- GS3000 indoor Modbus carbon monoxide transmitter
Sensor · Modbus register map
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus register map
Updated 17 November 2026
Wall-mounted electrochemical carbon monoxide transmitter (0-500 ppm) for garages and plant rooms. It is a Modbus RTU subordinate with fixed 9600 8N1 serial settings and a DIP-switch address, and it exposes just two holding registers: sensor status and the CO reading in ppm.
This page lists 2 Modbus registers for the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Johnson Controls
- Model
- GS3000 indoor Modbus carbon monoxide transmitter
- Equipment type
- Sensor
- Registers
- 2 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- GS3000, GS3001, 24-11484-00021
Integration notes: Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Set a unique address on the 8-way DIP switch, wire A-/B+/shield, and poll holding registers 0-1 at 9600 8N1: status then CO in ppm.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | CO Concentration | UINT16 | CO level in ppm | Read |
| HR 0 | CO Sensor Status | UINT16 | Sensor status (abnormal = fault) | Read |
Enable Modbus control & writes
Modbus is always on; set the address (1-255) with the DIP switch before connecting to the network.
Byte order & addressing
- Address is binary on DIP switches weighted 128-64-32-16-8-4-2-1.
- Baud, parity and stop bits are fixed (9600, none, 1).
Network setup
- Fit the PCB EOL jumper (121 ohm) only on the devices at each end of the segment.
- Use 22 AWG shielded twisted pair; ground the shield at one end; max 4000 ft per segment.
Watch out for
- Half-wave power supply: keep the same circuit ground on all devices and the controller.
- Allow 30 min warm-up before calibrating.
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | CO Sensor Status | 0x0000 normal, 0x0001 abnormal status. | UINT16 | Read | 0 = Normal; 1 = Abnormal | |||
| HR | 1doc 40002 | CO Concentration | Measured carbon monoxide, 0-500 ppm range. | UINT16 | ppm | Read |
Notes on this map
- Source is Johnson Controls' documentation portal; the guide's PDF attachment is 241148400021.pdf.
- Both registers are unsigned 16-bit words and read-only. Figure 11 shows both being read with function 03 (Read Holding Registers), one register per request; exception codes 01, 02 and 03 are returned for bad requests.
- Serial settings other than the address are fixed at the factory (the guide notes they may be factory-customised).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
What Modbus registers does the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter have?
This map lists 2 registers: 2 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 lists Modbus address 40001 with offset +0 and 40002 with offset +1, and the example query frames (Figure 11) send start address 0x0000 for status and 0x0001 for CO, so the wire addresses are 0 and 1.
What are the minimum Modbus registers to integrate the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter?
Start with HR 1 CO Concentration (CO level in ppm); HR 0 CO Sensor Status (Sensor status (abnormal = fault)).
How do I enable Modbus control of the Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter?
Modbus is always on; set the address (1-255) with the DIP switch before connecting to the network.
Where is the official Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter Modbus documentation?
The source is GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide (24-11484-00021 Rev. --), revision 2020-10-01, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/Johnson-Controls/en-US/GS3000-Indoor-Modbus-Carbon-Monoxide-Transmitter-Installation-Guide.
More Johnson Controls Modbus register maps
- Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Other valves, actuators & sensors register maps
- Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251
All valves, actuators & sensors Modbus register maps →
Source: GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide · 24-11484-00021 Rev. -- · rev. 2020-10-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.