | RH offset | Added to the RH reading; -10.0 to 10.0 %RH. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 1000doc 1001 | Test mode temperature value | Returned by IR3 while test mode is on. | INT16 | × 0.1 | Read/write | |||
| HR | 1001doc 1002 | Test mode RH value | Returned by IR4 while test mode is on. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 9000doc 9001-9016 | Device name | User text, null terminated. | STRING[32] | Read/write | ||||
| HR | 9016doc 9017-9048 | Device location | User text, null terminated. | STRING[64] | Read/write | ||||
| HR | 9048doc 9049-9080 | Device description | User text, null terminated. | STRING[64] | Read/write |
Notes on this map
- The map prints a 1-based Reference column and a 0-based Address column side by side (e.g. Reference 3 = Address 2 for the temperature value); this map uses the Address column.
- RH values and RH range registers are described only as tenths of %RH without a sign statement; they are listed as unsigned since RH cannot be negative. The RH offset is explicitly allowed to be negative (example -16 = -1.6 %RH) so it is INT16.
- Temperature registers carry no fixed unit: the unit follows holding register 0 (62 °C, 63 K, 64 °F).
- Temperature-only models have no RH element and RH-only models no temperature element; input register 0 shows which is fitted.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor
What Modbus registers does the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor have?
This map lists 21 registers: 1 coil, 12 input registers, 8 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a Reference (1-based, e.g. 3) and an Address (0-based, e.g. 2). The documented field here holds the Reference; the address field holds the Address column, which is what goes on the wire.
What are the minimum Modbus registers to integrate the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor?
Start with IR 2 Temperature sensor value (Temperature value); IR 3 RH sensor value (Relative humidity); HR 0 Temperature units (Temperature unit); IR 0 Sensors present (Which sensors are fitted); IR 9000 Unsigned test value (Decoding check 12345); IR 9001 Signed test value (Signed decoding check -12345).
How do I enable Modbus control of the ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor?
SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.
Where is the official ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor Modbus documentation?
The source is Wall Plate Series BACnet / Modbus User's Guide (I0000931), published free by ACI (Automation Components Inc.) at https://www.workaci.com/media/791/download.
More ACI (Automation Components Inc.) Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (particulate matter)
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
DFRobot SEN0662 Gravity BMV080 module with its DIP switch set to UART, firmware V1.0.0 / register map version 4, per the DFRobot wiki register page.
Also known as: SEN0662, Gravity BMV080, BMV080 PM2.5 sensor, DFRobot BMV080 - Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT - Sensor (CO2, humidity, temperature module)
Sensirion SCD30 CO2, humidity and temperature sensor module
Sensirion SCD30 sensor module with the SEL pin pulled high at power-up (Modbus mode), per interface description version 1.0.
Also known as: SCD30 - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340
All valves, actuators & sensors Modbus register maps →
Source: Wall Plate Series BACnet / Modbus User's Guide · I0000931. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.