Thermostat · Modbus register map
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module Modbus register map
Updated 17 November 2026
Modular electronic controller for HVAC and refrigeration: up to three sensor inputs drive up to ten relay or analog outputs. The C450CRN-1 control module is a Modbus RTU subordinate that exposes one holding-register image: module info, sensor types, offsets and live values (IEEE floats), sensor failure flags, output types and statuses, and a 13-register setup block per output (referenced sensor, on/off or setpoint/end point, delays, integration, failure mode).
This page lists 159 Modbus registers for the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module — 106 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Johnson Controls
- Model
- PENN System 450 with C450CRN-1 Modbus communications control module
- Equipment type
- Thermostat
- Registers
- 159 (106 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826
Integration notes: Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
Set address, baud, parity and stop bits on the C450CRN-1 Communications Setup screens, set the EOL switch on the end device, then read 40100-40110 to learn which outputs exist and poll sensor values (40301-40318) and output statuses (40201-40210). Change setpoints by writing SENS/ON/OFF (or SP/EP) and then any value to the output's Validate register.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Model ID | INT16 | Model ID check (24 = C450CRN) | Read |
| HR 99 | Number of System Outputs | INT16 | Number of outputs | Read |
| HR 300 | Sn-1 Value | FLOAT32 ABCD | Sn-1 sensed value (float) | Read |
| HR 302 | Sn-1 Failure State | INT16 | Sn-1 failure state | Read |
| HR 200 | Output 1 Status | INT16 | Output 1 status | Read |
| HR 1102 | Output 1 ON value (relay) / SP setpoint (analog) | FLOAT32 ABCD | Output 1 ON / setpoint | Read/write |
| HR 1104 | Output 1 OFF value (relay) / EP end point (analog) | FLOAT32 ABCD | Output 1 OFF / end point | Read/write |
| HR 1106 | Output 1 Validate setpoints | INT16 | Output 1 validate setpoint write | Read/write |
Enable Modbus control & writes
Use a C450CRN-1 control module (the only System 450 module with Modbus). In the module UI go to Communications Setup (COMM) and set Addr, bAUd, PAR and STOP.
Byte order & addressing
- Register numbers are 4xxxx: subtract 40001 for the PDU address.
- Floats span two registers, high word first.
- Setpoint writes are only validated when the Validate register (41n07) is written or all five setpoint registers have been written; invalid ON/OFF or SP/EP pairs (range or minimum differential) are rejected.
- Supported function codes: 3, 6 and 16 only.
Network setup
- Device address 1-247; baud 9600, 19200 or 38400; parity 0 none, 1 odd, 2 even; 1 or 2 stop bits (2 only with no parity).
- RS-485 terminals A'+, B'- and C' REF with shielded cable; set the EOL switch On only at the ends of the trunk.
Watch out for
- Outputs that report type 0 are not physically present; their setup registers have no effect.
- If a relay output references a binary-input sensor, its ON/OFF values are ignored.
- Changing a sensor type changes ranges and default setup values of the outputs that reference it.
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Model ID | INT16 | Read | 24 = C450CRN Modbus control module | ||||
| HR | 1doc 40002 | Network Image Version | Register map version. | INT16 | Read | ||||
| HR | 2doc 40003-40018 | Firmware Version | Up to 31 ASCII characters plus null. | STRING[32] | Read | ||||
| HR | 90doc 40091-40092 | CPU Temperature | FLOAT32 | ABCD | °F | Read | |||
| HR | 99doc 40100 | Number of System Outputs | 0-10. | INT16 | Read | ||||
| HR | 100doc 40101 | Output 1 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 101doc 40102 | Output 2 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 102doc 40103 | Output 3 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 103doc 40104 | Output 4 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 104doc 40105 | Output 5 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 105doc 40106 | Output 6 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 106doc 40107 | Output 7 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 107doc 40108 | Output 8 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 108doc 40109 | Output 9 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 109doc 40110 | Output 10 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 200doc 40201 | Output 1 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 201doc 40202 | Output 2 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 202doc 40203 | Output 3 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 203doc 40204 | Output 4 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 204doc 40205 | Output 5 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 205doc 40206 | Output 6 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 206doc 40207 | Output 7 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 207doc 40208 | Output 8 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 208doc 40209 | Output 9 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 209doc 40210 | Output 10 Status | Relay: 1 = On, 0 = Off. Analog: % of total signal strength (0-100). | INT16 | Read | ||||
| HR | 300doc 40301-40302 | Sn-1 Value | Sensed value; units per the sensor type. Binary input: 0.0 open, 1.0 closed. | FLOAT32 | ABCD | Read | |||
| HR | 302doc 40303 | Sn-1 Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 303doc 40304-40305 | Sn-2 Value | Sensed value; units per the sensor type. Binary input: 0.0 open, 1.0 closed. | FLOAT32 | ABCD | Read | |||
| HR | 305doc 40306 | Sn-2 Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 306doc 40307-40308 | Sn-3 Value | Sensed value; units per the sensor type. Binary input: 0.0 open, 1.0 closed. | FLOAT32 | ABCD | Read | |||
| HR | 308doc 40309 | Sn-3 Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 309doc 40310-40311 | Sn-d Value | Sn-1 minus Sn-2. | FLOAT32 | ABCD | Read | |||
| HR | 311doc 40312 | Sn-d Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 312doc 40313-40314 | HI-2 Value | Highest of Sn-1 and Sn-2. | FLOAT32 | ABCD | Read | |||
| HR | 314doc 40315 | HI-2 Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 315doc 40316-40317 | HI-3 Value | Highest of Sn-1, Sn-2 and Sn-3. | FLOAT32 | ABCD | Read | |||
| HR | 317doc 40318 | HI-3 Failure State | INT16 | Read | 0 = Operational; 1 = Failed | ||||
| HR | 400doc 40401-40404 | Sn-1 Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 404doc 40405-40408 | Sn-2 Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 408doc 40409-40412 | Sn-3 Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 412doc 40413-40416 | Sn-d Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 416doc 40417-40420 | HI-2 Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 420doc 40421-40424 | HI-3 Units | Units text, up to 7 characters plus null. | STRING[8] | Read | ||||
| HR | 500doc 40501 | Sn-1 Sensor Type | INT16 | Read/write | 0 = No sensor type; 1 = °F standard temperature; 2 = °C standard temperature; 3 = rH humidity; 4 = P 0.5 (inwc); 5 = P 8 (bar); 6 = P 10 (inwc); 7 = P 15 (bar); 8 = P 30 (bar); 9 = P 50 (bar); 10 = P 100 (psi); 11 = P 500 (psi); 12 = P 750 (psi); 13 = P 200 (psi); 14 = P 2.5 (inwc); 15 = P 5 (inwc); 16 = HI°F high temperature; 17 = HI°C high temperature; 18 = P 110 (psi); 19 = bin (binary input, dry contact); 20 = P 0.25 (inwc) | ||||
| HR | 501doc 40502-40503 | Sn-1 Temperature Offset | Temperature sensors only: ±5 °F in 1° steps or ±2.5 °C in 0.5° steps. | FLOAT32 | ABCD | Read/write | |||
| HR | 503doc 40504 | Sn-2 Sensor Type | INT16 | Read/write | 0 = No sensor type; 1 = °F standard temperature; 2 = °C standard temperature; 3 = rH humidity; 4 = P 0.5 (inwc); 5 = P 8 (bar); 6 = P 10 (inwc); 7 = P 15 (bar); 8 = P 30 (bar); 9 = P 50 (bar); 10 = P 100 (psi); 11 = P 500 (psi); 12 = P 750 (psi); 13 = P 200 (psi); 14 = P 2.5 (inwc); 15 = P 5 (inwc); 16 = HI°F high temperature; 17 = HI°C high temperature; 18 = P 110 (psi); 19 = bin (binary input, dry contact); 20 = P 0.25 (inwc) | ||||
| HR | 504doc 40505-40506 | Sn-2 Temperature Offset | Temperature sensors only: ±5 °F in 1° steps or ±2.5 °C in 0.5° steps. | FLOAT32 | ABCD | Read/write | |||
| HR | 506doc 40507 | Sn-3 Sensor Type | INT16 | Read/write | 0 = No sensor type; 1 = °F standard temperature; 2 = °C standard temperature; 3 = rH humidity; 4 = P 0.5 (inwc); 5 = P 8 (bar); 6 = P 10 (inwc); 7 = P 15 (bar); 8 = P 30 (bar); 9 = P 50 (bar); 10 = P 100 (psi); 11 = P 500 (psi); 12 = P 750 (psi); 13 = P 200 (psi); 14 = P 2.5 (inwc); 15 = P 5 (inwc); 16 = HI°F high temperature; 17 = HI°C high temperature; 18 = P 110 (psi); 19 = bin (binary input, dry contact); 20 = P 0.25 (inwc) | ||||
| HR | 507doc 40508-40509 | Sn-3 Temperature Offset | Temperature sensors only: ±5 °F in 1° steps or ±2.5 °C in 0.5° steps. | FLOAT32 | ABCD | Read/write | |||
| HR | 1100doc 41101 | Output 1 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1101doc 41102 | Output 1 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1102doc 41103-41104 | Output 1 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1104doc 41105-41106 | Output 1 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1106doc 41107 | Output 1 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1107doc 41108 | Output 1 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1108doc 41109 | Output 1 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1109doc 41110 | Output 1 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1110doc 41111 | Output 1 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1111doc 41112 | Output 1 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1112doc 41113 | Output 1 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1200doc 41201 | Output 2 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1201doc 41202 | Output 2 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1202doc 41203-41204 | Output 2 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1204doc 41205-41206 | Output 2 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1206doc 41207 | Output 2 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1207doc 41208 | Output 2 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1208doc 41209 | Output 2 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1209doc 41210 | Output 2 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1210doc 41211 | Output 2 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1211doc 41212 | Output 2 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1212doc 41213 | Output 2 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1300doc 41301 | Output 3 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1301doc 41302 | Output 3 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1302doc 41303-41304 | Output 3 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1304doc 41305-41306 | Output 3 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1306doc 41307 | Output 3 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1307doc 41308 | Output 3 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1308doc 41309 | Output 3 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1309doc 41310 | Output 3 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1310doc 41311 | Output 3 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1311doc 41312 | Output 3 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1312doc 41313 | Output 3 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1400doc 41401 | Output 4 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1401doc 41402 | Output 4 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1402doc 41403-41404 | Output 4 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1404doc 41405-41406 | Output 4 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1406doc 41407 | Output 4 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1407doc 41408 | Output 4 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1408doc 41409 | Output 4 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1409doc 41410 | Output 4 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1410doc 41411 | Output 4 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1411doc 41412 | Output 4 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1412doc 41413 | Output 4 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1500doc 41501 | Output 5 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1501doc 41502 | Output 5 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1502doc 41503-41504 | Output 5 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1504doc 41505-41506 | Output 5 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1506doc 41507 | Output 5 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1507doc 41508 | Output 5 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1508doc 41509 | Output 5 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1509doc 41510 | Output 5 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1510doc 41511 | Output 5 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1511doc 41512 | Output 5 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1512doc 41513 | Output 5 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1600doc 41601 | Output 6 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1601doc 41602 | Output 6 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1602doc 41603-41604 | Output 6 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1604doc 41605-41606 | Output 6 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1606doc 41607 | Output 6 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1607doc 41608 | Output 6 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1608doc 41609 | Output 6 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1609doc 41610 | Output 6 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1610doc 41611 | Output 6 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1611doc 41612 | Output 6 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1612doc 41613 | Output 6 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1700doc 41701 | Output 7 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1701doc 41702 | Output 7 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1702doc 41703-41704 | Output 7 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1704doc 41705-41706 | Output 7 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1706doc 41707 | Output 7 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1707doc 41708 | Output 7 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1708doc 41709 | Output 7 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1709doc 41710 | Output 7 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1710doc 41711 | Output 7 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1711doc 41712 | Output 7 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1712doc 41713 | Output 7 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1800doc 41801 | Output 8 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1801doc 41802 | Output 8 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1802doc 41803-41804 | Output 8 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1804doc 41805-41806 | Output 8 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1806doc 41807 | Output 8 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1807doc 41808 | Output 8 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1808doc 41809 | Output 8 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1809doc 41810 | Output 8 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1810doc 41811 | Output 8 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1811doc 41812 | Output 8 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1812doc 41813 | Output 8 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 1900doc 41901 | Output 9 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 1901doc 41902 | Output 9 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 1902doc 41903-41904 | Output 9 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1904doc 41905-41906 | Output 9 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 1906doc 41907 | Output 9 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 1907doc 41908 | Output 9 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1908doc 41909 | Output 9 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 1909doc 41910 | Output 9 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 1910doc 41911 | Output 9 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 1911doc 41912 | Output 9 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 1912doc 41913 | Output 9 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails | |||
| HR | 2000doc 42001 | Output 10 Type | INT16 | Read | 0 = No output present; 1 = Relay output; 2 = Analog output | ||||
| HR | 2001doc 42002 | Output 10 SENS (referenced sensor) | INT16 | Read/write | 0 = No sensor; 1 = Sn-1; 2 = Sn-2; 3 = Sn-3; 4 = Sn-d (Sn-1 minus Sn-2); 5 = HI-2 (highest of Sn-1/Sn-2); 6 = HI-3 (highest of Sn-1/Sn-2/Sn-3) | ||||
| HR | 2002doc 42003-42004 | Output 10 ON value (relay) / SP setpoint (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 2004doc 42005-42006 | Output 10 OFF value (relay) / EP end point (analog) | FLOAT32 | ABCD | Read/write | ||||
| HR | 2006doc 42007 | Output 10 Validate setpoints | Write any value to submit SENS/ON/OFF or SP/EP for validation. | INT16 | Read/write | ||||
| HR | 2007doc 42008 | Output 10 ONd on delay (relay) / OSP % signal at setpoint (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 2008doc 42009 | Output 10 OFFd off delay (relay) / OEP % signal at end point (analog) | Relay: 0-300 s. | INT16 | Read/write | ||||
| HR | 2009doc 42010 | Output 10 ONT min on time (relay) / I-C integration constant (analog) | Relay: 0-300 s. Analog: 0 = P only; 1-6 = 1 h, 30, 15, 5, 2, 1 min. | INT16 | Read/write | ||||
| HR | 2010doc 42011 | Output 10 OFFT min off time (relay) / UP-R update rate (analog) | Relay: 0-300 s. Analog: 1-240 s. | INT16 | Read/write | ||||
| HR | 2011doc 42012 | Output 10 SNF sensor failure mode (relay) / bNd dead band (analog) | Relay SNF: 0 on / 1 off on sensor failure. Analog: dead band 0-50 %. | INT16 | Read/write | ||||
| HR | 2012doc 42013 | Output 10 SNF sensor failure mode (analog) | Analog outputs only; unused for relay outputs. | INT16 | Read/write | 0 = Output on if sensor fails; 1 = Output off if sensor fails |
Notes on this map
- Source is Johnson Controls' own documentation portal; the same bulletin is offered there as a PDF attachment (LIT-12011826 .pdf).
- Float word order: the bulletin says floats are stored most significant byte first and that the Niagara Modbus driver calls this Order3210, i.e. fully big-endian: high word in the lower register (ABCD).
- 'Integer 16' is defined as a signed 16-bit integer, so all single registers are INT16.
- Sensor values, ON/OFF and SP/EP floats are in the units of the referenced sensor's Sensor Type (Table 21 in the bulletin); the Sn-x Units string registers give the units text.
- Output setup registers 41n01-41n13 (n = output number, output 10 uses 42001-42013) mean different things for relay and analog outputs; both meanings are given in each name. The bulletin lists the analog SNF in 41n13 and the analog dead band in 41n12.
- Serial defaults are not stated: address 1-247, baud 9600/19200/38400, parity none/odd/even and 1 or 2 stop bits (2 only with no parity) are set in the module UI.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
What Modbus registers does the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module have?
This map lists 159 registers: 159 holding registers. 106 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The bulletin lists 4xxxx holding registers and says the address in the request frame is the register address minus 40001 (40001 -> 0).
What byte order does the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module?
Start with HR 0 Model ID (Model ID check (24 = C450CRN)); HR 99 Number of System Outputs (Number of outputs); HR 300 Sn-1 Value (Sn-1 sensed value (float)); HR 302 Sn-1 Failure State (Sn-1 failure state); HR 200 Output 1 Status (Output 1 status); HR 1102 Output 1 ON value (relay) / SP setpoint (analog) (Output 1 ON / setpoint); HR 1104 Output 1 OFF value (relay) / EP end point (analog) (Output 1 OFF / end point); HR 1106 Output 1 Validate setpoints (Output 1 validate setpoint write).
How do I enable Modbus control of the Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module?
Use a C450CRN-1 control module (the only System 450 module with Modbus). In the module UI go to Communications Setup (COMM) and set Addr, bAUd, PAR and STOP.
Where is the official Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module Modbus documentation?
The source is System 450 Series Modular Control Systems with Communications Control Modules Technical Bulletin (LIT-12011826), revision 2021-01-14, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/System-450-Series-Modular-Control-Systems-with-Communications-Control-Modules-Technical-Bulletin.
More Johnson Controls Modbus register maps
- Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Other hvac equipment register maps
- Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC
All hvac equipment Modbus register maps →
Source: System 450 Series Modular Control Systems with Communications Control Modules Technical Bulletin · LIT-12011826 · rev. 2021-01-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.