Sensor · Modbus register map

Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus register map

Updated 17 November 2026

Short answer

Wall-mounted electrochemical carbon monoxide transmitter (0-500 ppm) for garages and plant rooms. It is a Modbus RTU subordinate with fixed 9600 8N1 serial settings and a DIP-switch address, and it exposes just two holding registers: sensor status and the CO reading in ppm.

This page lists 2 Modbus registers for the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.

Manufacturer
Johnson Controls
Model
GS3000 indoor Modbus carbon monoxide transmitter
Equipment type
Sensor
Registers
2 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
GS3000, GS3001, 24-11484-00021
Source document
GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide · 24-11484-00021 Rev. -- · rev. 2020-10-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter

Integration in brief

Set a unique address on the 8-way DIP switch, wire A-/B+/shield, and poll holding registers 0-1 at 9600 8N1: status then CO in ppm.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1CO ConcentrationUINT16CO level in ppmRead
HR 0CO Sensor StatusUINT16Sensor status (abnormal = fault)Read

Enable Modbus control & writes

Modbus is always on; set the address (1-255) with the DIP switch before connecting to the network.

Byte order & addressing

Network setup

Watch out for

Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

2 of 2 shown
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001CO Sensor Status0x0000 normal, 0x0001 abnormal status.UINT16Read0 = Normal; 1 = Abnormal
HR1doc 40002CO ConcentrationMeasured carbon monoxide, 0-500 ppm range.UINT16ppmRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter

What Modbus registers does the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter have?

This map lists 2 registers: 2 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 lists Modbus address 40001 with offset +0 and 40002 with offset +1, and the example query frames (Figure 11) send start address 0x0000 for status and 0x0001 for CO, so the wire addresses are 0 and 1.

What are the minimum Modbus registers to integrate the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter?

Start with HR 1 CO Concentration (CO level in ppm); HR 0 CO Sensor Status (Sensor status (abnormal = fault)).

How do I enable Modbus control of the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter?

Modbus is always on; set the address (1-255) with the DIP switch before connecting to the network.

Where is the official Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus documentation?

The source is GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide (24-11484-00021 Rev. --), revision 2020-10-01, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/Johnson-Controls/en-US/GS3000-Indoor-Modbus-Carbon-Monoxide-Transmitter-Installation-Guide.

More Johnson Controls Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide · 24-11484-00021 Rev. -- · rev. 2020-10-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.