- Averaging Series BACnet/Modbus duct averaging temperature sensor
Sensor (duct averaging temperature) · Modbus register map
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor Modbus register map
Updated 17 November 2026
ACI's duct averaging temperature sensor (continuous copper element or 4/9-point flexible element) with a DIP-switch selectable BACnet MS/TP or Modbus RTU RS-485 interface. It shares the same Modbus map as ACI's Wall Plate Series; the temperature is a signed tenths value in input register 2.
This page lists 21 Modbus registers for the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ACI (Automation Components Inc.)’s own free documentation (linked below) and checked against it.
- Manufacturer
- ACI (Automation Components Inc.)
- Model
- Averaging Series BACnet/Modbus duct averaging temperature sensor
- Equipment type
- Sensor (duct averaging temperature)
- Registers
- 21 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- Copper Averaging, Flexible Averaging, Averaging Series BACnet Modbus
- Source document
- Averaging Series BACnet / Modbus User's Guide · I0000932
Integration notes: ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
Switch the sensor to Modbus with SW4 DIP 4, give it a non-zero address and a fixed baud rate, then read input register 2 (temperature, tenths) with function 04. Check input registers 9000/9001 once to confirm your master decodes unsigned and signed values correctly.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2 | Temperature sensor value | INT16 | Temperature value | Read |
| HR 0 | Temperature units | UINT16 | Temperature unit | Read/write |
| IR 0 | Sensors present | BITMAP16 | Which sensors are fitted | Read |
| IR 9000 | Unsigned test value | UINT16 | Decoding check 12345 | Read |
| IR 9001 | Signed test value | INT16 | Signed decoding check -12345 | Read |
Enable Modbus control & writes
SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.
Byte order & addressing
- Temperature unit is set by holding register 0, not fixed; values are tenths of that unit.
- Test mode (coil 1000) substitutes HR1000/HR1001 values into the live registers and is cleared by reset or power cycle.
- String registers: test string and user text are null terminated, serial number and firmware are not.
Network setup
- Set SW4 DIP 4 ON to select Modbus (factory default is BACnet MS/TP), then power-cycle or press reset.
- Set the address on switches 1-7 (binary, 1-127). Address 0 is the factory default and cannot be used with Modbus.
- Set the baud rate on switches 8-10 (9600-115200); auto-baud does not work in Modbus mode.
- SW4 PAR 2 / PAR 1 DIP switches (1 = ON) set framing: 0/0 8-E-1, 0/1 8-O-1, 1/0 8-N-2, 1/1 8-N-1.
- Move the EOL jumper to EN on the last device of the RS-485 trunk (default DIS).
Watch out for
- The factory default is BACnet MS/TP with auto-baud; a sensor left at defaults will not answer Modbus.
- Address 0 is invalid for Modbus.
- 8-None-1 framing is labelled non-standard by ACI.
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000doc 1001 | Test mode enable | 1 = IR3/IR4 return the test values in HR1001/HR1002; not kept after reset. | BIT | Read/write | 0 = Disabled (live values); 1 = Enabled (test values) | |||
| IR | 0doc 1 | Sensors present | Which sensing elements are fitted. | BITMAP16 | Read | bit 0 = Temperature sensor present; bit 1 = RH sensor present | |||
| IR | 2doc 3 | Temperature sensor value | Tenths, in the unit chosen in HR1 (address 0). | INT16 | × 0.1 | Read | |||
| IR | 3doc 4 | RH sensor value | Not used on this temperature-only product family. | UINT16 | × 0.1 | %RH | Read | ||
| IR | 2000doc 2001 | Temperature range min | Lowest reportable temperature, tenths. | INT16 | × 0.1 | Read | |||
| IR | 2001doc 2002 | Temperature range max | Highest reportable temperature, tenths. | INT16 | × 0.1 | Read | |||
| IR | 2002doc 2003 | RH range min | UINT16 | × 0.1 | %RH | Read | |||
| IR | 2003doc 2004 | RH range max | UINT16 | × 0.1 | %RH | Read | |||
| IR | 9000doc 9001 | Unsigned test value | Always 12345; checks decoding. | UINT16 | Read | ||||
| IR | 9001doc 9002 | Signed test value | Always -12345; checks signed decoding. | INT16 | Read | ||||
| IR | 9002doc 9003-9006 | Test string | Always "-123.45", null terminated. | STRING[8] | Read | ||||
| IR | 9006doc 9007-9010 | Serial number | ASCII, not null terminated. | STRING[8] | Read | ||||
| IR | 9010doc 9011-9016 | Firmware version | ASCII, not null terminated, e.g. 02.00.000.90. | STRING[12] | Read | ||||
| HR | 0doc 1 | Temperature units | Unit used for the temperature value and ranges. | UINT16 | Read/write | 62 = °C; 63 = K; 64 = °F | |||
| HR | 1doc 2 | Temperature offset | Added to the reading; -5.0 to 5.0 °C/K (-9.0 to 9.0 °F). | INT16 | × 0.1 | Read/write | |||
| HR | 2doc 3 | RH offset | Added to the RH reading; -10.0 to 10.0 %RH. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 1000doc 1001 | Test mode temperature value | Returned by IR3 while test mode is on. | INT16 | × 0.1 | Read/write | |||
| HR | 1001doc 1002 | Test mode RH value | Returned by IR4 while test mode is on. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 9000doc 9001-9016 | Device name | User text, null terminated. | STRING[32] | Read/write | ||||
| HR | 9016doc 9017-9048 | Device location | User text, null terminated. | STRING[64] | Read/write | ||||
| HR | 9048doc 9049-9080 | Device description | User text, null terminated. | STRING[64] | Read/write |
Notes on this map
- The map prints a 1-based Reference column and a 0-based Address column side by side (e.g. Reference 3 = Address 2 for the temperature value); this map uses the Address column.
- RH values and RH range registers are described only as tenths of %RH without a sign statement; they are listed as unsigned since RH cannot be negative. The RH offset is explicitly allowed to be negative (example -16 = -1.6 %RH) so it is INT16.
- Temperature registers carry no fixed unit: the unit follows holding register 0 (62 °C, 63 K, 64 °F).
- The map in this guide is the same as the Wall Plate guide and still lists the RH registers; this product is temperature-only, so the RH registers are not expected to carry a measurement (input register 0 bit 1 shows whether an RH sensor is present).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
What Modbus registers does the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor have?
This map lists 21 registers: 1 coil, 12 input registers, 8 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a Reference (1-based, e.g. 3) and an Address (0-based, e.g. 2). The documented field here holds the Reference; the address field holds the Address column, which is what goes on the wire.
What are the minimum Modbus registers to integrate the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor?
Start with IR 2 Temperature sensor value (Temperature value); HR 0 Temperature units (Temperature unit); IR 0 Sensors present (Which sensors are fitted); IR 9000 Unsigned test value (Decoding check 12345); IR 9001 Signed test value (Signed decoding check -12345).
How do I enable Modbus control of the ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor?
SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.
Where is the official ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor Modbus documentation?
The source is Averaging Series BACnet / Modbus User's Guide (I0000932), published free by ACI (Automation Components Inc.) at https://www.workaci.com/media/809/download.
More ACI (Automation Components Inc.) Modbus register maps
Other valves, actuators & sensors register maps
- Actuator / valve (damper and valve actuator)
Belimo Air/water actuators with Modbus RTU (..24A-MOD)
Belimo ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD air/water actuators, per Modbus interface description edition 2026-05 / V3.08.
Also known as: LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD - Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280
All valves, actuators & sensors Modbus register maps →
Source: Averaging Series BACnet / Modbus User's Guide · I0000932. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.